MBMap Registry
  1. Devices
  2. Acrel
  3. ACR10RH-DxxT(R)E3 / E4

Acrel ACR10RH-DxxT(R)E3 / E4 Modbus register map

Also covers ACR10RH-DxxT(R)E4, ACR10R-D16TE4

Three-phase harmonic meters with split-core CTs or Rogowski coils (ACR10RH-DxxT(R)E3/E4), RS485 Modbus RTU

  • Official
  • 352 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
38400 8N1 · 38400 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
352 holding registers
Groups
12
Translation tables
2
Revision
2 · 2026-10-17
Added
()
File
maps/acrel/acr10rh.mbmap.json · 59 KB · history
SHA-256
718b9a3ae7046f966dba42831776f7019eb93180c559c7b532e194dfef62f0ba
Manufacturer
acrel-electric.com

Sources and notes

Source: Acrel, "External Roche Coil and Switched Transformer Harmonic Meter - Installation and operation instruction" V1.5, section 7.4-7.5

  • Acrel ACR10RH-DxxT(R)E3 and E4 harmonic meters (T: split-core CT, TR: Rogowski coil). The older name ACR10R is kept in the models.
  • Addresses are register numbers as sent on the bus. FC03 reads, FC10 writes; 32-bit values are high word first.
  • Measurements and energies are on the secondary side: multiply voltages by the voltage ratio (14), currents by the current ratio (16) and powers and energies by the power ratio (18), all float32.
  • The clock is BCD: a register reading 0x0026 means 26.
  • Event records, waveform samples, alarm and transmission settings and the second tariff calendar (from 1200) are in the manual and left out here; history for September-December is not listed in the manual.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 RW
HR 1 uint16 RW
HR 2 uint16 RW
HR 3 uint16 RW
HR 4 uint16 RW
HR 5 uint16 RW
HR 6 uint16 RW kV ×0.01
HR 7 uint16 RW A
HR 8 uint16 RW s 0 = always on
HR 9 uint16 RW s ×0.01 0 = level control
HR 10 uint16 RW s ×0.01 0 = level control
HR 11 uint16 RW s ×0.01 0 = level control
HR 12 uint16 RW s ×0.01 0 = level control
HR 14 float32 ABCD R Primary/secondary coefficient for voltages
HR 16 float32 ABCD R Primary/secondary coefficient for currents
HR 18 float32 ABCD R Primary/secondary coefficient for powers and energies
HR 21 uint16 RW Written as one 3-register period
HR 22 uint16 RW
HR 23 uint16 RW
HR 24 uint16 RW
HR 25 uint16 RW
HR 26 uint16 RW
HR 27 uint16 RW
HR 28 uint16 RW
HR 29 uint16 RW
HR 30 uint16 RW
HR 31 uint16 RW
HR 32 uint16 RW
HR 33 uint16 RW
HR 34 uint16 RW
HR 35 uint16 RW
HR 36 uint16 RW
HR 37 uint16 RW
HR 38 uint16 RW
HR 39 uint16 RW
HR 40 uint16 RW
HR 41 uint16 RW
HR 42 uint16 RW
HR 43 uint16 RW
HR 44 uint16 RW
HR 53 uint16 R
HR 54 uint16 R
HR 55 uint16 R
HR 56 uint16 R
HR 57 uint16 R
HR 58 uint16 R
HR 59 uint16 R
HR 60 uint16 R
HR 61 uint16 RW
HR 62 uint16 RW
HR 63 uint16 RW
HR 64 uint16 RW
HR 128 uint16 RW BCD; write all six registers together with FC16
HR 129 uint16 RW BCD
HR 130 uint16 RW BCD
HR 131 uint16 RW BCD
HR 132 uint16 RW BCD
HR 133 uint16 RW BCD
HR 242 uint16 R A ×0.001 × current ratio (16) for the primary value
HR 243 uint16 R V ×0.1 × voltage ratio (14) for the primary value
HR 244 uint16 R V ×0.1
HR 245 uint16 R V ×0.1
HR 246 uint16 R V ×0.1
HR 247 uint16 R V ×0.1
HR 248 uint16 R V ×0.1
HR 249 uint16 R A ×0.001 × current ratio (16) for the primary value
HR 250 uint16 R A ×0.001
HR 251 uint16 R A ×0.001
HR 252 uint16 R Hz ×0.01
HR 253 int32 ABCD R W ×0.01 × power ratio (18) for the primary value
HR 255 int32 ABCD R W ×0.01
HR 257 int32 ABCD R W ×0.01
HR 259 int32 ABCD R W ×0.01
HR 261 int32 ABCD R var ×0.01
HR 263 int32 ABCD R var ×0.01
HR 265 int32 ABCD R var ×0.01
HR 267 int32 ABCD R var ×0.01
HR 269 uint32 ABCD R VA ×0.01
HR 271 uint32 ABCD R VA ×0.01
HR 273 uint32 ABCD R VA ×0.01
HR 275 int32 ABCD R VA ×0.01
HR 277 int16 R ×0.001
HR 278 int16 R ×0.001
HR 279 int16 R ×0.001
HR 280 int16 R ×0.001
HR 287 uint16 R ×0.01
HR 288 uint16 R ×0.01
HR 289 uint16 R ×0.01
HR 299 uint16 R % ×0.1
HR 300 uint16 R % ×0.1
HR 301 uint32 ABCD R kW ×0.01
HR 333 uint32 ABCD R kWh ×0.01 × power ratio (18) for the primary value
HR 335 uint32 ABCD R kWh ×0.01
HR 337 uint32 ABCD R kWh ×0.01
HR 339 uint32 ABCD R kWh ×0.01
HR 341 uint32 ABCD R kWh ×0.01
HR 343 uint32 ABCD R kWh ×0.01
HR 345 uint32 ABCD R kWh ×0.01
HR 347 uint32 ABCD R kWh ×0.01
HR 349 uint32 ABCD R kWh ×0.01

Help improve this map