Carlo Gavazzi EM24-IS Modbus register map

Also covers EM24-DIN PFA, EM24-DIN PFB, EM24-DIN X

Three-phase energy analyzer (DIN rail) with RS485 Modbus RTU (IS output option)

  • Official
  • 104 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
11 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
41 holding registers, 63 input registers
Groups
6
Revision
2 · 2026-10-17
Added
()
File
maps/carlo-gavazzi/em24-is.mbmap.json · 22 KB · history
SHA-256
234ab559f0f0e940f8678b80537e6b8fa764749afd900a93043504ec31f903af
Manufacturer
gavazziautomation.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Carlo Gavazzi identification code input 11 uint16 71 = EM24-DIN AV9 / AV2, 72 = EM24-DIN AV5, 73 = EM24-DIN AV6
Firmware Revision code input 771 uint16

Sources and notes

Source: Carlo Gavazzi, "EM24-DIN PFA, PFB & X models Communication Protocol", version 4 revision 0 (2012-12-03)

  • FC03 or FC04 read (the same values), FC06 writes one register; at most 11 registers per read.
  • 32-bit values are low word first (bytes high first in each word).
  • Overflow (EEEE on the display) reads 7FFFh in the high word of the variable.
  • Status and identity registers (0x0300–0x0304, 0x000B) must be read one word at a time.
AreaAddressNameTypeAccessUnitScaleDescription
IR 0 int32 CDAB R V ×0.1
IR 2 int32 CDAB R V ×0.1
IR 4 int32 CDAB R V ×0.1
IR 6 int32 CDAB R V ×0.1
IR 8 int32 CDAB R V ×0.1
IR 10 int32 CDAB R V ×0.1
IR 12 int32 CDAB R A ×0.001
IR 14 int32 CDAB R A ×0.001
IR 16 int32 CDAB R A ×0.001
IR 18 int32 CDAB R W ×0.1
IR 20 int32 CDAB R W ×0.1
IR 22 int32 CDAB R W ×0.1
IR 24 int32 CDAB R VA ×0.1
IR 26 int32 CDAB R VA ×0.1
IR 28 int32 CDAB R VA ×0.1
IR 30 int32 CDAB R var ×0.1
IR 32 int32 CDAB R var ×0.1
IR 34 int32 CDAB R var ×0.1
IR 36 int32 CDAB R V ×0.1
IR 38 int32 CDAB R V ×0.1
IR 40 int32 CDAB R W ×0.1
IR 42 int32 CDAB R VA ×0.1
IR 44 int32 CDAB R var ×0.1
IR 46 int32 CDAB R W ×0.1
IR 48 int32 CDAB R VA ×0.1
IR 50 int16 R ×0.001 Negative = lead (C), positive = lag (L)
IR 51 int16 R ×0.001
IR 52 int16 R ×0.001
IR 53 int16 R ×0.001
IR 54 int16 R Meaningful only in 3-phase systems
IR 55 int16 R Hz ×0.1
IR 56 int32 CDAB R W ×0.1
IR 58 int32 CDAB R VA ×0.1
IR 60 int32 CDAB R A ×0.001
IR 62 int32 CDAB R kWh ×0.1
IR 64 int32 CDAB R kvarh ×0.1
IR 66 int32 CDAB R kWh ×0.1
IR 68 int32 CDAB R kvarh ×0.1
IR 70 int32 CDAB R kWh ×0.1
IR 72 int32 CDAB R kWh ×0.1
IR 74 int32 CDAB R kWh ×0.1
IR 76 int32 CDAB R kWh ×0.1
IR 78 int32 CDAB R kWh ×0.1
IR 80 int32 CDAB R kWh ×0.1
IR 82 int32 CDAB R kWh ×0.1
IR 84 int32 CDAB R kvarh ×0.1
IR 86 int32 CDAB R kvarh ×0.1
IR 88 int32 CDAB R kvarh ×0.1
IR 90 int32 CDAB R kvarh ×0.1
IR 92 int32 CDAB R kWh ×0.1
IR 94 int32 CDAB R kvarh ×0.1
IR 96 int32 CDAB R h ×0.01
IR 98 int32 CDAB R Weight ×10, ×100 or ×1000 per the digital input format setting (0x1133–0x1135)
IR 100 int32 CDAB R
IR 102 int32 CDAB R
IR 768 bool bit 0 R 1 = open, 0 = closed; read this register alone
IR 768 bool bit 1 R
IR 768 bool bit 2 R
IR 769 uint16 R
IR 772 uint16 R
IR 11 uint16 R Read alone, one word at a time: the same address is the high word of Voltage L3-L1
IR 770 uint16 R x = D or L
IR 771 uint16 R
HR 4864 uint16 R ASCII: high byte first letter, low byte second
HR 4865 uint16 R
HR 4866 uint16 R
HR 4867 uint16 R
HR 4868 uint16 R
HR 4869 uint16 R
HR 4870 uint16 R
HR 4352 uint16 RW
HR 4353 uint16 RW A, B, C, G on PFA only; E, F, H on PFB only; all on X
HR 4354 uint16 RW PFA and PFB support only 3Pn
HR 4355 uint16 RW min
HR 4356 uint16 RW
HR 4357 uint16 RW
HR 4358 uint16 RW
HR 4359 uint16 RW
HR 4360 uint16 RW
HR 4361 uint16 RW
HR 4362 uint16 RW
HR 4363 uint16 RW 8 data bits, no parity, 1 stop bit, fixed
HR 4364 uint16 RW
HR 4365 uint16 RW
HR 4366 uint16 RW
HR 4385 uint16 RW
HR 4386 uint16 RW
HR 4387 uint16 RW
HR 4388 uint16 RW
HR 4389 uint16 RW
HR 4390 uint16 RW
HR 4391 uint16 W Low byte 5Ah, high byte the tariff 0–3 (tariff 1–4); only when no digital input selects tariffs
HR 4403 uint16 RW
HR 4404 uint16 RW
HR 4405 uint16 RW
HR 4396 uint32 CDAB RW ×0.1
HR 4398 uint32 CDAB RW ×0.1
HR 4871 uint32 CDAB R
HR 12288 uint16 W
HR 12289 uint16 W