Cummins PowerCommand 3.3 Modbus register map
Also covers PCC3300
Generator set control, Modbus RTU on RS485, with fault status bitmaps
- Official
- 2,307 registers
- Modbus RTU
- Revision 1 · 2026-10-15
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1default
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 1-based · wire address = address − 1
- Max read
- 40 registers per request
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 2307 holding registers
- Groups
- 8
- Revision
- 1 · 2026-10-15
- Added
- ()
- File
- maps/cummins/powercommand-3x.mbmap.json · 425 KB · history
- SHA-256
- 0bd5ab8ae4a4dff18f21963b8c8e0f0299a396b244d8f38b7f16f6357263d50d
- Manufacturer
- cummins.com
Sources and notes
- Modbus Register Mapping, Control · version A029X159 (Issue 26), 2020-06 sections 13 (parametrics) and 14 (fault status bitmaps), registers marked PC 3.x; bits marked PCC3300 V2 only exist on that hardware
Source: Cummins, Modbus Register Mapping (Control), A029X159 Issue 26 (6-2020): sections 13 and 14
- Addresses are the manual's 4xxxx numbers less 40000, 1-based (40011 is holding register 11).
- 32-bit values have the high register first. Write both registers, high then low.
- Text values the manual lists as one character per register (serial numbers, time stamps) are left out.
- The manual does not give the factory serial settings: check baud rate, parity, stop bits and node address on the control.
- Save Trims writes the settings to flash memory, which wears out: use it only after a change, never on a schedule.
- Registers missing from older control software answer with an exception.
- Not available, out of range, network failure and hardware failure readings are the highest values of each type (section 13.2), declared as sentinels.
- 793 one-character text registers left out.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 10 | uint16 | R | ||||
| HR | 11 | uint16 | R | ||||
| HR | 12 | uint16 | R | ||||
| HR | 13 | uint16 | R | ||||
| HR | 14 | int16 | R | % | ×0.01 | ||
| HR | 16 | uint16 | R | ||||
| HR | 17 | uint16 | R | ||||
| HR | 18 | uint16 | R | V | |||
| HR | 19 | uint16 | R | V | |||
| HR | 20 | uint16 | R | V | |||
| HR | 21 | uint16 | R | V | |||
| HR | 22 | uint16 | R | V | |||
| HR | 23 | uint16 | R | V | |||
| HR | 24 | uint16 | R | V | |||
| HR | 25 | uint16 | R | V | |||
| HR | 26 | uint16 | R | A | |||
| HR | 27 | uint16 | R | A | |||
| HR | 28 | uint16 | R | A | |||
| HR | 29 | uint16 | R | A | |||
| HR | 30 | uint16 | R | A | |||
| HR | 31 | int16 | R | kW | |||
| HR | 32 | int16 | R | kW | |||
| HR | 33 | int16 | R | kW | |||
| HR | 34 | int16 | R | kW | |||
| HR | 35 | int16 | R | kVAR | |||
| HR | 36 | int16 | R | kVAR | |||
| HR | 37 | int16 | R | kVAR | |||
| HR | 38 | int16 | R | kVAR | |||
| HR | 39 | int16 | R | ×0.01 | |||
| HR | 40 | uint16 | R | kVA | |||
| HR | 41 | uint16 | R | kVA | |||
| HR | 42 | uint16 | R | kVA | |||
| HR | 43 | uint16 | R | kVA | |||
| HR | 44 | uint16 | R | Hz | ×0.01 | ||
| HR | 46 | uint32 ABCD | R | kWh | |||
| HR | 48 | uint32 ABCD | R | kWh | |||
| HR | 50 | int32 ABCD | R | kWh | |||
| HR | 52 | uint32 ABCD | R | kVARh | |||
| HR | 54 | uint32 ABCD | R | kVARh | |||
| HR | 56 | int32 ABCD | R | kVARh | |||
| HR | 58 | uint16 | R | % | ×0.1 | ||
| HR | 59 | uint16 | R | % | ×0.1 | ||
| HR | 60 | uint16 | R | % | ×0.1 | ||
| HR | 61 | uint16 | R | V | ×0.1 | ||
| HR | 62 | uint16 | R | kPa | |||
| HR | 63 | int16 | R | °F | ×0.1 | ||
| HR | 64 | int16 | R | °C | ×0.1 | ||
| HR | 65 | int16 | R | °F | ×0.1 | ||
| HR | 66 | int16 | R | °F | ×0.1 | ||
| HR | 67 | int16 | R | gal/h | ×0.05 | ||
| HR | 68 | uint16 | R | rpm | |||
| HR | 69 | uint16 | R | ||||
| HR | 70 | uint32 ABCD | R | s | ×0.1 | ||
| HR | 72 | uint32 ABCD | R | gal | ×0.1 | ||
| HR | 74 | uint32 ABCD | R | ||||
| HR | 118 | uint16 | R | V | |||
| HR | 119 | uint16 | R | V | |||
| HR | 120 | uint16 | R | V | |||
| HR | 121 | uint16 | R | V | |||
| HR | 122 | uint16 | R | V | |||
| HR | 123 | uint16 | R | V | |||
| HR | 124 | uint16 | R | V | |||
| HR | 125 | uint16 | R | V | |||
| HR | 126 | uint16 | R | A | |||
| HR | 127 | uint16 | R | A | |||
| HR | 128 | uint16 | R | A | |||
| HR | 129 | uint16 | R | A | |||
| HR | 131 | int16 | R | kW | |||
| HR | 132 | int16 | R | kW | |||
| HR | 133 | int16 | R | kW | |||
| HR | 134 | int16 | R | kW | |||
| HR | 135 | int16 | R | kVAR | |||
| HR | 136 | int16 | R | kVAR | |||
| HR | 137 | int16 | R | kVAR | |||
| HR | 138 | int16 | R | kVAR | |||
| HR | 139 | int16 | R | ×0.01 | |||
| HR | 140 | uint16 | R | kVA | |||
| HR | 141 | uint16 | R | kVA | |||
| HR | 142 | uint16 | R | kVA | |||
| HR | 143 | uint16 | R | kVA | |||
| HR | 144 | uint32 ABCD | R | Hz | ×0.001 | ||
| HR | 146 | uint32 ABCD | R | kWh | |||
| HR | 148 | uint32 ABCD | R | kWh | |||
| HR | 150 | int32 ABCD | R | kWh | |||
| HR | 152 | uint32 ABCD | R | kVARh | |||
| HR | 154 | uint32 ABCD | R | kVARh | |||
| HR | 156 | int32 ABCD | R | kVARh | |||
| HR | 158 | uint16 | R | V | |||
| HR | 159 | uint16 | R | V | |||
| HR | 160 | uint16 | R | V | |||
| HR | 161 | uint16 | R | V | |||
| HR | 162 | uint16 | R | V | |||
| HR | 163 | uint16 | R | V | |||
| HR | 164 | uint16 | R | V | |||
| HR | 165 | uint16 | R | V | |||
| HR | 166 | uint16 | R | A | |||
| HR | 167 | uint16 | R | A | |||
| HR | 168 | uint16 | R | A | |||
| HR | 169 | uint16 | R | A | |||
| HR | 171 | int16 | R | kW |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).