MBMap Registry
  1. Devices
  2. Carlo Gavazzi
  3. EM530 / EM540

Carlo Gavazzi EM530 / EM540 Modbus register map

Also covers EM530DINAV53XS1X

Three-phase energy analysers with RS485 (EM530 and EM540, standard and MID PFA/PFB/PFC). Some setup registers are read-only or missing on MID and AV2 models

  • Verified
  • 262 registers
  • Modbus RTU
  • Revision 4 · 2026-11-10
  • Identity: serial number

Verified: Tested on a real device.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
20 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
262 holding registers
Groups
21
Translation tables
4
Revision
4 · 2026-11-10
Firmware
1.3.3
Added
()
File
maps/carlo-gavazzi/em530-em540.mbmap.json · 47 KB · history
SHA-256
f6d382db5f07ce7cc82b590fd39a43dbe7f78152321b610cd1ff4fb33ad9a504
Manufacturer
gavazziautomation.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 20480 string[7]

Sources and notes

Source: Carlo Gavazzi, "EM530/EM540 Modbus communication protocol", public version 1.3 (2024-02-13), tables 4.1-4.24; https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM500_CPP_Mod_V1.3_13022024.pdf

  • Carlo Gavazzi EM530 and EM540 energy analysers (RS485).
  • FC03 and FC04 return the same values; this map reads everything as holding registers.
  • Tables 4.1 and 4.2 of the protocol hold the same values at two addresses; the second copy is in the group "By phase (copy)".
  • Tested on EM530DINAV53XS1X (EM530 X), firmware 1.3.3, October 2026, over RS485. Checked: voltage, frequency, device and setup registers, the "By phase (copy)" group and the 32-bit word order. Current, power, power factor and energy were read with no current flowing, and the per-phase registers of L2 and L3 were not tested under load.
  • A second unit was tested under load (about 15.5 A per phase) over RS485 at 9600 baud, November 2026: 252 of 257 registers read. Checked: voltages, currents, power, power factor, frequency, THD, demand, energies, the "By phase (copy)" group, setup and the 32-bit word order. Apparent power matches active and reactive power on every phase (L2: 2628 W and 2628 var give 3715.8 VA), the per-phase kWh add up to the total (20111.5 against 20111.7 kWh) and the 64-bit Wh copies agree with the 0.1 kWh values.
  • Digital input status (768), Active tariff (769) and the firmware word (770, firmware 1.3.3) answered illegal address when read together as one block of 3 registers, but each read fine on its own (768 and 769 as a block of 2, 770 alone). The meter refuses a read that runs from 0301h into 0302h, so the map reads 770 alone (read_alone) and 768 and 769 together (read_group). The identification code (11) read 0, which is not in the model list, and FC17 got no reply.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 int32 CDAB R V ×0.1
HR 2 int32 CDAB R V ×0.1
HR 4 int32 CDAB R V ×0.1
HR 6 int32 CDAB R V ×0.1
HR 8 int32 CDAB R V ×0.1
HR 10 int32 CDAB R V ×0.1
HR 12 int32 CDAB R A ×0.001
HR 14 int32 CDAB R A ×0.001
HR 16 int32 CDAB R A ×0.001
HR 18 int32 CDAB R W ×0.1
HR 20 int32 CDAB R W ×0.1
HR 22 int32 CDAB R W ×0.1
HR 24 int32 CDAB R VA ×0.1
HR 26 int32 CDAB R VA ×0.1
HR 28 int32 CDAB R VA ×0.1
HR 30 int32 CDAB R var ×0.1
HR 32 int32 CDAB R var ×0.1
HR 34 int32 CDAB R var ×0.1
HR 36 int32 CDAB R V ×0.1
HR 38 int32 CDAB R V ×0.1
HR 40 int32 CDAB R W ×0.1
HR 42 int32 CDAB R VA ×0.1
HR 44 int32 CDAB R var ×0.1
HR 46 int16 R ×0.001 Negative = exported active power, positive = imported. See the L/C rows for inductive or capacitive load
HR 47 int16 R ×0.001 Negative = exported active power, positive = imported. See the L/C rows for inductive or capacitive load
HR 48 int16 R ×0.001 Negative = exported active power, positive = imported. See the L/C rows for inductive or capacitive load
HR 49 int16 R ×0.001 Negative = exported active power, positive = imported. See the L/C rows for inductive or capacitive load
HR 50 int16 R Meaningful only in a 3-phase system
HR 51 int16 R Hz ×0.1
HR 52 int32 CDAB R kWh ×0.1
HR 54 int32 CDAB R kvarh ×0.1
HR 56 int32 CDAB R W ×0.1
HR 58 int32 CDAB R W ×0.1
HR 60 int32 CDAB R kWh ×0.1
HR 62 int32 CDAB R kvarh ×0.1
HR 64 int32 CDAB R kWh ×0.1
HR 66 int32 CDAB R kWh ×0.1
HR 68 int32 CDAB R kWh ×0.1
HR 70 int32 CDAB R kWh ×0.1
HR 72 int32 CDAB R kWh ×0.1
HR 78 int32 CDAB R kWh ×0.1
HR 80 int32 CDAB R kvarh ×0.1
HR 82 int32 CDAB R kWh ×0.1
HR 84 int32 CDAB R kvarh ×0.1
HR 86 int32 CDAB R kVAh ×0.1
HR 88 int32 CDAB R kVAh ×0.1
HR 90 int32 CDAB R h ×0.01
HR 92 int32 CDAB R h ×0.01
HR 110 int32 CDAB R h ×0.01
HR 112 int32 CDAB R h ×0.01
HR 114 int16 R ×0.001 Negative = lead (C), positive = lag (L)
HR 115 int16 R ×0.001 Negative = lead (C), positive = lag (L)
HR 116 int16 R ×0.001 Negative = lead (C), positive = lag (L)
HR 117 int16 R ×0.001 Negative = lead (C), positive = lag (L)
HR 118 int16 R
HR 119 int16 R
HR 120 int16 R
HR 121 int16 R
HR 130 int32 CDAB R % ×0.01
HR 132 int32 CDAB R % ×0.01
HR 134 int32 CDAB R % ×0.01
HR 138 int32 CDAB R % ×0.01
HR 140 int32 CDAB R % ×0.01
HR 142 int32 CDAB R % ×0.01
HR 146 int32 CDAB R % ×0.01
HR 148 int32 CDAB R % ×0.01
HR 150 int32 CDAB R % ×0.01
HR 152 int32 CDAB R A ×0.001
HR 154 int32 CDAB R A ×0.001
HR 156 int32 CDAB R A ×0.001
HR 158 int32 CDAB R A ×0.001
HR 160 int32 CDAB R A ×0.001
HR 162 int32 CDAB R A ×0.001
HR 164 int32 CDAB R A ×0.001
HR 172 int32 CDAB R W ×0.1
HR 174 int32 CDAB R W ×0.1
HR 176 int32 CDAB R W ×0.1
HR 178 int32 CDAB R W ×0.1
HR 180 int32 CDAB R W ×0.1
HR 182 int32 CDAB R W ×0.1
HR 190 int32 CDAB R W ×0.1 Same value as 0038h
HR 192 int32 CDAB R W ×0.1 Same value as 003Ah
HR 214 int32 CDAB R VA ×0.1
HR 216 int32 CDAB R VA ×0.1
HR 246 int32 CDAB R h ×0.01
HR 248 int32 CDAB R A ×0.001
HR 254 int32 CDAB R h ×0.01
HR 258 int32 CDAB R V ×0.1
HR 260 int32 CDAB R V ×0.1
HR 262 int32 CDAB R W ×0.1
HR 264 int32 CDAB R VA ×0.1
HR 266 int32 CDAB R var ×0.1
HR 268 int32 CDAB R ×0.001
HR 270 int32 CDAB R
HR 272 int32 CDAB R Hz ×0.1
HR 274 int32 CDAB R kWh ×0.1
HR 276 int32 CDAB R kvarh ×0.1
HR 278 int32 CDAB R kWh ×0.1
HR 280 int32 CDAB R kvarh ×0.1
HR 282 int32 CDAB R W ×0.1

Help improve this map