Hager ECR / ECA energy meters Modbus register map

Also covers ECR140D, ECR180D, ECR181D, ECA180D, ECA181D, ECR380D, ECR381D, ECR382D, ECA380D, ECA381D, ECA382D, ECR310D, ECR311D, ECR312D, ECA310D, ECA311D, ECA312D, ECR300C, ECR301C, ECR302C, ECA300C, ECA301C, ECA302C

Hager single- and three-phase MID energy meters with Modbus RTU (ECR, screw terminals) or Agardio RJ45 (ECA)

  • Official
  • 134 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
134 holding registers
Groups
8
Revision
2 · 2026-10-17
Added
()
File
maps/hager/ecn-ecp-ect-ecm-ecr-eca.mbmap.json · 24 KB · history
SHA-256
83504c74c752fe37b6a392204dbef7f245d5db6d6e07c0219d1fa56f8a548aca
Manufacturer
hager.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Product code holding 4112 string[16]
Firmware Software version holding 4128 uint32 ABCD
Serial number Serial number holding 4196 string[16]

Sources and notes

Source: Hager Electro / Herholdt Controls, "Modbus Tables Summary", rev. 1.14 (October 2022)

  • All registers are holding registers read with FC03; the writable ones use FC06.
  • 32-bit values are big-endian, high word first. Strings carry two characters per register, first character in the high byte.
  • Values a model does not provide read as all ones (0xFFFF, 0xFFFFFFFF, or 0x7FFF/0x7FFFFFFF for signed values). Single-phase meters have no L2/L3 values; the 1P 40 A meter has no partial energies.
  • On CT-connected meters (ECx30xC) currents, powers and energies are primary values.
  • The table gives no communication defaults; address, baud rate and parity are set on the meter and can be read at 0xC040-0xC041.
  • Not in this map: the triple single-phase meters (ECx180T, ECx300T) energy tables, secondary-side values of CT meters, overflow details and the Read Device Identification and user block functions.
AreaAddressNameTypeAccessUnitScaleDescription
HR 4096 string[16] R
HR 4112 string[16] R Commercial reference, e.g. ECR380D
HR 4128 uint32 ABCD R Version a.b.c coded as 0xaabbcc00
HR 4130 string[16] R
HR 4146 string[16] R
HR 4162 string[16] R
HR 4178 string[16] R
HR 4194 uint32 ABCD R Version a.b.c coded as 0xaabbcc00
HR 4196 string[16] R RRYYWWNNNN: reference, year, week, number
HR 4212 string[2] R
HR 4214 uint16 R
HR 4215 uint16 R
HR 45056 uint16 R V ×0.01
HR 45057 uint16 R V ×0.01
HR 45058 uint16 R V ×0.01
HR 45059 uint16 R V ×0.01
HR 45060 uint16 R V ×0.01
HR 45061 uint16 R V ×0.01
HR 45062 uint16 R Hz ×0.01
HR 45065 uint32 ABCD R A ×0.001
HR 45067 uint32 ABCD R A ×0.001
HR 45069 uint32 ABCD R A ×0.001
HR 45071 uint32 ABCD R A ×0.001
HR 45073 int32 ABCD R kW ×0.01
HR 45075 int32 ABCD R kvar ×0.01
HR 45077 uint32 ABCD R kVA ×0.01
HR 45079 int16 R ×0.001 P/S; 1.000 when no power flows
HR 45080 int16 R ×0.001 P/S; 1.000 when no power flows
HR 45081 int32 ABCD R kW ×0.01
HR 45083 int32 ABCD R kW ×0.01
HR 45085 int32 ABCD R kW ×0.01
HR 45087 int32 ABCD R kvar ×0.01
HR 45089 int32 ABCD R kvar ×0.01
HR 45091 int32 ABCD R kvar ×0.01
HR 45093 uint32 ABCD R kVA ×0.01
HR 45095 uint32 ABCD R kVA ×0.01
HR 45097 uint32 ABCD R kVA ×0.01
HR 45099 int16 R ×0.001
HR 45100 int16 R ×0.001
HR 45101 int16 R ×0.001
HR 45102 int16 R ×0.001
HR 45103 int16 R ×0.001
HR 45104 int16 R ×0.001
HR 45152 uint32 ABCD R kWh
HR 45154 uint32 ABCD R kvarh
HR 45156 uint32 ABCD R kWh
HR 45158 uint32 ABCD R kvarh
HR 45160 uint32 ABCD R kWh
HR 45162 uint32 ABCD R kWh
HR 45164 uint32 ABCD R Wh Firmware 1.2 and later; wraps at the 32-bit limit
HR 45166 uint32 ABCD R Wh Firmware 1.2 and later; wraps at the 32-bit limit
HR 45168 uint32 ABCD R kWh Three-phase meters, firmware 1.2 and later: net (vector) summation of the phases
HR 45170 uint32 ABCD R kWh Three-phase meters, firmware 1.2 and later
HR 45172 uint32 ABCD R Wh Three-phase meters, firmware 1.2 and later
HR 45174 uint32 ABCD R Wh Three-phase meters, firmware 1.2 and later
HR 45248 uint32 ABCD R kWh
HR 45250 uint32 ABCD R kWh
HR 45252 uint32 ABCD R kWh
HR 45254 uint32 ABCD R kWh
HR 45256 uint32 ABCD R kWh
HR 45258 uint32 ABCD R kWh
HR 45260 uint32 ABCD R kWh
HR 45262 uint32 ABCD R kWh
HR 45264 uint32 ABCD R kWh
HR 45266 uint32 ABCD R kWh
HR 45268 uint32 ABCD R kWh
HR 45270 uint32 ABCD R kWh
HR 45272 uint32 ABCD R kWh
HR 45274 uint32 ABCD R kWh
HR 45276 uint32 ABCD R kWh
HR 45278 uint32 ABCD R kWh
HR 45280 uint32 ABCD R kvarh
HR 45282 uint32 ABCD R kvarh
HR 45284 uint32 ABCD R kvarh
HR 45286 uint32 ABCD R kvarh
HR 45288 uint32 ABCD R kvarh
HR 45290 uint32 ABCD R kvarh
HR 45292 uint32 ABCD R kvarh
HR 45294 uint32 ABCD R kvarh
HR 45296 uint32 ABCD R kvarh
HR 45298 uint32 ABCD R kvarh
HR 45300 uint32 ABCD R kvarh
HR 45302 uint32 ABCD R kvarh
HR 45304 uint32 ABCD R kvarh
HR 45306 uint32 ABCD R kvarh
HR 45308 uint32 ABCD R kvarh
HR 45310 uint32 ABCD R kvarh
HR 45376 uint32 ABCD R kWh
HR 45378 uint32 ABCD R kWh
HR 45380 uint32 ABCD R kWh
HR 45382 uint32 ABCD R kWh
HR 45384 uint32 ABCD R kWh
HR 45386 uint32 ABCD R kWh
HR 45388 uint32 ABCD R kWh
HR 45390 uint32 ABCD R kWh
HR 45392 uint32 ABCD R kWh
HR 45394 uint32 ABCD R kWh
HR 45396 uint32 ABCD R kWh
HR 45398 uint32 ABCD R kWh
HR 45400 uint32 ABCD R kWh