GE EPM 6000 Modbus register map

Also covers EPM 6000T

GE Multilin EPM 6000 power meter and EPM 6000T transducer, Modbus RTU/ASCII over the optional RS-485 port

  • Official
  • 97 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
57600 8N1 · 57600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
97 holding registers
Groups
10
Revision
2 · 2026-10-17
Added
()
File
maps/ge/epm-6000.mbmap.json · 18 KB · history
SHA-256
2b91ad58a57579d9ff63427294bf5bad7d9e7d39fb3fb1abcf027d3edd7c191f
Manufacturer
gevernova.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter name holding 0 string[8]
Serial number Meter serial number holding 8 string[8]
Firmware Firmware version holding 17 string[2]

Sources and notes

Source: GE Vernova Multilin, "EPM 6000/6000T Power Meter Instruction Manual", software revision 1.17, GEK-106558G (1601-0215-A8)

  • All registers are holding registers (FC03 read, FC06/FC10 write). Addresses here are the zero-based hex addresses of the manual; the manual's decimal register numbers are one higher (e.g. 0x03E7 = register 1000).
  • 32-bit values and floats span two registers with the high-order half first.
  • Factory settings in normal mode are 57600 baud, address 1, Modbus RTU, 8 bits, no parity. For 5 seconds after power-up the RS-485 port also answers at 9600 baud, address 1, and keeps those settings for 5 minutes once used.
  • Energy registers are integers whose scale, digit count and decimal places follow the power and energy format setting (0x7535). Reset the energy after changing that format.
  • The 3-phase power readings at 0x0383-0x0388 are updated every 6 cycles; the other readings every 60 cycles. THD reads 65535 when it is not available (needs the THD option).
  • Not in this map: the individual harmonic magnitudes, the meter programming and encryption blocks, programmable settings and the 12-bit readings block (0x9C40-0x9CA3).
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 string[8] R
HR 8 string[8] R
HR 16 uint16 R
HR 17 string[2] R
HR 19 uint16 R
HR 20 uint16 R
HR 21 uint16 R
HR 39 string[8] R
HR 899 float32 ABCD R W
HR 901 float32 ABCD R var
HR 903 float32 ABCD R VA
HR 999 float32 ABCD R V
HR 1001 float32 ABCD R V
HR 1003 float32 ABCD R V
HR 1005 float32 ABCD R V
HR 1007 float32 ABCD R V
HR 1009 float32 ABCD R V
HR 1011 float32 ABCD R A
HR 1013 float32 ABCD R A
HR 1015 float32 ABCD R A
HR 1017 float32 ABCD R W
HR 1019 float32 ABCD R var
HR 1021 float32 ABCD R VA
HR 1023 float32 ABCD R
HR 1025 float32 ABCD R Hz
HR 1027 float32 ABCD R A
HR 1099 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1101 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1103 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1105 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1107 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1109 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1111 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1113 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1115 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1999 float32 ABCD R A
HR 2001 float32 ABCD R A
HR 2003 float32 ABCD R A
HR 2005 float32 ABCD R W
HR 2007 float32 ABCD R var
HR 2009 float32 ABCD R W
HR 2011 float32 ABCD R var
HR 2013 float32 ABCD R VA
HR 2015 float32 ABCD R
HR 2017 float32 ABCD R
HR 2999 float32 ABCD R V
HR 3001 float32 ABCD R V
HR 3003 float32 ABCD R V
HR 3005 float32 ABCD R V
HR 3007 float32 ABCD R V
HR 3009 float32 ABCD R V
HR 3011 float32 ABCD R A
HR 3013 float32 ABCD R A
HR 3015 float32 ABCD R A
HR 3017 float32 ABCD R W
HR 3019 float32 ABCD R var
HR 3021 float32 ABCD R W
HR 3023 float32 ABCD R var
HR 3025 float32 ABCD R VA
HR 3027 float32 ABCD R
HR 3029 float32 ABCD R
HR 3031 float32 ABCD R Hz
HR 3099 float32 ABCD R V
HR 3101 float32 ABCD R V
HR 3103 float32 ABCD R V
HR 3105 float32 ABCD R V
HR 3107 float32 ABCD R V
HR 3109 float32 ABCD R V
HR 3111 float32 ABCD R A
HR 3113 float32 ABCD R A
HR 3115 float32 ABCD R A
HR 3117 float32 ABCD R W
HR 3119 float32 ABCD R var
HR 3121 float32 ABCD R W
HR 3123 float32 ABCD R var
HR 3125 float32 ABCD R VA
HR 3127 float32 ABCD R
HR 3129 float32 ABCD R
HR 3131 float32 ABCD R Hz
HR 3999 uint16 R % ×0.1
HR 4000 uint16 R % ×0.1
HR 4001 uint16 R % ×0.1
HR 4002 uint16 R % ×0.1
HR 4003 uint16 R % ×0.1
HR 4004 uint16 R % ×0.1
HR 4099 int16 R ° ×0.1
HR 4100 int16 R ° ×0.1
HR 4101 int16 R ° ×0.1
HR 4102 int16 R ° ×0.1
HR 4103 int16 R ° ×0.1
HR 4104 int16 R ° ×0.1
HR 4999 uint16 R
HR 5000 uint16 R Bit-mapped: high byte = setpoint 1 of limits 8..1, low byte = setpoint 2; 0 = in limit, 1 = out
HR 5001 uint32 ABCD R s ×0.004
HR 19999 uint16 W Write the password (5555 when passwords are disabled)
HR 20000 uint16 W Write the password (5555 when passwords are disabled)
HR 24999 uint16 W Write the password (5555 when passwords are disabled)