MBMap Registry
  1. Devices
  2. Advantech
  3. ADAM-6017

Advantech ADAM-6017 Modbus register map

Also covers ADAM-6017-D

8-channel isolated analog input module with 2 digital outputs, Modbus TCP

  • Official
  • 152 registers
  • Modbus TCP
  • Revision 2 · 2026-10-17
  • Identity: model

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1
TCP port
502
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
98 holding registers, 54 coils
Groups
9
Translation tables
1
Revision
2 · 2026-10-17
Added
()
File
maps/advantech/adam-6017.mbmap.json · 20 KB · history
SHA-256
48793135045da5dcdb59e24ebe7ce8434dbf8fc144e224f5672a31dbb5403989
Manufacturer
advantech.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Module name 1 holding 211 uint16 0x6017 = ADAM-6017

Sources and notes

Source: Advantech, "ADAM-6000 Series User Manual", Edition 9, Appendix B.2 (I/O Modbus mapping tables)

  • Addresses are the Modicon numbers of the manual (00001 = coil 1, 40001 = holding register 1).
  • 32-bit counters and pulse settings are low word first (the manual: counter = (40002) × 65536 + (40001)).
  • The floats are in the module's engineering units; the manual does not give their word order (this map uses the counters' low word first).
  • Some registers (floats, GCL, diagnostics) need the CE or D version of the module.
AreaAddressNameTypeAccessUnitScaleDescription
CO 17 bool RW
CO 18 bool RW
CO 101 bool RW
CO 102 bool RW
CO 103 bool RW
CO 104 bool RW
CO 105 bool RW
CO 106 bool RW
CO 107 bool RW
CO 108 bool RW
CO 109 bool RW
CO 111 bool RW
CO 112 bool RW
CO 113 bool RW
CO 114 bool RW
CO 115 bool RW
CO 116 bool RW
CO 117 bool RW
CO 118 bool RW
CO 119 bool RW
CO 121 bool R
CO 122 bool R
CO 123 bool R
CO 124 bool R
CO 125 bool R
CO 126 bool R
CO 127 bool R
CO 128 bool R
CO 131 bool R
CO 132 bool R
CO 133 bool R
CO 134 bool R
CO 135 bool R
CO 136 bool R
CO 137 bool R
CO 138 bool R
CO 139 bool R
CO 141 bool R
CO 142 bool R
CO 143 bool R
CO 144 bool R
CO 145 bool R
CO 146 bool R
CO 147 bool R
CO 148 bool R
CO 149 bool R
HR 1 uint16 R Raw value of the range set by the type code
HR 2 uint16 R
HR 3 uint16 R
HR 4 uint16 R
HR 5 uint16 R
HR 6 uint16 R
HR 7 uint16 R
HR 8 uint16 R
HR 9 uint16 R
HR 11 uint16 R
HR 12 uint16 R
HR 13 uint16 R
HR 14 uint16 R
HR 15 uint16 R
HR 16 uint16 R
HR 17 uint16 R
HR 18 uint16 R
HR 19 uint16 R
HR 21 uint16 R
HR 22 uint16 R
HR 23 uint16 R
HR 24 uint16 R
HR 25 uint16 R
HR 26 uint16 R
HR 27 uint16 R
HR 28 uint16 R
HR 29 uint16 R
HR 31 float32 CDAB R CE/D version
HR 33 float32 CDAB R
HR 35 float32 CDAB R
HR 37 float32 CDAB R
HR 39 float32 CDAB R
HR 41 float32 CDAB R
HR 43 float32 CDAB R
HR 45 float32 CDAB R
HR 47 float32 CDAB R
HR 51 float32 CDAB R
HR 53 float32 CDAB R
HR 55 float32 CDAB R
HR 57 float32 CDAB R
HR 59 float32 CDAB R
HR 61 float32 CDAB R
HR 63 float32 CDAB R
HR 65 float32 CDAB R
HR 67 float32 CDAB R
HR 71 float32 CDAB R
HR 73 float32 CDAB R
HR 75 float32 CDAB R
HR 77 float32 CDAB R
HR 79 float32 CDAB R
HR 81 float32 CDAB R
HR 83 float32 CDAB R
HR 85 float32 CDAB R
HR 87 float32 CDAB R

Help improve this map