MBMap Registry
  1. Devices
  2. CET
  3. PMC-53

CET PMC-53 Modbus register map

Also covers PMC-53M, PMC-53V, PMC-53I

Three-phase panel multifunction meter (96x96 mm), RS485 Modbus RTU

  • Official
  • 171 registers
  • Modbus RTU
  • Revision 2 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
100
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
161 holding registers, 10 coils
Groups
11
Revision
2 · 2026-10-18
Added
()
File
maps/cet/pmc-53.mbmap.json · 29 KB · history
SHA-256
cbb5b292acc4e73da1a2f0a1bb2ff4671dc673455a4e57fb94e2586804b15920
Manufacturer
cet-global.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware version holding 60220 uint16
Serial number Serial number holding 60225 uint32 ABCD

Sources and notes

Source: CET, "PMC-53 Series Intelligent Multifunction Meter User Manual", V5.2A (2012-02-07), chapter 5

  • Register map for protocol version 6.0. Read with FC03, write with FC16; DO control with FC05 only.
  • Big endian: high byte and high word first.
  • PMC-53V measures voltages and frequency only, PMC-53I currents and frequency only; power, energy and the other values are on the PMC-53M.
  • Not in this map: SOE log (42000-42223).
AreaAddressNameTypeAccessUnitScaleDescription
HR 40000 uint32 ABCD R V ×0.01 PMC-53V and PMC-53M
HR 40002 uint32 ABCD R V ×0.01
HR 40004 uint32 ABCD R V ×0.01
HR 40006 uint32 ABCD R V ×0.01
HR 40008 uint32 ABCD R V ×0.01
HR 40010 uint32 ABCD R V ×0.01
HR 40012 uint32 ABCD R V ×0.01
HR 40014 uint32 ABCD R V ×0.01
HR 40016 uint32 ABCD R A ×0.001 PMC-53I and PMC-53M
HR 40018 uint32 ABCD R A ×0.001
HR 40020 uint32 ABCD R A ×0.001
HR 40022 uint32 ABCD R A ×0.001
HR 40024 int32 ABCD R kW ×0.001 PMC-53M only
HR 40026 int32 ABCD R kW ×0.001
HR 40028 int32 ABCD R kW ×0.001
HR 40030 int32 ABCD R kW ×0.001
HR 40032 int32 ABCD R kvar ×0.001
HR 40034 int32 ABCD R kvar ×0.001
HR 40036 int32 ABCD R kvar ×0.001
HR 40038 int32 ABCD R kvar ×0.001
HR 40040 int32 ABCD R kVA ×0.001
HR 40042 int32 ABCD R kVA ×0.001
HR 40044 int32 ABCD R kVA ×0.001
HR 40046 int32 ABCD R kVA ×0.001
HR 40048 int16 R ×0.001
HR 40049 int16 R ×0.001
HR 40050 int16 R ×0.001
HR 40051 int16 R ×0.001
HR 40052 uint16 R Hz ×0.01
HR 40053 uint32 ABCD R A ×0.001 Firmware V1.20.01 / protocol V6.0 or later
HR 40055 uint16 R % ×0.1
HR 40056 uint16 R % ×0.1
HR 40057 int16 R ×0.001
HR 40058 int16 R ×0.001
HR 40059 int16 R ×0.001
HR 40060 int32 ABCD R kW ×0.001 Firmware V1.20.01 / protocol V6.0 or later
HR 40062 int32 ABCD R kvar ×0.001
HR 40064 int32 ABCD R kVA ×0.001
HR 40066 uint32 ABCD R A ×0.001
HR 40068 uint32 ABCD R A ×0.001
HR 40070 uint32 ABCD R A ×0.001
HR 40072 uint16 R ° ×0.01
HR 40073 uint16 R ° ×0.01
HR 40074 uint16 R ° ×0.01
HR 40075 uint16 R ° ×0.01
HR 40076 uint16 R ° ×0.01
HR 40077 uint16 R ° ×0.01
HR 40078 uint16 R mA ×0.1 0x7FFF when no residual current sensor is connected
HR 40079 int16 R °C ×0.1 30000 = sensor broken or missing; -400 = below -40 °C
HR 40095 bool bit 0 R
HR 40095 bool bit 1 R
HR 40095 bool bit 2 R
HR 40095 bool bit 3 R
HR 40095 bool bit 4 R
HR 40095 bool bit 5 R
HR 40095 bool bit 6 R
HR 40095 bool bit 7 R
HR 40095 bool bit 8 R
HR 40096 bool bit 0 R
HR 40096 bool bit 1 R
HR 40097 bool bit 0 R
HR 40097 bool bit 1 R
HR 40098 uint32 ABCD R
HR 40100 uint32 ABCD RW kWh ×0.1 Presettable; rolls over after 99,999,999.9
HR 40102 uint32 ABCD RW kWh ×0.1
HR 40106 uint32 ABCD RW kvarh ×0.1
HR 40108 uint32 ABCD RW kvarh ×0.1
HR 40112 uint32 ABCD RW kVAh ×0.1
HR 40500 int32 ABCD R kW ×0.001 Firmware V1.20.01 / protocol V6.0 or later
HR 40502 uint32 ABCD R s UNIX time
HR 40504 int32 ABCD R kvar ×0.001
HR 40506 uint32 ABCD R s
HR 40508 int32 ABCD R kVA ×0.001
HR 40510 uint32 ABCD R s
HR 40512 int32 ABCD R A ×0.001
HR 40514 uint32 ABCD R s
HR 40516 int32 ABCD R A ×0.001
HR 40518 uint32 ABCD R s
HR 40520 int32 ABCD R A ×0.001
HR 40522 uint32 ABCD R s
HR 40703 uint16 R ×0.1
HR 40704 uint16 R ×0.1
HR 40705 uint16 R ×0.1
HR 40718 uint16 R % ×0.01
HR 40719 uint16 R % ×0.01
HR 40720 uint16 R % ×0.01
HR 40721 uint16 R % ×0.01
HR 40722 uint16 R % ×0.01
HR 40723 uint16 R % ×0.01
HR 41000 uint16 RW mA
HR 41001 uint16 RW s ×0.1
HR 41002 uint16 RW s ×0.1
HR 41003 uint16 RW s ×0.1
HR 41004 uint16 RW mA
HR 41005 uint16 RW °C
HR 41006 bool bit 0 RW
HR 41006 bool bit 1 RW
HR 41006 bool bit 2 RW
HR 41006 bool bit 3 RW
HR 41006 bool bit 4 RW

Help improve this map