MBMap Registry
  1. Devices
  2. Circutor
  3. CVM-C10

Circutor CVM-C10 Modbus register map

Three-phase panel power analyzer (CVM-C10-ITF, -ITF-IN, -MC, -mV, -Flex) with RS-485 Modbus RTU

  • Official
  • 129 registers
  • Modbus RTU
  • Revision 3 · 2026-11-10
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
40 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
123 input registers, 6 coils
Groups
14
Translation tables
1
Revision
3 · 2026-11-10
Added
()
File
maps/circutor/cvm-c10.mbmap.json · 24 KB · history
SHA-256
6cb7ede9f48f1739ccd134933fb4c03b1c3b679d279b2c3a92be2b5273d0a655
Manufacturer
circutor.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number input 1400 uint32 ABCD

Sources and notes

Source: Circutor, "CVM-C10 Instruction Manual", M001B01-03-23A; https://docs.circutor.com/docs/M001B01-03.pdf

  • Circutor CVM-C10 panel power analyzer, Modbus RTU over RS-485.
  • Addresses are the manual's hexadecimal addresses, sent as-is on the wire.
  • Every measurement is a 32-bit integer in two registers; at most 20 values (40 registers) per request.
  • Generated active power reads negative. Measurements answer FC03 and FC04; configuration answers FC04 and is written with FC16 (all registers of a group at once), and only takes effect after a reset.
AreaAddressNameTypeAccessUnitScaleDescription
IR 0 uint32 ABCD R V ×0.1
IR 2 uint32 ABCD R A ×0.001
IR 4 int32 ABCD R W Negative when generating
IR 6 int32 ABCD R var
IR 8 int32 ABCD R var
IR 10 int32 ABCD R VA
IR 12 int32 ABCD R ×0.01
IR 14 int32 ABCD R ×0.01
IR 16 uint32 ABCD R V ×0.1
IR 18 uint32 ABCD R A ×0.001
IR 20 int32 ABCD R W Negative when generating
IR 22 int32 ABCD R var
IR 24 int32 ABCD R var
IR 26 int32 ABCD R VA
IR 28 int32 ABCD R ×0.01
IR 30 int32 ABCD R ×0.01
IR 32 uint32 ABCD R V ×0.1
IR 34 uint32 ABCD R A ×0.001
IR 36 int32 ABCD R W Negative when generating
IR 38 int32 ABCD R var
IR 40 int32 ABCD R var
IR 42 int32 ABCD R VA
IR 44 int32 ABCD R ×0.01
IR 46 int32 ABCD R ×0.01
IR 48 int32 ABCD R W Negative when generating
IR 50 int32 ABCD R var
IR 52 int32 ABCD R var
IR 54 int32 ABCD R VA
IR 56 int32 ABCD R ×0.01
IR 58 int32 ABCD R ×0.01
IR 60 uint32 ABCD R Hz ×0.01 Measured on L1
IR 62 uint32 ABCD R V ×0.1
IR 64 uint32 ABCD R V ×0.1
IR 66 uint32 ABCD R V ×0.1
IR 68 uint32 ABCD R A ×0.001 Measured on -IN models
IR 70 uint32 ABCD R % ×0.1
IR 72 uint32 ABCD R % ×0.1
IR 74 uint32 ABCD R % ×0.1
IR 76 uint32 ABCD R % ×0.1
IR 78 uint32 ABCD R % ×0.1
IR 80 uint32 ABCD R % ×0.1
IR 82 uint32 ABCD R W
IR 84 uint32 ABCD R VA
IR 86 uint32 ABCD R A ×0.001
IR 88 uint32 ABCD R A ×0.001
IR 90 uint32 ABCD R A ×0.001
IR 92 uint32 ABCD R A ×0.001
IR 344 uint32 ABCD R W
IR 346 uint32 ABCD R VA
IR 348 uint32 ABCD R A ×0.001
IR 350 uint32 ABCD R A ×0.001
IR 352 uint32 ABCD R A ×0.001
IR 354 uint32 ABCD R A ×0.001
IR 220 uint32 ABCD R kWh Whole kWh; add the Wh register for the remainder
IR 222 uint32 ABCD R Wh Remainder below 1 kWh
IR 224 uint32 ABCD R kvarh Whole kvarh; add the varh register for the remainder
IR 226 uint32 ABCD R varh Remainder below 1 kvarh
IR 228 uint32 ABCD R kvarh Whole kvarh; add the varh register for the remainder
IR 230 uint32 ABCD R varh Remainder below 1 kvarh
IR 232 uint32 ABCD R kVAh Whole kVAh; add the VAh register for the remainder
IR 234 uint32 ABCD R VAh Remainder below 1 kVAh
IR 240 uint32 ABCD R kWh Whole kWh; add the Wh register for the remainder
IR 242 uint32 ABCD R Wh Remainder below 1 kWh
IR 244 uint32 ABCD R kvarh Whole kvarh; add the varh register for the remainder
IR 246 uint32 ABCD R varh Remainder below 1 kvarh
IR 248 uint32 ABCD R kvarh Whole kvarh; add the varh register for the remainder
IR 250 uint32 ABCD R varh Remainder below 1 kvarh
IR 252 uint32 ABCD R kVAh Whole kVAh; add the VAh register for the remainder
IR 254 uint32 ABCD R VAh Remainder below 1 kVAh
IR 94 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 136 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 178 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 98 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 140 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 182 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 102 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 144 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 186 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 106 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 148 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 190 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 114 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 156 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 198 uint32 ABCD R kWh Whole kWh; the Wh remainder is at the next address
IR 118 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 160 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 202 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 122 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 164 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 206 uint32 ABCD R kvarh Whole kvarh; the varh remainder is at the next address
IR 126 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 168 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 210 uint32 ABCD R kVAh Whole kVAh; the VAh remainder is at the next address
IR 236 uint32 ABCD R kg ×0.1
IR 238 uint32 ABCD R ×0.1
IR 256 uint32 ABCD R kg ×0.1
IR 258 uint32 ABCD R ×0.1
IR 260 uint32 ABCD R s Time counted on all tariffs
IR 2001 bool bit 0 R
IR 2001 bool bit 1 R

Help improve this map