MBMap Registry
  1. Devices
  2. Circutor
  3. CEM-C31

Circutor CEM-C31 Modbus register map

Also covers CEM-C31-485-T1, CEM-C31-485-DS, CEM-C31-485-T1-MID, CEM-C31-485-DS-MID

Three-phase energy meter for current transformers, DIN rail, with RS-485 (Modbus RTU) on the -485 models

  • Official
  • 85 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
84 holding registers, 1 coil
Groups
8
Revision
2 · 2026-10-17
Added
()
File
maps/circutor/cem-c31.mbmap.json · 15 KB · history
SHA-256
072c1ecbc788f087ad3b3ee8eb8619291b64a710562e62f60b14ed5c72c991be
Manufacturer
circutor.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 96 uint32 ABCD
Firmware Firmware version major holding 80 uint16
Firmware Firmware version minor holding 81 uint16
Firmware Firmware version revision holding 82 uint16

Sources and notes

Source: Circutor, "CEM-C31 energy meter instruction manual", M017B01-03-23A

  • Read with FC03 or FC04 and write with FC10; a request must cover the full size of each variable.
  • Energies per tariff (0x0100-0x0137), the digital input and impulse counters are only on the CEM-C31-485-DS with the matching digital input type.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint32 ABCD R Wh
HR 2 uint32 ABCD R Wh
HR 4 uint32 ABCD R varh
HR 6 uint32 ABCD R varh
HR 8 uint32 ABCD R varh
HR 10 uint32 ABCD R varh
HR 48 uint32 ABCD R Wh
HR 50 uint32 ABCD R Wh
HR 52 uint32 ABCD R varh
HR 54 uint32 ABCD R varh
HR 56 uint32 ABCD R varh
HR 58 uint32 ABCD R varh
HR 256 uint32 ABCD R Wh
HR 258 uint32 ABCD R Wh
HR 260 uint32 ABCD R varh
HR 262 uint32 ABCD R varh
HR 264 uint32 ABCD R varh
HR 266 uint32 ABCD R varh
HR 268 uint32 ABCD R Wh
HR 270 uint32 ABCD R Wh
HR 272 uint32 ABCD R varh
HR 274 uint32 ABCD R varh
HR 276 uint32 ABCD R varh
HR 278 uint32 ABCD R varh
HR 288 uint32 ABCD R Wh
HR 290 uint32 ABCD R Wh
HR 292 uint32 ABCD R varh
HR 294 uint32 ABCD R varh
HR 296 uint32 ABCD R varh
HR 298 uint32 ABCD R varh
HR 300 uint32 ABCD R Wh
HR 302 uint32 ABCD R Wh
HR 304 uint32 ABCD R varh
HR 306 uint32 ABCD R varh
HR 308 uint32 ABCD R varh
HR 310 uint32 ABCD R varh
CO 2048 bool W Write ON (0xFF00) with FC05
HR 1842 int32 ABCD R V ×0.1 Primary value
HR 1844 int32 ABCD R V ×0.1 Primary value
HR 1846 int32 ABCD R V ×0.1 Primary value
HR 1848 int32 ABCD R A ×0.01 Primary value
HR 1850 int32 ABCD R A ×0.01 Primary value
HR 1852 int32 ABCD R A ×0.01 Primary value
HR 1854 int32 ABCD R ×0.01
HR 1856 int32 ABCD R ×0.01
HR 1858 int32 ABCD R ×0.01
HR 1862 int32 ABCD R W
HR 1864 int32 ABCD R W
HR 1866 int32 ABCD R W
HR 1868 int32 ABCD R W
HR 1870 int32 ABCD R var
HR 1872 int32 ABCD R var
HR 1874 int32 ABCD R var
HR 1876 int32 ABCD R var
HR 1878 int32 ABCD R VA
HR 1880 int32 ABCD R VA
HR 1882 int32 ABCD R VA
HR 1884 int32 ABCD R VA
HR 32 uint16 R
HR 384 uint32 ABCD R
HR 386 uint32 ABCD R
HR 192 uint32 ABCD R
HR 194 uint32 ABCD R kg
HR 196 uint32 ABCD R s
HR 198 uint32 ABCD R s
HR 61456 string[6] R 12 ASCII characters coding the options (manual table 24)
HR 96 uint32 ABCD R
HR 104 uint32 ABCD R
HR 80 uint16 R
HR 81 uint16 R
HR 82 uint16 R
HR 1100 uint32 ABCD RW V
HR 1102 uint32 ABCD RW V
HR 1104 uint32 ABCD RW A
HR 1106 uint32 ABCD RW A
HR 128 uint16 RW
HR 129 uint16 RW Wh Wh per impulse
HR 1108 uint16 RW
HR 1000 uint16 RW Default 1
HR 1001 uint16 RW Default 0
HR 1002 uint16 RW Default 0
HR 176 uint32 ABCD RW ×0.0001
HR 178 uint32 ABCD RW kg ×0.0001
HR 180 uint16 RW Bit 0 partial energies, bit 1 tariffs, bit 2 reactive energy, bit 3 impulse, bit 4 efficiency factors
HR 181 uint16 RW s Default 60

Help improve this map