Korenix JetI/O 6520 Modbus register map

4-CH analog output Ethernet I/O server, Modbus/TCP. Output range set globally at addr 9 (0=0~+10V, 1=-10V~+10V, 2=0~20mA). Output values at addr 22-25 (s16; 0-10000=0-10V, ±10000=±10V, 0-20000=0-20mA). Slew rate at addr 8 (4-bit code per channel). Power-on values at addr 10-13. Calibration offset/span at addr 14-21.

  • Unofficial
  • 28 registers
  • Revision 2

Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
28 holding registers
Revision
2
Added
()
File
maps/korenix/jeti-o-6520.mbmap.json · 5 KB · history
SHA-256
351c913167cafbf4b663531321df865116ae47963d027f9311de5bd036aa4c6d
Manufacturer
beijerelectronics.com

Sources and notes

Source: Omni Console device library (OmniCoreST), modbus-library/korenix-jetio-6520.toml; Source: JetI/O 6520 User's Manual V0.1 (Jan. 2008). Not verified against the manufacturer's documentation

  • Korenix JetI/O 6520.
  • Converted automatically from the Omni Console device library (OmniCoreST).
  • Not verified against the manufacturer's documentation.
  • Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
  • | Korenix JetI/O 6520 Industrial Intelligent Ethernet I/O Server
  • |
  • | Source: JetI/O 6520 User's Manual V0.1 (Jan. 2008)
  • | Protocol: Modbus/TCP (Ethernet port 502); FC03 read holding, FC06 write single
  • | Module: 4-channel analog output, 16-bit
  • | Output ranges (set globally at addr 9):
  • | 0 = 0~+10V (0~10000 = 0~10V)
  • | 1 = -10V~+10V (-10000~10000 = -10V~+10V)
  • | 2 = 0~20mA (0~20000 = 0~20mA)
  • | Slew rate (addr 8): 4-bit code per channel packed into one register (ABCD = ch3,ch2,ch1,ch0).
  • | Power-on DA values (addr 10-13): stored output value applied on power-up.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 R
HR 1 uint16 R
HR 2 uint16 R
HR 3 uint16 R
HR 4 uint16 R
HR 5 uint16 R
HR 6 uint16 R
HR 7 uint16 R
HR 8 uint16 R
HR 9 uint16 R
HR 10 uint16 R
HR 11 uint16 R
HR 12 uint16 R
HR 13 uint16 R
HR 14 uint16 R
HR 15 uint16 R
HR 16 uint16 R
HR 17 uint16 R
HR 18 uint16 R
HR 19 uint16 R
HR 20 uint16 R
HR 21 uint16 R
HR 22 int16 R
HR 23 int16 R
HR 24 int16 R
HR 25 int16 R
HR 26 uint16 R
HR 27 uint16 R