Allen-Bradley Powermonitor 3000 Modbus register map

Also covers 1404 (Powermonitor 3000), 1404-M4, 1404-M5, 1404-M6, 1404-M8

Bulletin 1404 Powermonitor 3000 power monitors (M4, M5, M6, M8), native RS485 port with Modbus RTU

  • Official
  • 160 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1
Max read
100 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
63 holding registers, 97 input registers
Groups
12
Revision
2 · 2026-10-17
Added
()
File
maps/allen-bradley/powermonitor-3000.mbmap.json · 26 KB · history
SHA-256
ba389b106cd0f0c9204cc441db376a06777334558daa12e913ddcbf7ee66bd5c
Manufacturer
rockwellautomation.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Bulletin number input 601 int16 1404 = 1404 (Powermonitor 3000)
Firmware Application firmware input 613 int16

Sources and notes

Source: Rockwell Automation, "Powermonitor 3000 User Manual", publication 1404-UM001F-EN-P (November 2009), chapter 4 and appendix A

  • Modbus RTU on the native RS-485 or RS-232 port (auto-sense by default); Modbus ASCII and TCP are not supported. FC03/FC04 read, FC06/FC16 write, at most 100 registers per request.
  • Addresses are the one-based numbers of the manual: 30101 = input register 101, 40001 = holding register 1.
  • Floats are IEEE 754, big endian, high word first; a float must be read from its first (odd) address.
  • Energies are split into five signed parts (× 10^9, 10^6, 10^3, 1, 10^-3); add them for the value.
  • Configuration changes need the password in the first element of each table. Setpoints, logs, oscillography, TOU and the other tables of appendix A are left out.
AreaAddressNameTypeAccessUnitScaleDescription
IR 1 int16 R
IR 2 int16 R
IR 3 uint16 R Bit n = setpoint output flag n+1
IR 4 bool bit 0 R
IR 4 bool bit 1 R
IR 4 bool bit 2 R
IR 5 int16 R Rolls over after 29999
IR 6 int16 R
IR 101 float32 ABCD R A
IR 103 float32 ABCD R A
IR 105 float32 ABCD R A
IR 107 float32 ABCD R A
IR 109 float32 ABCD R V
IR 111 float32 ABCD R V
IR 113 float32 ABCD R V
IR 115 float32 ABCD R V
IR 117 float32 ABCD R V
IR 119 float32 ABCD R V
IR 121 float32 ABCD R V
IR 123 float32 ABCD R V
IR 125 float32 ABCD R Hz Last cycle; 0 or 999 when out of range
IR 127 float32 ABCD R
IR 201 float32 ABCD R A
IR 203 float32 ABCD R A
IR 205 float32 ABCD R A
IR 207 float32 ABCD R %
IR 209 float32 ABCD R V
IR 211 float32 ABCD R V
IR 213 float32 ABCD R %
IR 215 float32 ABCD R 0 none, 1 ABC, 2 ACB
IR 217 float32 ABCD R Hz
IR 219 float32 ABCD R 0 V1, 1 V2, 2 V3
IR 221 float32 ABCD R
IR 301 float32 ABCD R W
IR 303 float32 ABCD R W
IR 305 float32 ABCD R W
IR 307 float32 ABCD R W Signed to show direction
IR 309 float32 ABCD R var
IR 311 float32 ABCD R var
IR 313 float32 ABCD R var
IR 315 float32 ABCD R var
IR 317 float32 ABCD R VA
IR 319 float32 ABCD R VA
IR 321 float32 ABCD R VA
IR 323 float32 ABCD R VA
IR 325 float32 ABCD R
IR 401 float32 ABCD R A
IR 403 float32 ABCD R W
IR 405 float32 ABCD R var
IR 407 float32 ABCD R VA
IR 409 float32 ABCD R A
IR 411 float32 ABCD R W
IR 413 float32 ABCD R var
IR 415 float32 ABCD R VA
IR 417 float32 ABCD R min
IR 419 float32 ABCD R
IR 501 float32 ABCD R % + lead, - lag
IR 503 float32 ABCD R %
IR 505 float32 ABCD R %
IR 507 float32 ABCD R %
IR 509 float32 ABCD R %
IR 511 float32 ABCD R %
IR 513 float32 ABCD R %
IR 515 float32 ABCD R %
IR 517 float32 ABCD R %
IR 519 float32 ABCD R %
IR 521 float32 ABCD R %
IR 523 float32 ABCD R %
IR 525 float32 ABCD R
IR 1201 float32 ABCD R 1-9; selected through the harmonic analysis configuration table
IR 1203 float32 ABCD R %
IR 1205 float32 ABCD R %
IR 1207 float32 ABCD R
IR 1209 float32 ABCD R
IR 1211 float32 ABCD R M6/M8
IR 1213 float32 ABCD R M6/M8
IR 1215 float32 ABCD R M6/M8
IR 1217 float32 ABCD R M6/M8; -1 to 1
IR 1219 float32 ABCD R M6/M8
HR 501 int16 W Needed to clear or preset energy counters; reads -1
HR 502 int16 RW Bit field, see the manual section on clearing energy counters
HR 503 int16 R kWh ×1000000000 Add the five parts for the value; each part is -999 to 999
HR 504 int16 R kWh ×1000000
HR 505 int16 R kWh ×1000
HR 506 int16 R kWh
HR 507 int16 R kWh ×0.001
HR 508 int16 R kWh ×1000000000 Add the five parts for the value; each part is -999 to 999
HR 509 int16 R kWh ×1000000
HR 510 int16 R kWh ×1000
HR 511 int16 R kWh
HR 512 int16 R kWh ×0.001
HR 513 int16 R kWh ×1000000000 Add the five parts for the value; each part is -999 to 999
HR 514 int16 R kWh ×1000000
HR 515 int16 R kWh ×1000
HR 516 int16 R kWh
HR 517 int16 R kWh ×0.001
HR 518 int16 R kVAh ×1000000000 Add the five parts for the value; each part is -999 to 999
HR 519 int16 R kVAh ×1000000
HR 520 int16 R kVAh ×1000
HR 521 int16 R kVAh