MBMap Registry
  1. Devices
  2. IME
  3. Nemo D4 LE

IME Nemo D4 LE Modbus register map

Also covers Nemo D4-Le, Nemo D4-L+, MFD4421

Nemo D4-Le DIN rail multifunction meter with RS-485 (Jbus/Modbus)

  • Official
  • 160 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
160 holding registers
Groups
3
Revision
2 · 2026-10-17
Firmware
from 1.00
Added
()
File
maps/ime/nemo-d4-le.mbmap.json · 30 KB · history
SHA-256
b1b276a5e75f59386251c4869575439676d2e78a0d637d435408cceace9721d8
Manufacturer
imeitaly.com

Sources and notes

Source: IME, "Nemo D4-Le Jbus/Modbus communication protocol", PR 129 rev. 1 (2014-05-29)

  • Read with FC03; 32-bit values are most significant word first.
  • Energies at 0x1700 are split into a low part in Wh and a high part in MWh; the signed powers at 0x1720 are always W/var.
  • Not in this map: the legacy energy block at 0x1500 (kept for old Nemo 96HD software) and the setup parameters (0x2000 onwards).
AreaAddressNameTypeAccessUnitScaleDescription
HR 4096 uint32 ABCD R V ×0.001
HR 4098 uint32 ABCD R V ×0.001
HR 4100 uint32 ABCD R V ×0.001
HR 4102 uint32 ABCD R A ×0.001
HR 4104 uint32 ABCD R A ×0.001
HR 4106 uint32 ABCD R A ×0.001
HR 4108 uint32 ABCD R A ×0.001
HR 4110 uint32 ABCD R V ×0.001
HR 4112 uint32 ABCD R V ×0.001
HR 4114 uint32 ABCD R V ×0.001
HR 4116 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4118 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4120 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4122 uint16 R
HR 4123 uint16 R
HR 4124 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4126 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4128 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4130 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4132 int16 R ×0.01
HR 4133 uint16 R
HR 4134 uint16 R Hz ×0.1
HR 4135 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4137 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4139 uint16 R min
HR 4140 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4142 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4144 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4146 uint16 R
HR 4147 uint16 R
HR 4148 uint16 R
HR 4149 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4151 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4153 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4155 uint16 R
HR 4156 uint16 R
HR 4157 uint16 R
HR 4158 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4160 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4162 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4164 int16 R ×0.01
HR 4165 int16 R ×0.01
HR 4166 int16 R ×0.01
HR 4167 uint16 R
HR 4168 uint16 R
HR 4169 uint16 R
HR 4170 uint16 R % ×0.1
HR 4171 uint16 R % ×0.1
HR 4172 uint16 R % ×0.1
HR 4173 uint16 R % ×0.1
HR 4174 uint16 R % ×0.1
HR 4175 uint16 R % ×0.1
HR 4176 uint32 ABCD R A ×0.001
HR 4178 uint32 ABCD R A ×0.001
HR 4180 uint32 ABCD R A ×0.001
HR 4182 uint32 ABCD R A ×0.001
HR 4184 uint32 ABCD R A ×0.001
HR 4186 uint32 ABCD R A ×0.001
HR 4188 uint32 ABCD R A ×0.001
HR 4190 uint32 ABCD R V ×0.001
HR 4192 uint32 ABCD R V ×0.001
HR 4194 uint32 ABCD R V ×0.001
HR 4196 uint32 ABCD R V ×0.001
HR 4198 uint32 ABCD R V ×0.001
HR 4200 uint32 ABCD R V ×0.001
HR 4202 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4204 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4206 uint16 R h
HR 4207 uint16 R
HR 4208 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4210 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4212 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4214 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4216 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4218 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4608 uint16 R
HR 4609 uint16 R ×0.01
HR 4612 uint16 R
HR 4614 uint16 R 0 = both open, 1 = input 1 closed, 2 = input 2 closed, 3 = both closed
HR 4688 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4690 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4692 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4694 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4696 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4698 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4700 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4702 uint32 ABCD R Unit depends on KTA x KTV (protocol note 4): from Wh x 10 to kWh x 100
HR 4864 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4866 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4868 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4870 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4872 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4874 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4876 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4878 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4880 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4882 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4884 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4886 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA
HR 4888 uint32 ABCD R W, var or VA divided by 100 when KTA x KTV < 5000, otherwise W, var or VA

Help improve this map