MBMap Registry
  1. Devices
  2. Kohler
  3. MPAC 1000

Kohler MPAC 1000 Modbus register map

  • Official
  • 51 registers
  • Revision 3 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
50 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
51 holding registers
Revision
3 · 2026-11-10
Added
()
File
maps/kohler/mpac-1000.mbmap.json · 8 KB · history
SHA-256
62a949ee0989711a400d684f8b71a6eafb16e88d08376a958a15f52d33cabf23
Manufacturer
rehlko.com

Sources and notes

Source: Kohler, "Protocol Operation: Modbus Communications Protocol", TP-6113 12/21; https://techcomm.kohler.com/techcomm/pdf/tp6113.pdf

  • MPAC 1000 automatic transfer switch controller.
  • Addresses are zero-based: the manual register 40001 is address 0.
  • The manual limits a read to 50 registers. Only the monitoring part of the register table is in this map.
  • Data is available over Modbus RTU (8N1); Modbus TCP needs a Modbus/Ethernet converter.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint16 R V ×0.1
HR 2 uint16 R V ×0.1
HR 3 uint16 R V ×0.1
HR 4 uint16 R V ×0.1
HR 5 uint16 R V ×0.1
HR 6 uint16 R V ×0.1
HR 7 uint16 R V ×0.1
HR 8 uint16 R V ×0.1
HR 9 uint16 R V ×0.1
HR 10 uint16 R V ×0.1
HR 11 uint16 R V ×0.1
HR 12 uint16 R V ×0.1
HR 13 uint16 R Hz ×0.1
HR 14 uint16 R Hz ×0.1
HR 23 uint16 RW V ×0.1
HR 24 uint16 RW V ×0.1
HR 25 uint16 RW Hz ×0.1
HR 26 uint16 RW Hz ×0.1
HR 27 uint16 RW
HR 28 uint16 RW
HR 29 uint16 RW
HR 31 uint16 RW s
HR 32 uint16 RW s
HR 33 uint16 RW s
HR 34 uint16 RW s
HR 35 uint16 RW s
HR 36 uint16 RW s
HR 37 uint16 RW s
HR 38 uint16 RW s
HR 39 uint16 RW s ×0.1
HR 40 uint16 RW s ×0.1
HR 41 uint16 RW s
HR 42 uint16 RW s
HR 44 uint16 RW %
HR 45 uint16 RW %
HR 46 uint16 RW %
HR 47 uint16 RW %
HR 48 uint16 RW s ×0.1
HR 49 uint16 RW %
HR 50 uint16 RW %
HR 51 uint16 RW %
HR 52 uint16 RW %
HR 53 uint16 RW s ×0.1
HR 54 uint16 RW %
HR 55 uint16 RW %
HR 56 uint16 RW %
HR 57 uint16 RW %
HR 58 uint16 RW s ×0.1
HR 59 uint16 RW %
HR 60 uint16 RW %
HR 49998 uint16 R Fixed controller type code

Help improve this map