MBMap Registry
  1. Devices
  2. BEKO TECHNOLOGIES
  3. METPOINT VFS TI / TM

BEKO TECHNOLOGIES METPOINT VFS TI / TM Modbus register map

Also covers METPOINT VFS TI 220, METPOINT VFS TI 220 X, METPOINT VFS TI 400, METPOINT VFS TI 400 X, METPOINT VFS TM 20, METPOINT VFS TM 25, METPOINT VFS TM 50

Thermal mass flow meter for compressed air and gases, Modbus RTU (RS485)

  • Official
  • 93 registers
  • Modbus RTU
  • Revision 1 · 2026-11-09

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
247
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
35 holding registers, 58 input registers
Groups
11
Translation tables
14
Revision
1 · 2026-11-09
Added
()
File
maps/beko-technologies/metpoint-vfs.mbmap.json · 21 KB · history
SHA-256
beef8d93db505042e15e1721c454afd116bf048e9e7a53f15cf9347a78dc286e
Manufacturer
beko-technologies.com

Sources and notes

  • METPOINT VFS TI / TM, Original installation and service instructions (10-447) · version 00.02, 2025-03-31
    Chapter 4.6, Modbus settings

Source: BEKO TECHNOLOGIES, METPOINT VFS TI / TM, Original installation and service instructions 10-447, version 00.02, 31 March 2025

  • The manual gives the addresses without saying whether they are 0- or 1-based. The one example it gives (holding register 0x07D0 is decimal 2000) is a wire address, so they are given here as 0-based. If a read fails, try address_base 1.
  • Defaults from the manual: 19200 baud, 8 data bits, even parity, 1 stop bit, slave address 247. When the address is changed it can be 1 to 246.
  • Byte order is ABCD for floats and 32-bit integers (big-endian words). Each float takes two registers.
  • The manual lists the 4.6.3 table as Read Input Registers (0x04) and the 4.6.6 table as Write Multiple Holding Registers (0x10). The holding registers are given as RW; the manual does not say they can be read back with 0x03.
  • Input and holding registers use the same numbers for different things (3222, 3400 to 3406): they are separate address spaces.
  • Error flags: register 3200 holds all flags as a bit field (the manual numbers the bits 1 to 16, here 0 to 15). Registers 3201 to 3216 repeat each flag as a register; the manual lists no Error9 flag.
  • In the manual's unit lists for registers 3400 and 3701, value 4 is printed as l/h, the same as value 2. It is most likely l/s.
  • Changing the interface parameters is a three step write: 0xAC1D to register 5010, the parameter word to register 2000, then 0xBA5E to register 5020; restart the device afterwards.
  • The device also answers Read Device Identification (0x2B / 0x0E) with the vendor, product code, software version and serial number as text; this is not a register, so it is not in the map.
  • Written from the manufacturer's document; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
IR 1701 uint16 R
IR 3200 bool bit 0 R Bit 1 of the error flags word (Error1 flag)
IR 3200 bool bit 1 R Bit 2 of the error flags word (Error2 flag)
IR 3200 bool bit 2 R Bit 3 of the error flags word (Error3 flag)
IR 3200 bool bit 3 R Bit 4 of the error flags word (Error4 flag)
IR 3200 bool bit 4 R Bit 5 of the error flags word (Error5 flag)
IR 3200 bool bit 5 R Bit 6 of the error flags word (Error6 flag)
IR 3200 bool bit 6 R Bit 7 of the error flags word (Error7 flag)
IR 3200 bool bit 7 R Bit 8 of the error flags word (Error8 flag)
IR 3200 bool bit 9 R Bit 10 of the error flags word (Error10 flag)
IR 3200 bool bit 10 R Bit 11 of the error flags word (Error11 flag)
IR 3200 bool bit 11 R Bit 12 of the error flags word (Error12 flag)
IR 3200 bool bit 12 R Bit 13 of the error flags word (Error13 flag)
IR 3200 bool bit 13 R Bit 14 of the error flags word (Error14 flag)
IR 3200 bool bit 14 R Bit 15 of the error flags word (Error15 flag)
IR 3200 bool bit 15 R Bit 16 of the error flags word (Error16 flag)
IR 3201 uint16 R Code flash fault
IR 3202 uint16 R Configuration fault
IR 3203 uint16 R Product not adjusted
IR 3204 uint16 R Hardware fault
IR 3205 uint16 R Hardware fault, sensor memory
IR 3206 uint16 R Hardware fault, bridge DAC
IR 3207 uint16 R Hardware fault, current loop DAC
IR 3208 uint16 R Hardware fault, sensor RGS, RHZ or bridge
IR 3210 uint16 R Invalid offset value for bridge DAC
IR 3211 uint16 R TOF fault
IR 3212 uint16 R Sensor immersion depth fault
IR 3213 uint16 R Excess value warning
IR 3214 uint16 R Excess value error
IR 3215 uint16 R Gas temperature warning
IR 3216 uint16 R Gas temperature error
IR 3222 uint16 R Identification signal
IR 3300 uint16 R h Time left until the next calibration
IR 3400 float32 ABCD R m³/h
IR 3402 float32 ABCD R m³/min
IR 3404 float32 ABCD R l/h
IR 3406 float32 ABCD R l/min
IR 3408 float32 ABCD R l/s
IR 3410 float32 ABCD R cfm
IR 3412 float32 ABCD R cfh
IR 3414 float32 ABCD R kg/h
IR 3416 float32 ABCD R kg/min
IR 3418 float32 ABCD R kg/s
IR 3420 float32 ABCD R g/s
IR 3422 float32 ABCD R g/min
IR 3424 float32 ABCD R t/h
IR 3426 float32 ABCD R lbs/s
IR 3428 float32 ABCD R lbs/min
IR 3430 float32 ABCD R lbs/h
IR 3432 float32 ABCD R m/s
IR 3434 float32 ABCD R fpm
IR 3436 float32 ABCD R °C
IR 3438 float32 ABCD R °F
IR 3444 uint32 ABCD R m³ Consumption
IR 3446 uint32 ABCD R l Consumption
IR 3448 uint32 ABCD R kg Consumption
IR 3450 uint32 ABCD R cf Consumption
IR 3452 uint32 ABCD R lb Consumption
HR 2030 uint16 RW Bus termination at the end of a daisy chain
HR 3218 float32 ABCD RW User-defined reference condition; unit in register 3226
HR 3220 float32 ABCD RW User-defined reference condition; unit in register 3227
HR 3222 float32 ABCD RW Unit in register 3228
HR 3224 float32 ABCD RW Low flow cut-off value; unit in register 3229
HR 3226 uint16 RW
HR 3227 uint16 RW
HR 3228 uint16 RW
HR 3229 uint16 RW
HR 3301 uint16 RW h
HR 3302 uint16 RW h How long before the end of the recalibration interval the notice is given
HR 3400 uint16 RW Value sent on the 4 to 20 mA output
HR 3401 uint16 RW
HR 3402 float32 ABCD RW
HR 3404 float32 ABCD RW
HR 3406 float32 ABCD RW mA
HR 3600 uint32 ABCD RW Preset value of the consumption counter; unit in register 3602
HR 3602 uint16 RW
HR 3700 uint16 RW
HR 3701 uint16 RW Value that triggers the alarm
HR 3702 uint16 RW
HR 3703 uint16 RW
HR 3704 float32 ABCD RW
HR 3706 float32 ABCD RW
HR 3708 float32 ABCD RW
HR 3711 uint16 RW Consumption value that is sent as pulses
HR 3712 float32 ABCD RW Consumption that one pulse stands for
HR 3851 uint16 RW
HR 3852 uint16 RW
HR 3853 uint16 RW
HR 3854 uint16 RW
HR 3855 uint16 RW
HR 5010 uint16 W Write 0xAC1D (44061) here before writing register 2000
HR 2000 uint16 W High byte: baud rate, parity and stop bits (enum interface_serial); low byte: slave address 1 to 246. Example: 0x070A is 19200 baud, even parity, 1 stop bit, address 10
HR 5020 uint16 W Write 0xBA5E (47710) to store the interface parameters; they take effect about 10 s after a restart

Help improve this map