GoodWe Hybrid inverters (third-party EMS protocol) Modbus register map

GoodWe hybrid inverters (ET, EH, BH, BT, ESA and newer) for monitoring and EMS control

  • Official
  • 169 registers
  • Modbus TCP and RTU
  • Revision 1 · 2026-10-14
  • Identity: model, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
247
TCP port
502
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
100 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
169 holding registers
Groups
13
Revision
1 · 2026-10-14
Added
()
File
maps/goodwe/hybrid-ems.mbmap.json · 28 KB · history
SHA-256
c4ad9fb0ebd926354c6b6d5591f5751981a9199a84712f2488be174bfe2a4ba3
Manufacturer
goodwe.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Inverter serial number holding 35003 string[8]
Model Model name holding 35011 string[5]

Sources and notes

Source: GoodWe, Technical Information: Third-Party EMS Protocol MODBUS V1.1.1

  • Every register is a holding register: read with FC03, write with FC16.
  • The default slave address is 247 (RTU and TCP). Modbus TCP must be enabled through SEMS+.
  • Read at most 100 registers at a time, about once per second; the EMS mode and power registers must be written every second.
  • Not every model has every register: the descriptions say which models a register is for when the protocol does.
AreaAddressNameTypeAccessUnitScaleDescription
HR 33001 uint32 ABCD R W
HR 33004 uint32 ABCD R W
HR 33006 uint32 ABCD R W
HR 35001 uint16 R W
HR 35003 string[8] R
HR 35011 string[5] R EH and ET PLUS only
HR 35060 string[16] R
HR 35103 uint16 R V ×0.1
HR 35104 uint16 R A ×0.1
HR 35107 uint16 R V ×0.1
HR 35108 uint16 R A ×0.1
HR 35111 uint16 R V ×0.1
HR 35112 uint16 R A ×0.1
HR 35115 uint16 R V ×0.1
HR 35116 uint16 R A ×0.1
HR 35304 uint16 R V ×0.1
HR 35305 uint16 R A ×0.1
HR 35306 uint16 R V ×0.1
HR 35307 uint16 R A ×0.1
HR 35308 uint16 R V ×0.1
HR 35309 uint16 R A ×0.1
HR 35310 uint16 R V ×0.1
HR 35311 uint16 R A ×0.1
HR 35312 uint16 R V ×0.1
HR 35313 uint16 R A ×0.1
HR 35314 uint16 R V ×0.1
HR 35315 uint16 R A ×0.1
HR 35316 uint16 R V ×0.1
HR 35317 uint16 R A ×0.1
HR 35318 uint16 R V ×0.1
HR 35319 uint16 R A ×0.1
HR 35320 uint16 R V ×0.1
HR 35321 uint16 R A ×0.1
HR 35322 uint16 R V ×0.1
HR 35323 uint16 R A ×0.1
HR 35324 uint16 R V ×0.1
HR 35325 uint16 R A ×0.1
HR 35326 uint16 R V ×0.1
HR 35327 uint16 R A ×0.1
HR 35423 uint16 R V ×0.1
HR 35424 uint16 R A ×0.1
HR 35425 uint16 R V ×0.1
HR 35426 uint16 R A ×0.1
HR 35427 uint16 R V ×0.1
HR 35428 uint16 R A ×0.1
HR 35429 uint16 R V ×0.1
HR 35430 uint16 R A ×0.1
HR 35345 uint16 R A ×0.1
HR 35105 uint32 ABCD R W 200 ms average
HR 35337 uint16 R W 200 ms average
HR 35346 uint16 R A ×0.1
HR 35109 uint32 ABCD R W 200 ms average
HR 35338 uint16 R W 200 ms average
HR 35347 uint16 R A ×0.1
HR 35113 uint32 ABCD R W 200 ms average
HR 35339 uint16 R W 200 ms average
HR 35348 uint16 R A ×0.1
HR 35117 uint32 ABCD R W 200 ms average
HR 35340 uint16 R W 200 ms average
HR 35349 uint16 R A ×0.1
HR 35341 uint16 R W 200 ms average
HR 35350 uint16 R A ×0.1
HR 35342 uint16 R W 200 ms average
HR 35351 uint16 R A ×0.1
HR 35343 uint16 R W 200 ms average
HR 35352 uint16 R A ×0.1
HR 35344 uint16 R W 200 ms average
HR 35415 uint16 R A ×0.1
HR 35407 uint16 R W 200 ms average
HR 35416 uint16 R A ×0.1
HR 35408 uint16 R W 200 ms average
HR 35121 uint16 R V ×0.1
HR 35122 uint16 R A ×0.1
HR 35123 uint16 R Hz ×0.01
HR 35124 int32 ABCD R W
HR 35126 uint16 R V ×0.1
HR 35127 uint16 R A ×0.1
HR 35128 uint16 R Hz ×0.01
HR 35129 int32 ABCD R W
HR 35131 uint16 R V ×0.1
HR 35132 uint16 R A ×0.1
HR 35133 uint16 R Hz ×0.01
HR 35134 int32 ABCD R W
HR 35137 int32 ABCD R W
HR 35139 int32 ABCD R W On-grid power: the meter reading when the meter is connected, otherwise the inverter on-grid port
HR 35141 int32 ABCD R var
HR 35143 int32 ABCD R VA
HR 35169 int32 ABCD R W
HR 35171 int32 ABCD R W On-grid load, backup not included
HR 35181 int16 R A ×0.1
HR 35182 int32 ABCD R W 200 ms average
HR 35184 uint16 R
HR 35186 uint16 R Code from table 1-1 of the protocol
HR 35187 uint16 R
HR 35212 uint16 R
HR 35262 uint16 R V ×0.1
HR 35263 int16 R A ×0.1
HR 35264 int32 ABCD R W
HR 35267 uint16 R
HR 35301 uint32 ABCD R W