Korenix JetI/O 6520 Modbus register map
4-CH analog output Ethernet I/O server, Modbus/TCP. Output range set globally at addr 9 (0=0~+10V, 1=-10V~+10V, 2=0~20mA). Output values at addr 22-25 (s16; 0-10000=0-10V, ±10000=±10V, 0-20000=0-20mA). Slew rate at addr 8 (4-bit code per channel). Power-on values at addr 10-13. Calibration offset/span at addr 14-21.
- Unofficial
- 28 registers
- Revision 2
Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus TCP and RTUdefault
- Unit ID
- 1default
- TCP port
- 502default
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 28 holding registers
- Revision
- 2
- Added
- ()
- File
- maps/korenix/jeti-o-6520.mbmap.json · 5 KB · history
- SHA-256
- 351c913167cafbf4b663531321df865116ae47963d027f9311de5bd036aa4c6d
- Manufacturer
- beijerelectronics.com
Sources and notes
Source: Omni Console device library (OmniCoreST), modbus-library/korenix-jetio-6520.toml; Source: JetI/O 6520 User's Manual V0.1 (Jan. 2008). Not verified against the manufacturer's documentation
- Korenix JetI/O 6520.
- Converted automatically from the Omni Console device library (OmniCoreST).
- Not verified against the manufacturer's documentation.
- Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
- | Korenix JetI/O 6520 Industrial Intelligent Ethernet I/O Server
- |
- | Source: JetI/O 6520 User's Manual V0.1 (Jan. 2008)
- | Protocol: Modbus/TCP (Ethernet port 502); FC03 read holding, FC06 write single
- | Module: 4-channel analog output, 16-bit
- | Output ranges (set globally at addr 9):
- | 0 = 0~+10V (0~10000 = 0~10V)
- | 1 = -10V~+10V (-10000~10000 = -10V~+10V)
- | 2 = 0~20mA (0~20000 = 0~20mA)
- | Slew rate (addr 8): 4-bit code per channel packed into one register (ABCD = ch3,ch2,ch1,ch0).
- | Power-on DA values (addr 10-13): stored output value applied on power-up.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 0 | uint16 | R | ||||
| HR | 1 | uint16 | R | ||||
| HR | 2 | uint16 | R | ||||
| HR | 3 | uint16 | R | ||||
| HR | 4 | uint16 | R | ||||
| HR | 5 | uint16 | R | ||||
| HR | 6 | uint16 | R | ||||
| HR | 7 | uint16 | R | ||||
| HR | 8 | uint16 | R | ||||
| HR | 9 | uint16 | R | ||||
| HR | 10 | uint16 | R | ||||
| HR | 11 | uint16 | R | ||||
| HR | 12 | uint16 | R | ||||
| HR | 13 | uint16 | R | ||||
| HR | 14 | uint16 | R | ||||
| HR | 15 | uint16 | R | ||||
| HR | 16 | uint16 | R | ||||
| HR | 17 | uint16 | R | ||||
| HR | 18 | uint16 | R | ||||
| HR | 19 | uint16 | R | ||||
| HR | 20 | uint16 | R | ||||
| HR | 21 | uint16 | R | ||||
| HR | 22 | int16 | R | ||||
| HR | 23 | int16 | R | ||||
| HR | 24 | int16 | R | ||||
| HR | 25 | int16 | R | ||||
| HR | 26 | uint16 | R | ||||
| HR | 27 | uint16 | R |