MBMap Registry
  1. Devices
  2. GE
  3. EPM 7000

GE EPM 7000 Modbus register map

Also covers EPM 7000T

GE Multilin EPM 7000 power quality meter and EPM 7000T transducer, Modbus RTU/ASCII over RS-485

  • Official
  • 172 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
57600 8N1 · 57600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
172 holding registers
Groups
8
Revision
2 · 2026-10-17
Added
()
File
maps/ge/epm-7000.mbmap.json · 35 KB · history
SHA-256
c68f27e67e0e07616347261da8859e5ead7b0f696dca705e0fa75708f576a885
Manufacturer
gevernova.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter name holding 0 string[8]
Serial number Meter serial number holding 8 string[8]
Firmware Firmware version holding 17 string[2]

Sources and notes

Source: GE Vernova Multilin, "Multilin EPM 7000/7000T Power Quality Meter Instruction Manual", product revision 1.10 (1601-0266-A6)

  • All registers are holding registers (FC03 read, FC06/FC10 write). Addresses here are the zero-based hex addresses of the manual; the manual's decimal register numbers are one higher (e.g. 0x03E7 = register 1000).
  • 32-bit values and floats span two registers with the high-order half first.
  • Factory settings in normal mode are 57600 baud, address 1, Modbus RTU. Right after power-up the RS-485 port also answers at 9600 baud, address 1 (factory initial default settings).
  • Energy registers are integers whose scale, digit count and decimal places follow the power and energy format setting (register 0x7535). Reset the energy after changing that format.
  • Per-phase power and power factor are non-zero only with a wye hookup. The EPM 7100 is not covered by this manual.
  • Not in this map: the integer readings block, uncompensated readings, minimum/maximum blocks and timestamps, harmonic and waveform registers, option card blocks, programmable settings, secondary readings and log retrieval.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 string[8] R
HR 8 string[8] R
HR 16 uint16 R
HR 17 string[2] R
HR 19 uint16 R
HR 20 uint16 R
HR 21 uint16 R
HR 22 string[2] R
HR 24 uint16 R
HR 25 uint16 R
HR 26 string[4] R
HR 999 float32 ABCD R V
HR 1001 float32 ABCD R V
HR 1003 float32 ABCD R V
HR 1005 float32 ABCD R V
HR 1007 float32 ABCD R V
HR 1009 float32 ABCD R V
HR 1011 float32 ABCD R A
HR 1013 float32 ABCD R A
HR 1015 float32 ABCD R A
HR 1017 float32 ABCD R W
HR 1019 float32 ABCD R var
HR 1021 float32 ABCD R VA
HR 1023 float32 ABCD R
HR 1025 float32 ABCD R Hz
HR 1027 float32 ABCD R A
HR 1029 float32 ABCD R W
HR 1031 float32 ABCD R W
HR 1033 float32 ABCD R W
HR 1035 float32 ABCD R var
HR 1037 float32 ABCD R var
HR 1039 float32 ABCD R var
HR 1041 float32 ABCD R VA
HR 1043 float32 ABCD R VA
HR 1045 float32 ABCD R VA
HR 1047 float32 ABCD R
HR 1049 float32 ABCD R
HR 1051 float32 ABCD R
HR 1053 float32 ABCD R V
HR 1055 float32 ABCD R V
HR 1057 float32 ABCD R V
HR 1059 int16 R ° ×0.1
HR 1060 int16 R ° ×0.1
HR 1061 int16 R ° ×0.1
HR 1062 uint16 R % ×0.01
HR 1063 uint16 R % ×0.01
HR 1064 uint16 R % ×0.01
HR 1499 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1501 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1503 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1505 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1507 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1509 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1511 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1513 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1515 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1517 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1519 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1521 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1523 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1525 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1527 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1529 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1531 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1533 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1535 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1537 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1539 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1541 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1543 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1545 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1547 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1549 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1551 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1553 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1555 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1557 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1559 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1561 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1563 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1565 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1567 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1569 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1571 uint32 ABCD R
HR 1573 uint32 ABCD R
HR 1575 uint32 ABCD R
HR 1577 uint32 ABCD R
HR 1579 uint32 ABCD R
HR 1581 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1583 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1585 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1587 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1589 int32 ABCD R VAh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1591 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1593 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1595 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1597 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1599 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1601 int32 ABCD R Wh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)
HR 1603 int32 ABCD R varh Integer energy; scale and decimal places follow the power and energy format setting (0x7535)