MBMap Registry
  1. Devices
  2. Electro Industries
  3. Shark 250

Electro Industries Shark 250 Modbus register map

Also covers Shark 250T

Electro Industries/GaugeTech Shark 250 cyber-secure revenue meter and Shark 250T transducer, Modbus RTU/ASCII over RS-485

  • Official
  • 159 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
57600 8N1 · 57600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
159 holding registers
Groups
9
Revision
2 · 2026-10-17
Added
()
File
maps/electro-industries/shark-250.mbmap.json · 30 KB · history
SHA-256
63ace0e6062964b441d7211b59e82c7462e4f074de6f43b243d9deb4d8d2c68e
Manufacturer
electroind.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter name holding 1 string[8]
Serial number Meter serial number holding 9 string[8]
Firmware Firmware version holding 18 string[2]

Sources and notes

  • Shark 250 Meter Modbus Manual · version V.1.07
    Doc# E169711, chapter 4, Modbus register map (Rev 3); downloaded through the vendor's download form

Source: Electro Industries/GaugeTech, "Shark 250 Meter Modbus Manual", V.1.07 (Doc# E169711)

  • All registers are holding registers (FC03 read, FC06/FC10 write). Addresses are the manual's 1-based decimal register numbers (register 1000 = PDU address 0x03E7).
  • 32-bit values and floats span two registers with the high-order half first.
  • Factory settings of the RS-485 port (COM2): 57600 baud, no parity, address 1, Modbus RTU (setup registers 30026 and 30027).
  • Energy registers are integers formatted by registers 30117 (Wh and VAh) and 30118 (varh): energy scale (unit, kilo or mega), digit count and decimal places. The factory format is 8 digits in kilo units with no decimals.
  • Q1+Q4 energy and power are labelled delivered and Q2+Q3 received by default (registers 30297-30344). Per-phase power and power factor are non-zero only with a wye hookup.
  • Not in this map: the quadrant, Q, Vh, Ah, V2t and I2t accumulators, uncompensated readings, minimum/maximum blocks, harmonics and waveforms, option cards, aggregators, time of use, programmable settings other than the energy formats, secondary readings and logs.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 string[8] R
HR 9 string[8] R
HR 17 uint16 R Bits 9-8: 0 panel meter, 1 transducer; bits 7-0: V-switch
HR 18 string[2] R
HR 20 uint16 R
HR 21 uint16 R
HR 22 uint16 R
HR 23 string[2] R
HR 25 uint16 R
HR 26 uint16 R
HR 88 string[4] R
HR 1000 float32 ABCD R V
HR 1002 float32 ABCD R V
HR 1004 float32 ABCD R V
HR 1006 float32 ABCD R V
HR 1008 float32 ABCD R V
HR 1010 float32 ABCD R V
HR 1012 float32 ABCD R A
HR 1014 float32 ABCD R A
HR 1016 float32 ABCD R A
HR 1018 float32 ABCD R W
HR 1020 float32 ABCD R var
HR 1022 float32 ABCD R VA
HR 1024 float32 ABCD R
HR 1026 float32 ABCD R Hz
HR 1028 float32 ABCD R A
HR 1030 float32 ABCD R W
HR 1032 float32 ABCD R W
HR 1034 float32 ABCD R W
HR 1036 float32 ABCD R var
HR 1038 float32 ABCD R var
HR 1040 float32 ABCD R var
HR 1042 float32 ABCD R VA
HR 1044 float32 ABCD R VA
HR 1046 float32 ABCD R VA
HR 1048 float32 ABCD R
HR 1050 float32 ABCD R
HR 1052 float32 ABCD R
HR 1054 float32 ABCD R V
HR 1056 float32 ABCD R V
HR 1058 float32 ABCD R V
HR 1060 int16 R ° ×0.1
HR 1061 int16 R ° ×0.1
HR 1062 int16 R ° ×0.1
HR 1063 uint16 R % ×0.01
HR 1064 uint16 R % ×0.01
HR 1065 uint16 R % ×0.01
HR 1075 float32 ABCD R V
HR 1077 float32 ABCD R V
HR 1079 float32 ABCD R A
HR 1500 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1502 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1504 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1506 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1508 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1510 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1512 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1514 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1516 int32 ABCD R VAh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1518 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1520 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1522 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1524 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1526 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1528 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1530 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1532 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1534 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1536 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1538 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1540 int32 ABCD R Wh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1542 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1544 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1546 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1548 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1550 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1552 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1554 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1556 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1558 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1560 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1562 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1564 int32 ABCD R varh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1566 int32 ABCD R VAh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1568 int32 ABCD R VAh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 1570 int32 ABCD R VAh Integer energy formatted by register 30117 (Wh, VAh) or 30118 (varh)
HR 2000 float32 ABCD R A
HR 2002 float32 ABCD R A
HR 2004 float32 ABCD R A
HR 2006 float32 ABCD R W
HR 2008 float32 ABCD R var
HR 2010 float32 ABCD R W
HR 2012 float32 ABCD R var
HR 2014 float32 ABCD R VA
HR 2016 float32 ABCD R
HR 2018 float32 ABCD R
HR 2020 float32 ABCD R A
HR 2022 float32 ABCD R W
HR 2024 float32 ABCD R W
HR 2026 float32 ABCD R W

Help improve this map