Delta VFD-E Modbus register map
Delta VFD-E compact drive (RS-485 Modbus): control and status words, output measurements, and the main motor and communication parameters
- Official
- 32 registers
- Modbus RTU
- Revision 1 · 2026-11-10
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1
- Serial
- 9600 8N2 · 9600 baud, 8 data bits, none parity, 2 stop bits
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 32 holding registers
- Groups
- 3
- Translation tables
- 12
- Revision
- 1 · 2026-11-10
- Added
- ()
- File
- maps/delta/vfd-e.mbmap.json · 14 KB · history
- SHA-256
- 5396b63944aaf066809c2b7ab0e2906e4ea4916ce88b016736c82c77856022ba
- Manufacturer
- deltaww.com
Sources and notes
- Delta VFD-E Series User Manual · version SW PW V1.11 / CTL V2.11 (04EE), 2008-06 chapter 4, group 9 communication parameters and section 3.5 address list; also on deltaww.com
Source: Delta VFD-E Series User Manual, SW PW V1.11 / CTL V2.11, June 2008 (04EE)
- The drive answers the Modbus functions 03 (read), 06 (write one register) and 10 (write several); a parameter GG.nn is the holding register 0xGGnn (Pr.04.01 is 0x0401), and only one parameter can be read per request.
- Factory serial format is ASCII 7N2 at 9600 bit/s, station 1 (Pr.09.04 = 0). This map assumes RTU 8N2 (Pr.09.04 = 3), so set that parameter on the drive first; the baud rate and station are not changed by it.
- The manual's address list gives units only for current and voltages (one decimal). The 0.01 Hz scale of the frequency registers follows Pr.01.00 and the other frequency parameters, which have two decimals.
- The control word (0x2000) and fault bits (0x2002) are write-only; they are listed as bit fields of the same register. To start, write run and direction together in one 0x2000 write.
- To control the drive over the link set Pr.02.00 = 3 (frequency) and Pr.02.01 = 3 or 4 (run command). Only the most used parameters are listed; any other parameter can be added by its GG.nn address.
- Written from the manufacturer's manual; not tested on a device.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 8192 | uint16 bits 0–1 | W | Bits 1-0 of the command word: stop or run. | |||
| HR | 8192 | uint16 bits 4–5 | W | Bits 5-4 of the command word. | |||
| HR | 8192 | uint16 bits 6–7 | W | Bits 7-6 of the command word: acceleration and deceleration set to use. | |||
| HR | 8193 | uint16 | RW | Hz | ×0.01 | Frequency set point written through the serial link, in 0.01 Hz (5000 = 50.00 Hz). Used when the master frequency source is RS-485 (Pr.02.00 = 3). | |
| HR | 8194 | uint16 bit 0 | W | Bit 0: 1 raises an external fault (EF). | |||
| HR | 8194 | uint16 bit 1 | W | Bit 1: 1 resets the drive after a fault. | |||
| HR | 8448 | uint16 | R | Last fault of the drive; 0 means no fault. | |||
| HR | 8449 | uint16 bits 0–1 | R | Bits 1-0 of the status word: RUN/STOP LED state. | |||
| HR | 8449 | uint16 bit 2 | R | Bit 2: 1 while a jog command is active. | |||
| HR | 8449 | uint16 bits 3–4 | R | Bits 4-3 of the status word. | |||
| HR | 8449 | uint16 bit 8 | R | Bit 8: 1 when the master frequency comes from the serial interface. | |||
| HR | 8449 | uint16 bit 9 | R | Bit 9: 1 when the master frequency comes from an analog signal. | |||
| HR | 8449 | uint16 bit 10 | R | Bit 10: 1 when the operation command comes from the serial interface. | |||
| HR | 8450 | uint16 | R | Hz | ×0.01 | Frequency set point in use. | |
| HR | 8451 | uint16 | R | Hz | ×0.01 | Output frequency of the drive. | |
| HR | 8452 | uint16 | R | A | ×0.1 | Output current. | |
| HR | 8456 | uint16 | R | V | ×0.1 | DC bus voltage. | |
| HR | 8457 | uint16 | R | V | ×0.1 | Output voltage. | |
| HR | 8458 | uint16 | R | °C | Temperature of the IGBT. | ||
| HR | 0 | uint16 | R | Pr.00.00: model code of the drive, which gives its power and rated voltage class. | |||
| HR | 1 | uint16 | R | A | ×0.1 | Pr.00.01: rated current of the drive. | |
| HR | 2 | uint16 | RW | Pr.00.02: 0 = parameters can be written, 1 = read-only, 9 = reset to factory settings (50 Hz base), 10 = reset to factory settings (60 Hz base). | |||
| HR | 256 | uint16 | RW | Hz | ×0.01 | Pr.01.00. | |
| HR | 265 | uint16 | RW | s | ×0.1 | Pr.01.09. The unit is 0.1 s or 0.01 s depending on Pr.01.19. | |
| HR | 266 | uint16 | RW | s | ×0.1 | Pr.01.10. The unit is 0.1 s or 0.01 s depending on Pr.01.19. | |
| HR | 512 | uint16 | RW | Pr.02.00. | |||
| HR | 513 | uint16 | RW | Pr.02.01. | |||
| HR | 2304 | uint16 | RW | Pr.09.00: Modbus station address of the drive (1 to 254). | |||
| HR | 2305 | uint16 | RW | Pr.09.01. | |||
| HR | 2306 | uint16 | RW | Pr.09.02. | |||
| HR | 2307 | uint16 | RW | s | ×0.1 | Pr.09.03: 0 disables the check. | |
| HR | 2308 | uint16 | RW | Pr.09.04: Modbus mode and frame format. |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).