MBMap Registry
  1. Devices
  2. IME
  3. Nemo 96

IME Nemo 96 Modbus register map

Also covers Nemo 96HD, Nemo 96HD+, Nemo 96 HD

96 mm panel multifunction meter Nemo 96HD/HD+ with the RS-485 Modbus module

  • Official
  • 104 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
104 holding registers
Groups
3
Revision
2 · 2026-10-17
Firmware
from 2.30
Added
()
File
maps/ime/nemo-96.mbmap.json · 21 KB · history
SHA-256
620f1c382ef3145b9530ab9e76aec3b58a66c2516d8f554e7e1575b6d57c6cd4
Manufacturer
imeitaly.com

Sources and notes

Source: IME, "Nemo 96HD/HD+ Modbus communication protocol", PR 106 rev. 4 (2012-12-18), firmware 2.30 and later

  • Read with FC03; 32-bit values are most significant word first. Values marked BYTE in the protocol are sent as a word with a zero high byte.
  • Powers in the 0x1000 block are W/var/VA divided by 100 when KTA x KTV < 5000 and in W/var/VA otherwise; the signed powers at 0x1518 are always W/var.
  • Energies are split into a low part in Wh (up to 999999) and a high part in MWh.
  • Not in this map: the first address table (0x0301-0x03FF), which carries the same values, and the setup and module parameter blocks (0x2000-0x2700).
AreaAddressNameTypeAccessUnitScaleDescription
HR 4096 uint32 ABCD R V ×0.001
HR 4098 uint32 ABCD R V ×0.001
HR 4100 uint32 ABCD R V ×0.001
HR 4102 uint32 ABCD R A ×0.001
HR 4104 uint32 ABCD R A ×0.001
HR 4106 uint32 ABCD R A ×0.001
HR 4108 uint32 ABCD R A ×0.001
HR 4110 uint32 ABCD R V ×0.001
HR 4112 uint32 ABCD R V ×0.001
HR 4114 uint32 ABCD R V ×0.001
HR 4116 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4118 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4120 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4122 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4123 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4124 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4126 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4128 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4130 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4132 uint16 R ×0.01
HR 4133 uint16 R
HR 4134 uint16 R Hz ×0.1
HR 4135 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4137 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4139 uint16 R min
HR 4140 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4142 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4144 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4146 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4147 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4148 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4149 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4151 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4153 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4155 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4156 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4157 uint16 R W, var or VA / 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4158 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4160 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4162 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4164 uint16 R ×0.01
HR 4165 uint16 R ×0.01
HR 4166 uint16 R ×0.01
HR 4167 uint16 R
HR 4168 uint16 R
HR 4169 uint16 R
HR 4170 uint16 R %
HR 4171 uint16 R %
HR 4172 uint16 R %
HR 4173 uint16 R %
HR 4174 uint16 R %
HR 4175 uint16 R %
HR 4176 uint32 ABCD R A ×0.001
HR 4178 uint32 ABCD R A ×0.001
HR 4180 uint32 ABCD R A ×0.001
HR 4182 uint32 ABCD R A ×0.001
HR 4184 uint32 ABCD R A ×0.001
HR 4186 uint32 ABCD R A ×0.001
HR 4188 uint32 ABCD R A ×0.001
HR 4190 uint32 ABCD R V ×0.001
HR 4192 uint32 ABCD R V ×0.001
HR 4194 uint32 ABCD R V ×0.001
HR 4196 uint32 ABCD R V ×0.001
HR 4198 uint32 ABCD R V ×0.001
HR 4200 uint32 ABCD R V ×0.001
HR 4202 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4204 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4206 uint16 R h
HR 4207 uint16 R
HR 4208 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4210 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4212 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4214 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4216 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4218 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4608 uint16 R
HR 4609 uint16 R ×0.1
HR 4610 uint32 ABCD R
HR 4612 uint16 R
HR 4613 uint16 R
HR 5376 uint32 ABCD R kWh ×0.001 Low part, in Wh up to 999999
HR 5378 uint32 ABCD R MWh High part, in MWh
HR 5380 uint32 ABCD R kvarh ×0.001 Low part, in Wh up to 999999
HR 5382 uint32 ABCD R Mvarh High part, in MWh
HR 5384 uint32 ABCD R kWh ×0.001 Low part, in Wh up to 999999
HR 5386 uint32 ABCD R MWh High part, in MWh
HR 5388 uint32 ABCD R kvarh ×0.001 Low part, in Wh up to 999999
HR 5390 uint32 ABCD R Mvarh High part, in MWh
HR 5392 uint32 ABCD R kWh ×0.001 Low part, in Wh up to 999999
HR 5394 uint32 ABCD R MWh High part, in MWh
HR 5396 uint32 ABCD R kvarh ×0.001 Low part, in Wh up to 999999
HR 5398 uint32 ABCD R Mvarh High part, in MWh
HR 5400 int32 ABCD R W
HR 5402 int32 ABCD R var
HR 5404 int32 ABCD R W
HR 5406 int32 ABCD R W
HR 5408 int32 ABCD R W
HR 5410 int32 ABCD R var
HR 5412 int32 ABCD R var
HR 5414 int32 ABCD R var

Help improve this map