MBMap Registry
  1. Devices
  2. Danfoss
  3. VLT Micro Drive FC 51

Danfoss VLT Micro Drive FC 51 Modbus register map

VLT Micro Drive FC 51 over the built-in RS485 port, Modbus RTU with the FC control profile

  • Official
  • 95 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
95 holding registers
Groups
10
Translation tables
6
Revision
1 · 2026-11-10
Added
()
File
maps/danfoss/fc-51.mbmap.json · 20 KB · history
SHA-256
ed9e7e22c189e55b0ff1949a086e8a9502567225af753a91b38bc6271dbbc0f6
Manufacturer
danfoss.com

Sources and notes

Source: Danfoss, "VLT Micro Drive FC 51 Design Guide", MG02K402 (01/2016) and "VLT Micro Drive FC 51 Programming Guide", MG02C602 (software 2.7X)

  • Holding register of parameter x-yy is 10 times its number: 3-41 is register 3410, 16-14 is register 16140, 8-30 is register 8300. The guide counts registers from 1 and the bus address is one less, so this map uses address_base 1.
  • Control word, bus reference, status word and main actual value are registers 50000, 50010, 50200 and 50210. From software 2.32 they are also at 2810, 2811, 2910 and 2911.
  • Array parameters (3-10, 15-30) need the index in register 9 first. A 32-bit parameter uses two registers, high word first. One-byte parameters are read and written as one register.
  • Coil 65 chooses whether written parameters go to RAM only (0) or to RAM and EEPROM (1). Coils 1 to 64 repeat the control word, reference, status word and output frequency; they are not in this map, use the registers instead.
  • To enable Modbus: 8-30 Protocol = Modbus RTU, 8-31 Address 1 to 247, 8-32 baud rate, 8-33 parity. The guide gives even parity with 1 stop bit as the default; the Programming Guide lists 19200 baud as the Modbus default.
  • The guide's text for 8-32 allows up to 115200 baud, while the Programming Guide for software 2.7X lists 2400 to 38400. Only the Programming Guide values are in the table.
  • The Design Guide is for software 3.1X and the Programming Guide for 2.7X; conversion indexes are taken from the latter. Some Programming Guide parameters (motor power 1-20, text parameters such as 15-43 and 15-51) are not listed, as no size or scaling is given.
  • Function codes: 1, 3, 5, 6, 15 and 16, plus 11, 17 and the diagnostics function 8.
  • Written from the manufacturer's documents; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 7 uint16 R Fault code last returned by the parameter database
HR 8 uint16 R Address of the register that caused the last error
HR 9 uint16 RW Index used for the next access to an array parameter (for example 3-10 or 15-30); set it before reading or writing one
HR 50000 uint16 RW FC profile control word (8-10 Control Word Profile = FC profile)
HR 50000 uint16 bits 0–1 RW Chooses one of the four values of 3-10 Preset Reference (bits 0 and 1)
HR 50000 bool bit 2 RW 0 = DC brake and stop, 1 = ramp
HR 50000 bool bit 3 RW 0 = coast to a stop, 1 = no coasting
HR 50000 bool bit 4 RW 0 = quick stop, 1 = ramp
HR 50000 bool bit 5 RW 0 = hold the present output frequency, 1 = use the ramp
HR 50000 bool bit 6 RW 0 = ramp stop, 1 = start
HR 50000 bool bit 7 RW Reset a trip on the rising edge
HR 50000 bool bit 8 RW 1 = run at the jog speed (3-11)
HR 50000 bool bit 9 RW 0 = ramp 1, 1 = ramp 2
HR 50000 bool bit 10 RW 1 = the drive uses the control word, 0 = it ignores it
HR 50000 bool bit 11 RW 1 = relay 01 on, if 5-40 Function Relay selects control word bit 11
HR 50000 bool bit 12 RW 1 = relay 02 on, if 5-40 Function Relay selects control word bit 12
HR 50000 bool bit 13 RW 0 = set-up 1, 1 = set-up 2 (only with 0-10 Active Set-up = Multi set-up)
HR 50000 bool bit 15 RW 1 = reverse (acts only if 8-54 Reversing Select allows the bus)
HR 50010 int16 RW % ×0.006103515625 Speed reference in percent of the maximum reference (3-03): 16384 (4000 hex) = 100%, negative values in two's complement. Scale is 100/16384
HR 50200 uint16 R FC profile status word
HR 50200 bool bit 0 R 0 = control not ready, 1 = control ready
HR 50200 bool bit 1 R 0 = not ready, 1 = ready for operation
HR 50200 bool bit 2 R 0 = coasting, 1 = enabled
HR 50200 bool bit 3 R 1 = the drive has tripped
HR 50200 bool bit 4 R 1 = error without a trip
HR 50200 bool bit 6 R 1 = tripped and locked
HR 50200 bool bit 7 R 1 = a warning is active
HR 50200 bool bit 8 R 0 = speed differs from the reference, 1 = speed matches the reference
HR 50200 bool bit 9 R 0 = local operation, 1 = the drive can be controlled over the bus
HR 50200 bool bit 10 R 0 = output frequency at a speed limit (4-12 or 4-14), 1 = within limits
HR 50200 bool bit 11 R 0 = motor not running, 1 = in operation
HR 50200 bool bit 12 R 1 = stopped for temporary overtemperature, resumes by itself
HR 50200 bool bit 13 R 1 = DC link voltage too low or too high
HR 50200 bool bit 14 R 1 = the current limit is exceeded
HR 50200 bool bit 15 R 1 = a motor or drive thermal timer has passed 100%
HR 50210 int16 R % ×0.006103515625 Actual output frequency, scaled like the bus reference: 16384 (4000 hex) = 100%. Scale is 100/16384
HR 2810 uint16 RW Same control word as register 50000, in the lower register area (software 2.32 and later)
HR 2811 int16 RW % ×0.006103515625 Same bus reference as register 50010 (16384 = 100%), lower register area (software 2.32 and later)
HR 2910 uint16 R Same status word as register 50200, lower register area (software 2.32 and later)
HR 2911 int16 R % ×0.006103515625 Same main actual value as register 50210 (16384 = 100%), lower register area (software 2.32 and later)
HR 16010 int32 ABCD R ×0.001 Present reference in the unit of the configuration (Hz in open loop)
HR 16020 int16 R % ×0.1
HR 16050 int16 R % ×0.01
HR 16100 uint16 R kW ×0.001
HR 16110 uint16 R hp ×0.001
HR 16120 uint16 R V
HR 16130 uint16 R Hz ×0.1
HR 16140 uint16 R A ×0.01
HR 16150 uint16 R % ×0.1
HR 16180 uint16 R % Calculated thermal load of the motor; 100% is the cutout limit. The parameter is one byte, read as a register
HR 16300 uint16 R V
HR 16340 uint16 R °C One-byte parameter, read as a register
HR 16350 uint16 R % One-byte parameter, read as a register
HR 16360 uint16 R A ×0.01
HR 16370 uint16 R A ×0.01
HR 16600 uint16 R Bit pattern of the digital inputs
HR 16620 uint16 R V ×0.01
HR 16630 uint16 R mA ×0.01
HR 16640 uint16 R mA ×0.01
HR 16650 uint16 R mA ×0.01
HR 16710 uint16 R Bit pattern of the relay outputs; one-byte parameter, read as a register
HR 16900 uint32 ABCD R Alarm word as a bit pattern (bits are in the Programming Guide)
HR 16920 uint32 ABCD R Warning word as a bit pattern (bits are in the Programming Guide)
HR 16940 uint32 ABCD R
HR 15000 uint32 ABCD R days Days the drive has been powered up
HR 15010 uint32 ABCD R h
HR 15020 uint32 ABCD R kWh
HR 15030 uint32 ABCD R
HR 15040 uint16 R
HR 15050 uint16 R
HR 15300 uint16 R Array of the last trips; set the index in register 9 first (one-byte parameter, read as a register)
HR 1220 uint16 RW V
HR 1230 uint16 RW Hz
HR 1240 uint16 RW A ×0.01
HR 1250 uint16 RW RPM
HR 3020 int32 ABCD RW ×0.001
HR 3030 int32 ABCD RW ×0.001
HR 3100 int16 RW % ×0.01 Array of 8 values; set the index in register 9 first
HR 3110 uint16 RW Hz ×0.1
HR 3410 uint32 ABCD RW s ×0.01
HR 3420 uint32 ABCD RW s ×0.01
HR 3510 uint32 ABCD RW s ×0.01
HR 3520 uint32 ABCD RW s ×0.01
HR 4120 uint16 RW Hz ×0.1
HR 4140 uint16 RW Hz ×0.1
HR 4160 uint16 RW %
HR 4170 uint16 RW %
HR 8010 uint16 RW One-byte parameter, written as a register
HR 8020 uint16 RW
HR 8030 uint16 RW s ×0.1
HR 8040 uint16 RW
HR 8300 uint16 RW Takes effect after the drive is powered off and on
HR 8310 uint16 RW
HR 8320 uint16 RW
HR 8330 uint16 RW

Help improve this map