Inepro Metering PRO2-Mod Modbus register map
Inepro PRO2 single-phase DIN rail energy meter with Modbus RTU over RS-485
- Official
- 47 registers
- Modbus RTU
- Revision 2 · 2026-10-17
- Identity: firmware, serial number
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 47 holding registers
- Groups
- 3
- Revision
- 2 · 2026-10-17
- Added
- ()
- File
- maps/inepro-metering/metering-pro2.mbmap.json · 9 KB · history
- SHA-256
- eaed9724870fcb6e6b9d46a82aeb921da658dd751dc843856866549f42dbc190
- Manufacturer
- ineprometering.com
Device identity
What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.
| Role | Register | Address | Type | Values |
|---|---|---|---|---|
| Serial number | Serial number | holding 16384 | uint32 ABCD | |
| Firmware | Software version | holding 16391 | float32 ABCD |
Sources and notes
- PRO2 Series user manual Appendix A3.2, Modbus register map; linked from the PRO2-Mod product page
Source: Inepro Metering, "PRO2 Series user manual", appendix A3 (Modbus register map)
- All registers are holding registers read with FC03. Settings are written with FC06 (one register) or FC10 (floats).
- Floats are IEEE 754 in ABCD order (high word first).
- Defaults: address 1, 9600 baud, 8 data bits, even parity, 1 stop bit. Baud rate can be lowered to 4800, 2400 or 1200; parity can be none or odd.
- Power is given in kW, kvar and kVA, energy in kWh and kvarh.
- The register map is shared with the PRO380; the registers it marks as PRO380 only (per-phase L2/L3 and CT values) are left out.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 16384 | uint32 ABCD | R | Read as hexadecimal | |||
| HR | 16386 | uint16 | R | Read as hexadecimal | |||
| HR | 16387 | int16 | RW | 0 = broadcast, default 1 | |||
| HR | 16388 | int16 | RW | The value is the baud rate itself | |||
| HR | 16389 | float32 ABCD | R | ||||
| HR | 16391 | float32 ABCD | R | ||||
| HR | 16393 | float32 ABCD | R | ||||
| HR | 16395 | int16 | R | A | |||
| HR | 16397 | float32 ABCD | RW | imp/kWh | 10000, 2000, 1000, 100, 10, 1, 0.1 or 0.01 | ||
| HR | 16399 | int16 | RW | ||||
| HR | 16400 | uint16 | RW | s | Read and written as hexadecimal digits (0x0025 = 25 s) | ||
| HR | 16401 | int16 | RW | ||||
| HR | 16402 | string[1] | R | ||||
| HR | 16405 | int16 | R | ||||
| HR | 16406 | int16 | RW | Write 0 to reset | |||
| HR | 16407 | int16 | R | ||||
| HR | 16411 | uint32 ABCD | R | ||||
| HR | 16413 | uint32 ABCD | R | ||||
| HR | 20480 | float32 ABCD | R | V | |||
| HR | 20482 | float32 ABCD | R | V | |||
| HR | 20488 | float32 ABCD | R | Hz | |||
| HR | 20490 | float32 ABCD | R | A | |||
| HR | 20492 | float32 ABCD | R | A | |||
| HR | 20498 | float32 ABCD | R | kW | |||
| HR | 20506 | float32 ABCD | R | kvar | |||
| HR | 20514 | float32 ABCD | R | kVA | |||
| HR | 20522 | float32 ABCD | R | ||||
| HR | 24576 | float32 ABCD | R | kWh | |||
| HR | 24578 | float32 ABCD | R | kWh | |||
| HR | 24580 | float32 ABCD | R | kWh | |||
| HR | 24588 | float32 ABCD | R | kWh | |||
| HR | 24590 | float32 ABCD | R | kWh | |||
| HR | 24592 | float32 ABCD | R | kWh | |||
| HR | 24600 | float32 ABCD | R | kWh | |||
| HR | 24602 | float32 ABCD | R | kWh | |||
| HR | 24604 | float32 ABCD | R | kWh | |||
| HR | 24612 | float32 ABCD | R | kvarh | |||
| HR | 24614 | float32 ABCD | R | kvarh | |||
| HR | 24616 | float32 ABCD | R | kvarh | |||
| HR | 24624 | float32 ABCD | R | kvarh | |||
| HR | 24626 | float32 ABCD | R | kvarh | |||
| HR | 24628 | float32 ABCD | R | kvarh | |||
| HR | 24636 | float32 ABCD | R | kvarh | |||
| HR | 24638 | float32 ABCD | R | kvarh | |||
| HR | 24640 | float32 ABCD | R | kvarh | |||
| HR | 24648 | int16 | RW | ||||
| HR | 24649 | float32 ABCD | RW | kWh | Write 0 (two registers, FC10) to reset |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.