Three-phase DIN-rail multifunction meter with RS485 Modbus RTU and optional LoRaWAN

  • Official
  • 659 registers
  • Modbus RTU
  • Revision 2 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
100
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
659 holding registers
Groups
20
Revision
2 · 2026-10-18
Added
()
File
maps/cet/pmc-350-c.mbmap.json · 99 KB · history
SHA-256
5eabaec5900c0b89093fb79767d5593b2e429666aee9d47da623accbd89589f2
Manufacturer
cet-global.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware version holding 60220 uint16
Serial number Serial number holding 60225 uint32 ABCD

Sources and notes

Source: CET, "PMC-350-C Digital Three-Phase LoRaWAN DIN Energy Meter User Manual", V1.4 (2025-12-30), chapter 5 (protocol version 1.3)

  • Read with FC03, write with FC16; DO control also with FC05.
  • Big endian: high byte and high word first. Floats are IEEE 754.
  • Harmonic, TDD and unbalance values have no unit in the manual; the sister PMC-53A sends them as fractions (0.1 = 10 %).
  • Not in this map: max demand, max/min, monthly energy, freeze, SOE and data recorder logs, setpoint, data recorder, custom data, TOU, LoRaWAN and fire monitoring set-up.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 float32 ABCD R V
HR 2 float32 ABCD R V
HR 4 float32 ABCD R V
HR 6 float32 ABCD R V
HR 8 float32 ABCD R V
HR 10 float32 ABCD R V
HR 12 float32 ABCD R V
HR 14 float32 ABCD R V
HR 16 float32 ABCD R A
HR 18 float32 ABCD R A
HR 20 float32 ABCD R A
HR 22 float32 ABCD R A
HR 24 float32 ABCD R W
HR 26 float32 ABCD R W
HR 28 float32 ABCD R W
HR 30 float32 ABCD R W
HR 32 float32 ABCD R var
HR 34 float32 ABCD R var
HR 36 float32 ABCD R var
HR 38 float32 ABCD R var
HR 40 float32 ABCD R VA
HR 42 float32 ABCD R VA
HR 44 float32 ABCD R VA
HR 46 float32 ABCD R VA
HR 48 float32 ABCD R
HR 50 float32 ABCD R
HR 52 float32 ABCD R
HR 54 float32 ABCD R
HR 56 float32 ABCD R Hz
HR 58 float32 ABCD R ° Uab/Ubc/Uca in 3P3W
HR 60 float32 ABCD R °
HR 62 float32 ABCD R °
HR 64 float32 ABCD R °
HR 66 float32 ABCD R °
HR 68 float32 ABCD R °
HR 70 float32 ABCD R A
HR 72 float32 ABCD R mA Ir option only
HR 74 float32 ABCD R
HR 76 float32 ABCD R
HR 78 float32 ABCD R
HR 80 float32 ABCD R
HR 86 float32 ABCD R °C RTD option only
HR 88 float32 ABCD R °C
HR 90 float32 ABCD R °C
HR 92 float32 ABCD R °C
HR 94 bool bit 0 R
HR 95 bool bit 0 R
HR 95 bool bit 1 R
HR 95 bool bit 2 R
HR 95 bool bit 3 R
HR 96 bool bit 0 R
HR 96 bool bit 1 R
HR 96 bool bit 2 R
HR 96 bool bit 3 R
HR 98 bool bit 0 R
HR 98 bool bit 1 R
HR 99 bool bit 0 R
HR 99 bool bit 1 R
HR 100 bool bit 0 R
HR 100 bool bit 1 R
HR 100 bool bit 2 R
HR 100 bool bit 3 R
HR 100 bool bit 4 R
HR 100 bool bit 5 R
HR 100 bool bit 6 R
HR 100 bool bit 7 R
HR 100 bool bit 8 R
HR 100 bool bit 9 R
HR 101 bool bit 0 R 1 = abnormal
HR 101 bool bit 1 R
HR 101 bool bit 2 R
HR 101 bool bit 3 R
HR 101 bool bit 6 R
HR 101 bool bit 7 R
HR 101 bool bit 8 R
HR 101 bool bit 9 R
HR 101 bool bit 10 R
HR 101 bool bit 11 R
HR 101 bool bit 12 R
HR 101 bool bit 13 R
HR 101 bool bit 14 R
HR 102 uint32 ABCD R
HR 104 uint32 ABCD R h ×0.1 Counts while any phase current is above 100 mA
HR 106 bool bit 0 R
HR 107 bool bit 0 R
HR 107 bool bit 1 R
HR 107 bool bit 2 R
HR 107 bool bit 3 R
HR 108 bool bit 0 R
HR 108 bool bit 1 R
HR 108 bool bit 2 R
HR 108 bool bit 3 R
HR 108 bool bit 4 R
HR 108 bool bit 5 R
HR 108 bool bit 6 R
HR 108 bool bit 7 R
HR 108 bool bit 14 R
HR 108 bool bit 15 R
HR 112 float32 ABCD R W
HR 114 float32 ABCD R W

Help improve this map