MBMap Registry
  1. Devices
  2. Carlo Gavazzi
  3. EM26-96

Carlo Gavazzi EM26-96 Modbus register map

Three-phase energy analyzer (96x96 mm panel) with RS485 Modbus RTU

  • Official
  • 130 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
11 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
52 holding registers, 78 input registers
Groups
7
Revision
2 · 2026-10-17
Added
()
File
maps/carlo-gavazzi/em26-96.mbmap.json · 28 KB · history
SHA-256
5a4efb20fb430e118a1ad16f02431d3ca4a5fd050dc95c6958113b0e6cab85b6
Manufacturer
gavazziautomation.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Carlo Gavazzi identification code input 11 uint16 49 = EM26-96 AV5, 50 = EM26-96 AV6
Firmware Revision code input 771 uint16

Sources and notes

Source: Carlo Gavazzi, "EM26-96 Communication Protocol", version 2 revision 0 (2008-03-25)

  • FC03 or FC04 read (the same values), FC06 writes one register; at most 11 registers per read.
  • 32-bit values are low word first (bytes high first in each word).
  • Overflow (---- on the display) reads 7FFFh in the high word of the variable.
  • Status and identity registers (0x0300-0x0305, 0x000B) must be read one word at a time.
AreaAddressNameTypeAccessUnitScaleDescription
IR 0 int32 CDAB R V ×0.1
IR 2 int32 CDAB R V ×0.1
IR 4 int32 CDAB R V ×0.1
IR 6 int32 CDAB R V ×0.1
IR 8 int32 CDAB R V ×0.1
IR 10 int32 CDAB R V ×0.1
IR 12 int32 CDAB R A ×0.001
IR 14 int32 CDAB R A ×0.001
IR 16 int32 CDAB R A ×0.001
IR 18 int32 CDAB R W ×0.1
IR 20 int32 CDAB R W ×0.1
IR 22 int32 CDAB R W ×0.1
IR 24 int32 CDAB R VA ×0.1
IR 26 int32 CDAB R VA ×0.1
IR 28 int32 CDAB R VA ×0.1
IR 30 int32 CDAB R var ×0.1
IR 32 int32 CDAB R var ×0.1
IR 34 int32 CDAB R var ×0.1
IR 36 int32 CDAB R V ×0.1
IR 38 int32 CDAB R V ×0.1
IR 40 int32 CDAB R W ×0.1
IR 42 int32 CDAB R VA ×0.1
IR 44 int32 CDAB R var ×0.1
IR 46 int32 CDAB R W ×0.1
IR 48 int32 CDAB R VA ×0.1
IR 50 int16 R ×0.001 Negative = lead (C), positive = lag (L)
IR 51 int16 R ×0.001
IR 52 int16 R ×0.001
IR 53 int16 R ×0.001
IR 54 int16 R Meaningful only in 3-phase systems
IR 55 int16 R Hz ×0.1
IR 56 int32 CDAB R W ×0.1
IR 58 int32 CDAB R VA ×0.1
IR 60 int32 CDAB R A ×0.001
IR 62 int32 CDAB R kWh ×0.1
IR 64 int32 CDAB R kvarh ×0.1
IR 66 int32 CDAB R kWh ×0.1
IR 68 int32 CDAB R kvarh ×0.1
IR 70 int32 CDAB R kWh ×0.1
IR 72 int32 CDAB R kWh ×0.1
IR 74 int32 CDAB R kWh ×0.1
IR 76 int32 CDAB R kWh ×0.1
IR 78 int32 CDAB R kWh ×0.1
IR 80 int32 CDAB R kWh ×0.1
IR 82 int32 CDAB R kWh ×0.1
IR 84 int32 CDAB R kvarh ×0.1
IR 86 int32 CDAB R kvarh ×0.1
IR 88 int32 CDAB R kvarh ×0.1
IR 90 int32 CDAB R kvarh ×0.1
IR 92 int32 CDAB R kWh ×0.1
IR 94 int32 CDAB R kvarh ×0.1
IR 96 int32 CDAB R h ×0.01
IR 98 int32 CDAB R ×0.1
IR 100 int32 CDAB R ×0.1
IR 102 int32 CDAB R ×0.1
IR 104 int32 CDAB R A ×0.001
IR 106 int32 CDAB R A ×0.001
IR 108 int32 CDAB R A ×0.001
IR 110 int16 R % ×0.1
IR 111 int16 R % ×0.1
IR 112 int16 R % ×0.1
IR 113 int16 R % ×0.1
IR 114 int16 R % ×0.1
IR 115 int16 R % ×0.1
IR 116 int16 R % ×0.1
IR 117 int16 R % ×0.1
IR 118 int16 R % ×0.1
IR 768 bool bit 0 R 1 = open, 0 = closed; read this register alone
IR 768 bool bit 1 R
IR 768 bool bit 2 R
IR 769 uint16 R
IR 773 bool bit 0 R Read this register alone
IR 773 bool bit 1 R
IR 773 bool bit 2 R
IR 772 uint16 R
IR 11 uint16 R Read alone, one word at a time: the same address is the high word of Voltage L3-L1
IR 770 uint16 R
IR 771 uint16 R
HR 4352 uint16 RW
HR 4353 uint16 RW
HR 4354 uint16 RW
HR 4355 uint16 RW min
HR 4356 uint16 RW
HR 4357 uint16 RW
HR 4358 uint16 RW
HR 4359 uint16 RW
HR 4360 uint16 RW
HR 4361 uint16 RW
HR 4362 uint16 RW
HR 4363 uint16 RW 8 data bits, no parity, 1 stop bit, fixed
HR 4364 uint16 RW
HR 4365 uint16 RW
HR 4366 uint16 RW
HR 4385 uint16 RW
HR 4386 uint16 RW
HR 4387 uint16 RW
HR 4388 uint16 RW
HR 4389 uint16 RW
HR 4390 uint16 RW
HR 4391 uint16 W Low byte 5Ah, high byte the tariff 0–3 (tariff 1–4); only when no digital input selects tariffs

Help improve this map