Chauvin Arnoux ENERIUM 100/200/300 V2 Modbus register map

Also covers ENERIUM 200, ENERIUM 300, ENERIUM 310

Panel-mounted power and energy analysers with RS-485 Modbus RTU and Modbus TCP

  • Official
  • 215 registers
  • Modbus TCP and RTU
  • Revision 2 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502default
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
125 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
215 holding registers
Groups
9
Translation tables
8
Revision
2 · 2026-10-18
Added
()
File
maps/chauvin-arnoux/enerium-100-200-300-v2.mbmap.json · 37 KB · history
SHA-256
b49ea36def7e2059e0f5c314f01aed533f7ed3d7fe486c030df6c7bff8fd047a
Manufacturer
chauvin-arnoux.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 3 uint32 ABCD
Firmware Firmware major holding 10 uint16 bits 8–15
Firmware Firmware revision holding 10 uint16 bits 0–7

Sources and notes

Source: Chauvin Arnoux Energy, Definition de l'interface Modbus des centrales de mesure ENERIUM 100/200/300 V2, MS0-7423 Ed05

  • All 32-bit values take two registers with the most significant word first (the manual shows the serial number as MSB at 0x0003 and LSB at 0x0004); each register is big-endian. The units below follow the manual's resolution column: voltages 1/100 V, currents 1/10000 A, powers in W, var and VA, frequencies 1/100 Hz.
  • Reads use function 3 or 4 (the same data) and are limited to 125 registers. Settings are not written to the 0x68xx configuration area, which is read only: they are changed with command words. Write the command code to 0xD000 and its arguments from 0xD001 with function 16 (for example 0x0200 sets the slave address, 0x0201 the RS-485 speed, 0x0202 the parity, 0x0203 the stop bits).
  • Not mapped: minima and maxima with their dates (0x0AE4 to 0x0CFE and 0x0B34 to 0x0CBE), the 51-point harmonic spectra (0x0600 to 0x07F8), the averaged harmonics (0x1102 and up), the alarm FIFO (0x0F00), alarm, HMI, digital and analogue I/O configuration (0x6842 to 0x6CBC), recording and load curves (0x6DAE and up), power quality (ENERIUM 300 only) and the MAC address (0x001E to 0x0023).
  • Power factor and cos phi are followed by a quadrant register (0 inductive, 1 capacitive). Average powers are split into consumed (receiver) and generated values; the manual's generated side has no sign convention beyond the name.
  • Serial settings: 9600 bit/s, no parity and 1 stop bit are the defaults (formats F10 to F12); the optical front port is fixed at 38400 bit/s, 8 data bits, no parity, 1 stop bit and accepts any slave address. Modbus TCP listens on port 502. ASCII mode is selectable but this map is for RTU/TCP.
  • The command words that are not valid on a given product version answer with exception 3.
  • The alarm status word is 32 bits wide (0x0200 and 0x0201): the high register holds the global alarm state in bits 0 to 7 and the global alarm memory in bits 8 to 15; the low register holds the 16 elementary alarms.
AreaAddressNameTypeAccessUnitScaleDescription
HR 3 uint32 ABCD R High word at 0x0003, low word at 0x0004
HR 10 uint16 bits 8–15 R DSP software version only (format F14, 0xAABB)
HR 10 uint16 bits 0–7 R
HR 30 uint16 R
HR 31 uint16 R
HR 32 uint16 R
HR 33 uint16 R
HR 34 uint16 R
HR 35 uint16 R
HR 26624 uint32 ABCD R
HR 26626 uint32 ABCD R
HR 26628 uint32 ABCD R
HR 26630 uint32 ABCD R
HR 26632 uint16 R The manual names format F32, which it does not define; format F34 (0 = 50 Hz, 1 = 60 Hz) is the network-frequency one
HR 26633 uint16 R s One of 60, 120, 180, 240, 300, 360, 600, 720, 900, 1200, 1800 or 3600 s
HR 26634 uint16 R
HR 26638 uint32 ABCD R
HR 26640 uint32 ABCD R
HR 28628 uint32 ABCD R
HR 28630 uint32 ABCD R ENERIUM 300 and 310 only
HR 26642 uint16 R 1 to 247
HR 26643 uint16 R
HR 26644 uint16 R
HR 26645 uint16 R ms ×50 0 to 500 steps of 50 ms (RTU mode)
HR 26646 uint16 R
HR 26647 uint16 R
HR 1280 uint32 ABCD R V ×0.01
HR 1282 uint32 ABCD R V ×0.01
HR 1284 uint32 ABCD R V ×0.01
HR 1286 uint32 ABCD R V ×0.01
HR 1288 uint32 ABCD R V ×0.01
HR 1290 uint32 ABCD R V ×0.01
HR 1292 uint32 ABCD R V ×0.01
HR 1294 uint32 ABCD R A ×0.0001
HR 1296 uint32 ABCD R A ×0.0001
HR 1298 uint32 ABCD R A ×0.0001
HR 1300 uint32 ABCD R A ×0.0001
HR 1302 int32 ABCD R W
HR 1304 int32 ABCD R W
HR 1306 int32 ABCD R W
HR 1308 int32 ABCD R W
HR 1310 int32 ABCD R var
HR 1312 int32 ABCD R var
HR 1314 int32 ABCD R var
HR 1316 int32 ABCD R var
HR 1318 uint32 ABCD R VA
HR 1320 uint32 ABCD R VA
HR 1322 uint32 ABCD R VA
HR 1324 uint32 ABCD R VA
HR 1326 int16 R % ×0.01
HR 1327 uint16 R
HR 1328 int16 R % ×0.01
HR 1329 uint16 R
HR 1330 int16 R % ×0.01
HR 1331 uint16 R
HR 1332 int16 R % ×0.01
HR 1333 uint16 R
HR 1334 int16 R ×0.0001
HR 1335 uint16 R
HR 1336 int16 R ×0.0001
HR 1337 uint16 R
HR 1338 int16 R ×0.0001
HR 1339 uint16 R
HR 1340 int16 R ×0.0001
HR 1341 uint16 R
HR 1342 uint16 R ×0.0001
HR 1343 uint16 R ×0.0001
HR 1344 uint16 R ×0.0001
HR 1345 uint16 R ×0.0001
HR 1346 uint16 R ×0.0001
HR 1347 uint16 R ×0.0001
HR 1348 int16 R % ×0.01
HR 1349 uint16 R Hz ×0.01
HR 1350 int32 ABCD R ×0.0001
HR 1352 uint16 R Hz ×0.01
HR 2013 uint16 R % ×0.01
HR 2014 uint16 R % ×0.01
HR 2015 uint16 R % ×0.01
HR 2016 uint16 R % ×0.01
HR 2017 uint16 R % ×0.01
HR 2018 uint16 R % ×0.01
HR 2019 uint16 R % ×0.01
HR 2020 uint16 R % ×0.01
HR 2021 uint16 R % ×0.01
HR 2093 uint16 R % ×0.01
HR 1995 uint16 R
HR 1996 uint16 R
HR 1997 uint16 R
HR 1998 uint16 R
HR 1999 uint16 R
HR 2000 uint16 R
HR 2001 uint16 R
HR 2002 uint16 R
HR 2003 uint16 R
HR 2091 uint16 R
HR 2004 uint16 R % ×0.01
HR 2005 uint16 R % ×0.01
HR 2006 uint16 R % ×0.01
HR 2007 uint16 R % ×0.01
HR 2008 uint16 R % ×0.01