MBMap Registry
  1. Devices
  2. Embrasul
  3. MD20

Embrasul MD20 Modbus register map

Three-phase multifunction energy meter with RS485 Modbus RTU

  • Official
  • 171 registers
  • Modbus RTU
  • Revision 1 · 2026-11-11

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
171 holding registers
Groups
12
Translation tables
7
Revision
1 · 2026-11-11
Added
()
File
maps/embrasul/md20.mbmap.json · 37 KB · history
SHA-256
ab0d075642211ca3cfa56a37311590dc6ec74b8a82bd7f5f3309bd7e8b4e395c
Manufacturer
embrasul.com.br

Sources and notes

  • Manual de Instalação e Operação do MD20
    Sections 7 and 8, supplied with the map request

Source: Embrasul, Manual de Instalação e Operação do MD20, section 7 (Modbus RTU) and section 8 (register list)

  • Register addresses are the decimal ones in the manual, used as they are (address_base 0): the manual's read example for the phase voltages sends start address 1000 (0x03E8). Function 0x03 reads; function 0x10 writes.
  • Data bytes are sent high byte first and the example (0x435C0000 = 220) shows a 32-bit float with the high word first, so the word order is big. The manual does not state the word order of the 32-bit integers; big is assumed.
  • Registers marked R/WC in the manual (clock, communication, power parameters and the others) are changed with the configuration command block: write an instruction code and its parameters with function 0x10 at registers 300 to 423, then read the result code at 425 (0 = accepted). They are marked read-only here because they cannot be written directly. The instruction codes are in sections 8.1 to 8.8 and are not mapped.
  • Energy registers are integers in 0.1 kWh, 0.1 kvarh and 0.1 kVAh; the scale of 0.1 gives kWh, kvarh and kVAh.
  • Names follow the manual's aliases. I1VGMax and I1VGMin in the manual are the maximum and minimum of the average three-phase current; the manual lists phase B minimum power at 6078, which is taken as the 6072 the sequence implies.
  • The peak demand dates (5120, 5128, 5136), the demand reset time (5002) and the unmapped date-time values use four registers of the manual's date format and are not mapped.
  • Serial settings: 2400, 4800, 9600 or 19200 baud, no, odd or even parity, 8 data bits, 1 stop bit, address 1 to 247. Defaults are 9600 baud, no parity, address 1.
AreaAddressNameTypeAccessUnitScaleDescription
HR 50 string[20] R UTF-8 text
HR 70 uint32 ABCD R
HR 72 uint16 R Format X.Y.ZTT
HR 73 uint16 R 0 to 99, years since 2000
HR 74 uint16 R Month in the high byte, day in the low byte
HR 75 uint16 R Hour in the high byte, minute in the low byte
HR 76 uint16 R 0 to 59999 (seconds and milliseconds)
HR 80 uint16 R 1 to 247
HR 81 uint16 R
HR 82 uint16 R
HR 90 uint16 R
HR 91 uint32 ABCD R V/V ×0.0001 Sent as the ratio multiplied by 10000
HR 93 uint32 ABCD R A/A ×0.0001 Sent as the ratio multiplied by 10000
HR 150 uint16 R
HR 151 uint16 R
HR 152 uint16 R
HR 1000 float32 ABCD R V
HR 1002 float32 ABCD R V
HR 1004 float32 ABCD R V
HR 1006 float32 ABCD R V
HR 1008 float32 ABCD R V
HR 1010 float32 ABCD R V
HR 1012 float32 ABCD R V
HR 1014 float32 ABCD R V
HR 1016 float32 ABCD R A
HR 1018 float32 ABCD R A
HR 1020 float32 ABCD R A
HR 1022 float32 ABCD R A
HR 1026 float32 ABCD R W
HR 1028 float32 ABCD R W
HR 1030 float32 ABCD R W
HR 1032 float32 ABCD R W
HR 1034 float32 ABCD R var
HR 1036 float32 ABCD R var
HR 1038 float32 ABCD R var
HR 1040 float32 ABCD R var
HR 1042 float32 ABCD R VA
HR 1044 float32 ABCD R VA
HR 1046 float32 ABCD R VA
HR 1048 float32 ABCD R VA
HR 1050 float32 ABCD R
HR 1052 float32 ABCD R
HR 1054 float32 ABCD R
HR 1056 float32 ABCD R
HR 1058 float32 ABCD R
HR 1060 float32 ABCD R
HR 1062 float32 ABCD R
HR 1064 float32 ABCD R
HR 1066 float32 ABCD R Hz
HR 2000 float32 ABCD R %
HR 2002 float32 ABCD R %
HR 2004 float32 ABCD R %
HR 2006 float32 ABCD R %
HR 2008 float32 ABCD R %
HR 2010 float32 ABCD R %
HR 2012 float32 ABCD R %
HR 2014 float32 ABCD R %
HR 4000 uint32 ABCD R kWh ×0.1
HR 4002 uint32 ABCD R kWh ×0.1
HR 4004 uint32 ABCD R kWh ×0.1
HR 4006 uint32 ABCD R kWh ×0.1
HR 4008 uint32 ABCD R kWh ×0.1
HR 4010 uint32 ABCD R kWh ×0.1
HR 4012 uint32 ABCD R kWh ×0.1
HR 4014 uint32 ABCD R kWh ×0.1
HR 4024 uint32 ABCD R kvarh ×0.1
HR 4026 uint32 ABCD R kvarh ×0.1
HR 4028 uint32 ABCD R kvarh ×0.1
HR 4030 uint32 ABCD R kvarh ×0.1
HR 4032 uint32 ABCD R kvarh ×0.1
HR 4034 uint32 ABCD R kvarh ×0.1
HR 4036 uint32 ABCD R kvarh ×0.1
HR 4038 uint32 ABCD R kvarh ×0.1
HR 4048 uint32 ABCD R kVAh ×0.1
HR 4050 uint32 ABCD R kVAh ×0.1
HR 4052 uint32 ABCD R kVAh ×0.1
HR 4054 uint32 ABCD R kVAh ×0.1
HR 5000 uint16 R
HR 5001 uint16 R min
HR 5020 float32 ABCD R W
HR 5022 float32 ABCD R W
HR 5028 float32 ABCD R W
HR 5030 float32 ABCD R W
HR 5036 float32 ABCD R W
HR 5038 float32 ABCD R W
HR 5044 float32 ABCD R W
HR 5046 float32 ABCD R W
HR 5052 float32 ABCD R var
HR 5054 float32 ABCD R var
HR 5060 float32 ABCD R var
HR 5062 float32 ABCD R var
HR 5068 float32 ABCD R var
HR 5070 float32 ABCD R var
HR 5076 float32 ABCD R var
HR 5078 float32 ABCD R var
HR 5084 float32 ABCD R VA
HR 5086 float32 ABCD R VA
HR 5092 float32 ABCD R VA
HR 5094 float32 ABCD R VA
HR 5100 float32 ABCD R VA