MBMap Registry
  1. Devices
  2. Accuenergy
  3. Acuvim-L

Accuenergy Acuvim-L Modbus register map

Also covers Acuvim-AL, Acuvim-BL, Acuvim-CL, Acuvim-DL, Acuvim-EL, Acuvim-KL

Acuvim-L series multifunction power meters (AL, BL, CL, DL, EL, KL), RS485 Modbus RTU

  • Official
  • 555 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
555 holding registers
Groups
13
Revision
2 · 2026-10-17
Added
()
File
maps/accuenergy/acuvim-l.mbmap.json · 98 KB · history
SHA-256
35852483fbc64e8fba8aa621739667288f617c24385a6848d23e1a36ff60f82a
Manufacturer
accuenergy.com

Sources and notes

Source: Accuenergy, "Acuvim-L Series Power Meter User's Manual" 1030E2202, V2.0.3 (December 2025), section 4.5

  • Acuvim-L series (AL, BL, CL, DL, EL, KL); not every model has every value (THD and harmonics need the higher models, TOU the EL/KL).
  • FC03 reads, FC16 writes; big endian, high word first. The primary values from 0x600 are floats in V, A, W, var and VA.
  • The integer basic values from 0x130 are on the secondary side: multiply voltages by PT1/PT2, currents by CT1/CT2 and powers by both.
  • Energies are counts of 0.1 kWh (kvarh, kVAh). Max/min values carry their time as year, month, day, hour, minute and second bytes.
  • The TOU season, schedule and holiday tables from 0x820 are in the manual and not in this map.
AreaAddressNameTypeAccessUnitScaleDescription
HR 304 uint16 R Hz ×0.01
HR 305 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 306 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 307 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 308 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 309 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 310 uint16 R V ×0.1 Multiply by PT1/PT2 for the primary value
HR 311 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 312 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 313 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 314 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 315 int16 R W Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 316 int16 R W Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 317 int16 R W Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 318 int16 R W Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 319 int16 R var Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 320 int16 R var Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 321 int16 R var Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 322 int16 R var Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 323 uint16 R VA Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 324 int16 R ×0.001
HR 325 int16 R ×0.001
HR 326 int16 R ×0.001
HR 327 int16 R ×0.001
HR 328 uint16 R % ×0.1
HR 329 uint16 R % ×0.1
HR 330 uint16 R
HR 331 int16 R VA Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 332 int16 R VA Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 333 int16 R VA Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 335 int16 R VA Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 336 int16 R W Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 337 int16 R var Multiply by (PT1/PT2)×(CT1/CT2) for the primary value
HR 338 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 339 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 340 uint16 R A ×0.001 Multiply by CT1/CT2 for the primary value
HR 1536 float32 ABCD R Hz
HR 1538 float32 ABCD R V
HR 1540 float32 ABCD R V
HR 1542 float32 ABCD R V
HR 1544 float32 ABCD R V
HR 1546 float32 ABCD R V
HR 1548 float32 ABCD R V
HR 1550 float32 ABCD R A
HR 1552 float32 ABCD R A
HR 1554 float32 ABCD R A
HR 1556 float32 ABCD R A
HR 1558 float32 ABCD R W
HR 1560 float32 ABCD R W
HR 1562 float32 ABCD R W
HR 1564 float32 ABCD R W
HR 1566 float32 ABCD R var
HR 1568 float32 ABCD R var
HR 1570 float32 ABCD R var
HR 1572 float32 ABCD R var
HR 1574 float32 ABCD R VA
HR 1576 float32 ABCD R
HR 1578 float32 ABCD R
HR 1580 float32 ABCD R
HR 1582 float32 ABCD R
HR 1584 float32 ABCD R Ratio, 0-1
HR 1586 float32 ABCD R Ratio, 0-1
HR 1590 float32 ABCD R VA
HR 1592 float32 ABCD R VA
HR 1594 float32 ABCD R VA
HR 1598 float32 ABCD R VA
HR 1600 float32 ABCD R W
HR 1602 float32 ABCD R var
HR 1604 float32 ABCD R A
HR 1606 float32 ABCD R A
HR 1608 float32 ABCD R A
HR 1024 uint16 R % ×0.01
HR 1025 uint16 R % ×0.01
HR 1026 uint16 R % ×0.01
HR 1027 uint16 R % ×0.01
HR 1028 uint16 R % ×0.01
HR 1029 uint16 R % ×0.01
HR 1030 uint16 R % ×0.01
HR 1031 uint16 R % ×0.01
HR 1032 uint16 R % ×0.01
HR 1033 uint16 R % ×0.01
HR 1034 uint16 R % ×0.01
HR 1035 uint16 R % ×0.01
HR 1036 uint16 R % ×0.01
HR 1037 uint16 R % ×0.01
HR 1038 uint16 R % ×0.01
HR 1039 uint16 R % ×0.01
HR 1040 uint16 R % ×0.01
HR 1041 uint16 R % ×0.01
HR 1042 uint16 R % ×0.01
HR 1043 uint16 R % ×0.01
HR 1044 uint16 R % ×0.01
HR 1045 uint16 R % ×0.01
HR 1046 uint16 R % ×0.01
HR 1047 uint16 R % ×0.01
HR 1048 uint16 R % ×0.01
HR 1049 uint16 R % ×0.01
HR 1050 uint16 R % ×0.01
HR 1051 uint16 R % ×0.01
HR 1052 uint16 R % ×0.01

Help improve this map