ABB ACH580 Modbus register map

HVAC drive, HVAC control program, over the embedded fieldbus (EFB, Modbus RTU)

  • Official
  • 1,888 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
1845 holding registers, 22 coils, 21 discrete inputs
Groups
61
Translation tables
12
Revision
1 · 2026-11-10
Firmware
ACH580 HVAC control program (the version the manual applies to)
Added
()
File
maps/abb/ach580.mbmap.json · 398 KB · history
SHA-256
420da7a7740bce282d711c03e3a0d4f9632e4edcc92f0df6eba33e97886eb23b
Manufacturer
abb.com

Sources and notes

  • ACH580 HVAC control program firmware manual · version 3AXD50000027537 revision J, 2026-02-23
    chapter Modbus RTU control through the embedded fieldbus interface (EFB), chapter Parameters and Additional parameter data

Source: ABB, "ACH580 HVAC control program firmware manual", 3AXD50000027537 revision J (2026-02-23); https://library.abb.com/d/3AXD50000027537

  • Embedded fieldbus (terminals on the control unit), 58.01 Protocol enable = Modbus RTU. Defaults: node address 1, 19.2 kbit/s, 8 even 1.
  • Addresses are 1-based register numbers (400001 = 1). Parameters use 58.33 Addressing mode = Mode 0, the default.
  • Real-type parameters are read as 32-bit values (register 420000 + 200 × group + 2 × index) with the FbEq32 scaling of the chapter Additional parameter data; their 16-bit copies at 400000 + 100 × group + index use the FbEq16 scalings of the Parameters chapter (several depend on group 46) and are not in this map.
  • 32-bit values use 58.34 Word order = LO-HI (the default): low word first.
  • Lists, sources (Analog src, Binary src), packed Boolean words (PB) and data parameters are read as 16-bit values (400000 + 100 × group + index). Bits of packed Boolean words are listed where the manual names them; reserved bits are left out.
  • Parameters with an index above 99 (for example 01.102 Line current of the ACH580-31 and -34, or 58.101 Data I/O 1) are only reachable with addressing mode 1 or 2 and are not in this map.
  • Date, time and duration parameters (for example 34.12 Timer 1 start time, 34.72 Exception 1 start) have no FbEq16 or FbEq32 scaling in the manual (shown as a dash) and are not in this map.
  • 23.33, 40.41, 40.42, 41.41, 41.42 and 83.04 are listed in the chapter Additional parameter data but their entries are missing from the parameter listing; they have no default or selection labels here. 47.05-47.08 and 47.25-47.28 are in the parameter listing but missing from the additional data and are taken to have the type and scaling of their neighbours (47.04, 47.24).
  • Some units depend on settings: power in kW or hp and torque in N·m or lb·ft (96.16), temperatures in °C or °F, analog values in mA or V, process values in the PID units of group 40. Where the unit is not fixed it is given in the description.
  • Registers 1-14 carry the data selected by 58.101-58.114; the defaults are shown. Coils and discrete inputs follow the ABB Drives profile (58.25 = ABB Drives); coils 9 and 10 (jogging) are not used by the ACH580.
  • Parameters without a default value in the manual (actual signals, status words) are read-only; the others are writable within the range given by write_min and write_max. Defaults that differ between 50 Hz and 60 Hz supply (95.20 bit 0) are shown as written in the manual.
  • 96.78 appears twice in the manual (550 Compatibility mode, a list 0...2, and Legacy Modbus mapping, disable/enable) with different selections and is not in this map.
  • Parameters of the ACH580-31 and ACH580-34 supply unit (groups 94 and others marked as only visible for those types) appear only where their index is 99 or lower.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint16 RW Default CW 16bit; selected by 58.101
HR 2 int16 RW Default Ref1 16bit; selected by 58.102; scaled by 58.26 and group 46
HR 3 int16 RW Default Ref2 16bit; selected by 58.103; scaled by 58.27 and group 46
HR 4 uint16 R Default SW 16bit; selected by 58.104
HR 5 int16 R Default Act1 16bit; selected by 58.105; scaled by 58.28 and group 46
HR 6 int16 R Default Act2 16bit; selected by 58.106; scaled by 58.29 and group 46
HR 7 uint16 RW Selected by 58.107
HR 8 uint16 RW Selected by 58.108
HR 9 uint16 RW Selected by 58.109
HR 10 uint16 RW Selected by 58.110
HR 11 uint16 RW Selected by 58.111
HR 12 uint16 RW Selected by 58.112
HR 13 uint16 RW Selected by 58.113
HR 14 uint16 RW Selected by 58.114
HR 90 uint16 W Clears registers 91-95
HR 91 uint16 R Function code of the last failed query
HR 92 uint16 R Set with exception code 04h
HR 93 uint16 R
HR 94 uint16 R
HR 95 uint16 R
CO 1 bool RW ABB Drives profile
CO 2 bool RW ABB Drives profile
CO 3 bool RW ABB Drives profile
CO 4 bool RW ABB Drives profile
CO 5 bool RW ABB Drives profile
CO 6 bool RW ABB Drives profile
CO 7 bool RW ABB Drives profile
CO 8 bool RW ABB Drives profile
CO 11 bool RW ABB Drives profile
CO 12 bool RW ABB Drives profile
CO 13 bool RW ABB Drives profile
CO 14 bool RW ABB Drives profile
CO 15 bool RW ABB Drives profile
CO 16 bool RW ABB Drives profile
CO 33 bool RW 10.99 RO/DIO control word bit 0
CO 34 bool RW 10.99 RO/DIO control word bit 1
CO 35 bool RW 10.99 RO/DIO control word bit 2
CO 36 bool RW 10.99 RO/DIO control word bit 3
CO 37 bool RW 10.99 RO/DIO control word bit 4
CO 38 bool RW 10.99 RO/DIO control word bit 5
CO 39 bool RW 10.99 RO/DIO control word bit 6
CO 40 bool RW 10.99 RO/DIO control word bit 8
DI 1 bool R ABB Drives profile
DI 2 bool R ABB Drives profile
DI 3 bool R ABB Drives profile
DI 4 bool R ABB Drives profile
DI 5 bool R ABB Drives profile
DI 6 bool R ABB Drives profile
DI 7 bool R ABB Drives profile
DI 8 bool R ABB Drives profile
DI 9 bool R ABB Drives profile
DI 10 bool R ABB Drives profile
DI 11 bool R ABB Drives profile
DI 12 bool R ABB Drives profile
DI 13 bool R ABB Drives profile
DI 14 bool R ABB Drives profile
DI 15 bool R ABB Drives profile
DI 33 bool R 10.02 bit 0
DI 34 bool R 10.02 bit 1
DI 35 bool R 10.02 bit 2
DI 36 bool R 10.02 bit 3
DI 37 bool R 10.02 bit 4
DI 38 bool R 10.02 bit 5
HR 20202 int32 CDAB R rpm ×0.01
HR 20204 int32 CDAB R rpm ×0.01
HR 20206 int32 CDAB R % ×0.01
HR 20212 int32 CDAB R Hz ×0.01
HR 20214 uint32 CDAB R A ×0.01
HR 20216 uint32 CDAB R % ×0.1
HR 20218 uint32 CDAB R % ×0.1
HR 20220 int32 CDAB R % ×0.1
HR 20222 uint32 CDAB R V ×0.01
HR 20226 uint32 CDAB R V
HR 20228 int32 CDAB R kW ×0.01
HR 20230 int32 CDAB R % ×0.01
HR 20234 int32 CDAB R ×0.01 Unit: kW or hp
HR 20236 uint32 CDAB R GWh
HR 20238 uint32 CDAB R MWh
HR 20240 uint32 CDAB R kWh
HR 20248 uint32 CDAB R %
HR 20260 uint32 CDAB R ×0.001 Unit: N·m or lb·ft
HR 20262 int32 CDAB R ×0.1 Unit: °C or °F
HR 20300 uint32 CDAB R kWh ×0.01
HR 20302 uint32 CDAB R kWh ×0.01
HR 20304 uint32 CDAB R kWh ×0.01
HR 20306 uint32 CDAB R kWh ×0.01
HR 20308 int32 CDAB R kWh
HR 20310 uint32 CDAB R GWh
HR 20312 uint32 CDAB R MWh
HR 20314 uint32 CDAB R kWh
HR 20316 int32 CDAB R kWh
HR 20322 uint32 CDAB R rpm ×0.01
HR 20324 uint32 CDAB R % ×0.01
HR 20326 uint32 CDAB R Hz ×0.01
HR 20328 uint32 CDAB R % ×0.1
HR 20330 uint32 CDAB R kW ×0.01
HR 20332 uint32 CDAB R % ×0.01
HR 20336 uint32 CDAB R ×0.01 Unit: kW or hp
HR 20344 uint32 CDAB R A ×0.01
HR 20346 uint32 CDAB R A ×0.01