MBMap Registry
  1. Devices
  2. Kohler
  3. Decision-Maker 340

Kohler Decision-Maker 340 Modbus register map

  • Official
  • 50 registers
  • Revision 3 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
50 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
50 holding registers
Revision
3 · 2026-11-10
Added
()
File
maps/kohler/decision-maker-340.mbmap.json · 7 KB · history
SHA-256
4d09b442b146ed085059bd4f08da46bbe68de5199883923686960effa8942b93
Manufacturer
rehlko.com

Sources and notes

Source: Kohler, "Protocol Operation: Modbus Communications Protocol", TP-6113 12/21; https://techcomm.kohler.com/techcomm/pdf/tp6113.pdf

  • Decision-Maker 340 generator set controller (through the Modbus/KBUS converter).
  • Baud rate must be 9600 to match the KBUS side of the converter.
  • Addresses are zero-based: the manual register 40001 is address 0.
  • The manual limits a read to 50 registers. Only the monitoring part of the register table is in this map.
  • Data is available over Modbus RTU (8N1); Modbus TCP needs a Modbus/Ethernet converter.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint16 R
HR 2 uint16 R
HR 3 uint16 R
HR 4 uint16 R
HR 5 uint16 R
HR 6 uint16 R
HR 7 uint16 R V
HR 8 uint16 R V
HR 9 uint16 R V
HR 10 uint16 R Hz
HR 11 uint16 R V
HR 12 uint16 R V
HR 13 uint16 R V
HR 14 uint16 R
HR 15 uint16 R
HR 16 uint16 R
HR 17 uint16 R
HR 18 uint16 R V ×0.1
HR 19 uint16 R A
HR 20 uint16 R A
HR 21 uint16 R A
HR 22 uint16 R ×0.01
HR 23 uint16 R kW
HR 24 uint16 R % ×0.01
HR 33 uint16 R
HR 47 uint16 R s
HR 48 uint16 R s
HR 49 uint16 R s
HR 50 uint16 R
HR 51 uint16 R s
HR 52 uint16 R s
HR 53 uint16 R s
HR 54 uint16 R s
HR 55 uint16 R s
HR 56 uint16 R s
HR 57 uint16 R s
HR 58 uint16 R s
HR 59 uint16 R s
HR 60 uint16 R s
HR 61 uint16 R s
HR 62 uint16 R s
HR 63 uint16 R %
HR 64 uint16 R %
HR 65 uint16 R %
HR 66 uint16 R %
HR 67 uint16 R %
HR 68 uint16 R V ×0.1
HR 69 uint16 R V ×0.1
HR 70 uint16 R V
HR 71 uint16 R Hz

Help improve this map