MBMap Registry
  1. Devices
  2. KEBA
  3. KeContact P30

KEBA KeContact P30 Modbus register map

Also covers KeContact P30 c-series, KeContact P30 x-series

EV charging station, Modbus TCP

  • Official
  • 32 registers
  • Modbus TCP
  • Revision 1 · 2026-11-10
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
255
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
2 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
32 holding registers
Groups
8
Translation tables
6
Revision
1 · 2026-11-10
Added
()
File
maps/keba/kecontact-p30.mbmap.json · 9 KB · history
SHA-256
99743906f2fa989ae3b661eb2ca58dd45a7147cccbd7779600e3e0cab9b210f0
Manufacturer
keba.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 1014 uint32 ABCD

Sources and notes

Source: KEBA, KeContact P30 Modbus TCP Programmers Guide, V 1.07 (en), 12.2025

  • The interface needs a P30 c-series with firmware 3.10.16 or later, or a P30 x-series with software 1.11 or later. DIP switch DSW1.3 on the station must be ON to enable Modbus TCP. The guide says Modbus TCP and the UDP interface must not be used together.
  • The guide says the Unit ID must be 255, that only function codes 3 (read) and 6 (write) are supported, and that registers cannot be read in blocks: each value is read on its own, at most 2 registers (one 32-bit value). Registers are numbered from 0 (address_base 0), although the guide adds that some clients need +1.
  • Every readable value is a 32-bit unsigned integer in two registers. The guide does not state the word order; big (high word first) is assumed. Check against the display or the serial number if a value looks wrong.
  • Write registers hold one 16-bit value, are write-only (the guide marks them wo) and cannot be read back. The guide recommends reading no faster than every 0.5 s and writing no faster than every 5 s.
  • Firmware version (1018) is hex-coded in the decimal value (30A0D00 hex is 3.10.14); it has no firmware role because the raw value is not a version string. The guide notes that Modbus TCP version 1.11 numbers this register 1013.
  • Product type and features (1016) is a decimal number whose digits give the product type, cable or socket, maximum current, series, meter type and RFID; the digit tables are in the guide. Error code (1006) is a decimal number to be read as hex: the leading hex digit is the error group.
  • Written from the manufacturer's document; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1000 uint32 ABCD R
HR 1004 uint32 ABCD R
HR 1006 uint32 ABCD R 0 is no error; otherwise read the decimal value as hex
HR 1008 uint32 ABCD R A ×0.001
HR 1010 uint32 ABCD R A ×0.001
HR 1012 uint32 ABCD R A ×0.001
HR 1014 uint32 ABCD R
HR 1016 uint32 ABCD R Decimal digits for type, cable or socket, current, series, meter and RFID; see the guide
HR 1018 uint32 ABCD R Hex-coded: read the decimal value as hex, one byte per version part
HR 1020 uint32 ABCD R W ×0.001
HR 1036 uint32 ABCD R Wh ×0.1 Lifetime energy of the station
HR 1040 uint32 ABCD R V
HR 1042 uint32 ABCD R V
HR 1044 uint32 ABCD R V
HR 1046 uint32 ABCD R % ×0.1
HR 1100 uint32 ABCD R A ×0.001
HR 1110 uint32 ABCD R A ×0.001 Hardware limit: lowest of DIP switch, cable coding and temperature limit; socket models show 6 A with no cable plugged
HR 1500 uint32 ABCD R First 4 bytes of the card UID, when the session was authorized by RFID
HR 1502 uint32 ABCD R Wh ×0.1 Energy of the current session
HR 1550 uint32 ABCD R
HR 1552 uint32 ABCD R
HR 1600 uint32 ABCD R A ×0.001 Active setting, not necessarily the persisted one
HR 1602 uint32 ABCD R s Active setting, not necessarily the persisted one
HR 5004 uint16 W A ×0.001 Raw value in mA; lasts until the next reboot
HR 5010 uint16 W Wh ×10 Ends the current or next session once this energy is delivered
HR 5012 uint16 W Write 0; only in suspended state
HR 5014 uint16 W Disabling stops an active session
HR 5016 uint16 W A ×0.001 Raw value in mA: 0 stops charging, otherwise 6000 to 32000. Only active once a failsafe timeout is sent
HR 5018 uint16 W s 0 turns failsafe off, otherwise 5 to 600
HR 5020 uint16 W Write 1 to store the failsafe settings
HR 5050 uint16 W Chooses the channel that drives contact x2
HR 5052 uint16 W

Help improve this map