Daikin EKMBPP1 / EKMBPP1A Modbus register map

Modbus adapter for Daikin Sky Air and VRV indoor units over P1P2

  • Verified
  • 191 registers
  • Modbus RTU
  • Revision 2

Verified: Tested on a real device.

Communication

Protocol
Modbus RTU
Unit ID
1default
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
10 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
35 holding registers, 156 input registers
Groups
23
Translation tables
7
Revision
2
Added
()
File
maps/daikin/ekmbpp1-ekmbpp1a.mbmap.json · 34 KB · history
SHA-256
25b9cde6bd20d92aeb297a8abc602981084abdbb460295f7124c8d73e0d5ae8d
Manufacturer
daikin.com

Sources and notes

Source: Daikin, "EKMBPP1+EKMBPP1A Modbus adapter installation manual", 4P720139-1C (2024-11), sections 6.3-6.5

  • Daikin EKMBPP1 / EKMBPP1A Modbus adapter for Sky Air and VRV indoor units (P1P2).
  • Holding registers control the units; input registers read them back.
  • Temperatures in input registers are signed, in 0.01 °C. At most 10 registers per request. The unit (slave) address is set with DIP switches (0-63).
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 int16 RW °C 16-32; out-of-range values are limited
HR 2 uint16 RW Units with 3 speeds use 1, 3 and 5; reads 5 when the fan is on Auto
HR 3 uint16 RW
HR 4 uint16 RW
HR 5 uint16 RW
HR 10 uint16 RW Writing the global register sets all of them
HR 11 uint16 RW
HR 12 uint16 RW
HR 13 uint16 RW
HR 14 uint16 RW
HR 15 uint16 RW
HR 20 int16 RW °C 16-32; 0 = no limit
HR 21 int16 RW °C 16-32; 0 = no limit
HR 22 uint16 RW Sum of the inhibited speeds; 0 = no limit
HR 22 bool bit 1 RW
HR 22 bool bit 2 RW
HR 22 bool bit 3 RW
HR 22 bool bit 4 RW
HR 22 bool bit 5 RW
HR 23 uint16 RW Sum of the inhibited modes; 0 = no limit
HR 23 bool bit 0 RW
HR 23 bool bit 1 RW
HR 23 bool bit 2 RW
HR 23 bool bit 3 RW
HR 23 bool bit 4 RW
HR 24 uint16 RW Sum of the inhibited directions; 0 = no limit
HR 24 bool bit 1 RW
HR 24 bool bit 2 RW
HR 24 bool bit 3 RW
HR 24 bool bit 4 RW
HR 24 bool bit 5 RW
HR 24 bool bit 6 RW
HR 30 uint16 RW
HR 31 uint16 RW Reads 2 when on Auto
HR 55 uint16 RW
IR 50 int16 R °C ×0.01 Only with one indoor unit and the remote controller set as secondary; 0 otherwise
IR 51 uint16 R
IR 20 uint16 R Indoor units found on the network (0-16)
IR 21 uint16 R
IR 22 uint16 R Code of the first unit with an error
IR 22 string[1] R The two ASCII characters of the Daikin error code
IR 23 int16 R °C ×0.01
IR 24 uint16 R
IR 25 int16 R °C ×0.01
IR 26 int16 R °C ×0.01
IR 30 uint16 R
IR 35 uint16 R
IR 120 uint16 R
IR 121 uint16 R
IR 122 uint16 R
IR 122 string[1] R
IR 123 int16 R °C ×0.01
IR 124 uint16 R
IR 130 uint16 R
IR 131 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 132 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 220 uint16 R
IR 221 uint16 R
IR 222 uint16 R
IR 222 string[1] R
IR 223 int16 R °C ×0.01
IR 224 uint16 R
IR 230 uint16 R
IR 231 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 232 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 320 uint16 R
IR 321 uint16 R
IR 322 uint16 R
IR 322 string[1] R
IR 323 int16 R °C ×0.01
IR 324 uint16 R
IR 330 uint16 R
IR 331 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 332 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 420 uint16 R
IR 421 uint16 R
IR 422 uint16 R
IR 422 string[1] R
IR 423 int16 R °C ×0.01
IR 424 uint16 R
IR 430 uint16 R
IR 431 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 432 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 520 uint16 R
IR 521 uint16 R
IR 522 uint16 R
IR 522 string[1] R
IR 523 int16 R °C ×0.01
IR 524 uint16 R
IR 530 uint16 R
IR 531 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 532 int16 R °C ×0.01 Only when the adapter is P1P2 main
IR 620 uint16 R
IR 621 uint16 R
IR 622 uint16 R
IR 622 string[1] R
IR 623 int16 R °C ×0.01
IR 624 uint16 R
IR 630 uint16 R
IR 631 int16 R °C ×0.01 Only when the adapter is P1P2 main

Help improve this map