Altus Optidrive Eco Modbus register map

Also covers ODV-3

HVAC variable speed drive: control word, speed reference, ramp time, status and trip code, output frequency, current, torque and power, inputs, DC bus, temperature and energy meters

  • Official
  • 32 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
115200 8N1 · 115200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
32 holding registers
Groups
6
Revision
1 · 2026-11-10
Added
()
File
maps/altus/optidrive-eco.mbmap.json · 7 KB · history
SHA-256
f9b5ed5a9a9d804c29d28d33ea52f0a846b6fa07c92a7732d13d3216b6116c4c
Manufacturer
altus.com.br

Sources and notes

  • Guia do usuário do Optidrive ECO · version Versão 3.12
    linked in issue #119; section 10.2 (Comunicações do Modbus RTU); written for firmware 2.51

Source: Guia do usuário do Optidrive ECO, Versão 3.12

  • Modbus RTU on the RJ45 connector (pin 7 RS485-, pin 8 RS485+), also used by BACnet MS/TP. FC03, FC06 and FC16 (registers 1 to 4 only). Registers are numbered from 1, as in the guide: masters that start at 0 must subtract 1.
  • Factory settings: address 1 (P5-01, 1 to 63; P5-16 allows 0 to 247), 115.2 kbit/s (P5-03), no parity and 1 stop bit (P5-04 = n-1). P5-04 also allows n-2, odd and even parity with one stop bit; P5-01, P5-03 and P5-04 cannot be changed over Modbus.
  • Registers 1 and 2 control the drive only when P1-12 = 4 (Modbus RTU) and no fieldbus module is fitted; register 4 needs fieldbus ramp control. Registers 6 to 35 can always be read. Register 3 is reserved.
  • Every parameter of groups 1 to 5 is also a register: its number is the parameter number (P1-01 is register 101). Values with a decimal point are sent multiplied by 10. Only P1-01 is listed here as an example.
  • Register 6: the low byte is the status byte, the high byte is the fault number. The guide's text for the pre-ramp speed reference (register 22) gives no scale; it is shown raw. Energy meters are two registers each (kWh and MWh parts) with no stated decimals. The guide is written for firmware 2.51.
  • Written from the user guide; this map has not been tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 bool bit 0 RW 1 = run, 0 = stop
HR 1 bool bit 1 RW 1 = stop with the second deceleration ramp
HR 1 bool bit 2 RW 1 = reset an active trip; set back to 0 after the fault clears
HR 1 bool bit 3 RW 1 = coast to stop
HR 2 uint16 RW Hz ×0.1 Setpoint in Hz with one decimal
HR 4 uint16 RW s ×0.01 Acceleration and deceleration time, 0 to 60000 raw; used when fieldbus ramp control is enabled
HR 6 bool bit 0 R
HR 6 bool bit 1 R
HR 6 bool bit 2 R
HR 6 bool bit 3 R
HR 6 bool bit 4 R
HR 6 bool bit 5 R
HR 6 bool bit 6 R
HR 6 bool bit 7 R 1 = low or high load detected
HR 6 uint16 bits 8–15 R Number of the active fault; see the fault list in the guide
HR 7 uint16 R Hz ×0.1
HR 8 uint16 R A ×0.1
HR 9 int16 R % ×0.1
HR 10 uint16 R kW ×0.01
HR 11 uint16 R Bit 0 = digital input 1, and so on
HR 20 uint16 R % ×0.1
HR 21 uint16 R % ×0.1
HR 22 uint16 R Internal frequency setpoint
HR 23 uint16 R V
HR 24 int16 R °C
HR 30 uint16 R User-resettable energy meter, kWh part (P0-26); decimals not stated
HR 31 uint16 R User-resettable energy meter, MWh part (P0-27)
HR 32 uint16 R Non-resettable energy meter, kWh part
HR 33 uint16 R Non-resettable energy meter, MWh part
HR 34 uint16 R h Total operating time, hours (P0-31)
HR 35 uint16 R Total operating time, minutes and seconds (P0-31); packing not described
HR 101 uint16 RW Hz ×0.1 P1-01