MBMap Registry
  1. Devices
  2. KRON
  3. Konect

KRON Konect Modbus register map

Three-phase energy meter with RS-485, Ethernet, Wi-Fi and Bluetooth: voltages, currents, frequency, power, power factor, energy, demand, THD, minimums and maximums, mass memory settings and commands

  • Official
  • 262 registers
  • Modbus TCP and RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
255
TCP port
502
Serial
9600 8N2 · 9600 baud, 8 data bits, none parity, 2 stop bits
Byte / word order
DCBA · bytes little-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1
Max read
8 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
47 holding registers, 190 input registers, 20 coils, 5 discrete inputs
Groups
20
Translation tables
3
Revision
1 · 2026-11-10
Added
()
File
maps/kron/konect.mbmap.json · 49 KB · history
SHA-256
de1295fc81420c70a2b4f0455bfcdf2f79116f644ed93a6685768933da839e53
Manufacturer
kron.com.br

Sources and notes

Source: KRON, "Protocolo MODBUS – Konect", rev. 2.1 (May 2022)

  • Modbus RTU on RS-485 and Modbus TCP (port 502, up to 2 sockets). Addresses are numbered from 1 as in the document (30.015 is input register 15, sent as 14). Commands are coils: command 006 is coil 6, sent as 5.
  • Float values use the KRON sequence F2, F1, F0, EXP, which is the bytes fully reversed (the document's example sends 60 Hz as 00 00 70 42): little byte order and little word order. That is the default of holding register 42901; changing it breaks the float registers. Integers described as MSB first override this with big byte order.
  • The document gives 254 as the factory Modbus RTU address and 255 as the Modbus TCP slave id; 255 is used here. After a factory restore (coil 090) the serial format is 8N2 at 9600 bit/s, which is what the connection defaults show. Baud rates 9600, 19200, 38400 and 57600; formats 8N1, 8N2, 8E1 and 8O1. At most 8 holding registers per request.
  • Registers marked firmware 6.7 or later exist only from that version; the document does not say how older units answer. Holding register 40007 and most network settings take effect only after the device restarts (coil 006).
  • The THD values have no scale or unit in the document and are given raw. The harmonic grouping tables (34.001 to 34.480), the real-time clock registers 42.001 to 42.004 (packed BCD), the MAC addresses (6 raw bytes at 39.501 to 39.509), the IP, mask, gateway and DNS addresses, the MQTT broker, user, token and topic strings, the Wi-Fi and Bluetooth passwords, the LoRa keys and settings, the solar module registers (special version) and the mass memory read-out are not mapped.
  • Written from the protocol document; this map has not been tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
IR 1 uint32 ABCD R
IR 3 float32 DCBA R V
IR 5 float32 DCBA R V
IR 7 float32 DCBA R V
IR 9 float32 DCBA R V
IR 11 float32 DCBA R V In delta systems this holds the line-to-line voltage
IR 13 float32 DCBA R V In delta systems this holds the line-to-line voltage
IR 15 float32 DCBA R V In delta systems this holds the line-to-line voltage
IR 17 float32 DCBA R A
IR 19 float32 DCBA R A
IR 21 float32 DCBA R A
IR 23 float32 DCBA R A
IR 25 float32 DCBA R A
IR 27 float32 DCBA R Hz
IR 29 float32 DCBA R Hz
IR 31 float32 DCBA R Hz
IR 33 float32 DCBA R Hz
IR 35 float32 DCBA R W
IR 37 float32 DCBA R W
IR 39 float32 DCBA R W
IR 41 float32 DCBA R W
IR 43 float32 DCBA R var
IR 45 float32 DCBA R var
IR 47 float32 DCBA R var
IR 49 float32 DCBA R var
IR 51 float32 DCBA R VA
IR 53 float32 DCBA R VA
IR 55 float32 DCBA R VA
IR 57 float32 DCBA R VA
IR 59 float32 DCBA R
IR 61 float32 DCBA R
IR 63 float32 DCBA R
IR 65 float32 DCBA R
IR 67 float32 DCBA R
IR 69 float32 DCBA R
IR 71 float32 DCBA R
IR 73 float32 DCBA R
IR 75 float32 DCBA R Voltage unbalance factor (factor D in the document); no unit given
IR 77 float32 DCBA R
IR 79 float32 DCBA R
IR 81 float32 DCBA R
IR 95 float32 DCBA R Pulse count, 0 to 9999999 then back to 0
IR 97 float32 DCBA R Pulse count, 0 to 9999999 then back to 0
IR 99 float32 DCBA R Pulse count, 0 to 9999999 then back to 0
IR 111 uint16 BA R Firmware 6.7 or later
IR 112 uint16 BA R Firmware 6.7 or later
IR 113 uint16 BA R Firmware 6.7 or later
IR 114 uint16 BA R Firmware 6.7 or later
IR 115 uint16 BA R Firmware 6.7 or later
IR 131 uint16 BA R s ×0.1 Interval between two rising edges, in units of 100 ms (0 to 999, 999 meaning 99.9 s or more); firmware 6.7 or later
IR 132 uint16 BA R s ×0.1 Interval between two rising edges, in units of 100 ms (0 to 999, 999 meaning 99.9 s or more); firmware 6.7 or later
IR 133 uint16 BA R s ×0.1 Interval between two rising edges, in units of 100 ms (0 to 999, 999 meaning 99.9 s or more); firmware 6.7 or later
IR 151 uint16 BA R 0 off, 1 on; tied to the hour meter trigger, firmware 6.7 or later
IR 161 float32 DCBA R h Hours with the hundredths as a fraction of an hour (45.50 is 45 h 30 min); firmware 6.7 or later
IR 201 float32 DCBA R kWh
IR 203 float32 DCBA R kvarh
IR 205 float32 DCBA R kWh
IR 207 float32 DCBA R kvarh
IR 209 float32 DCBA R kW
IR 211 float32 DCBA R kW
IR 213 float32 DCBA R kVA
IR 215 float32 DCBA R kVA
IR 1005 float32 DCBA R V
IR 1007 float32 DCBA R V
IR 1009 float32 DCBA R V
IR 1011 float32 DCBA R V
IR 1013 float32 DCBA R V
IR 1015 float32 DCBA R V
IR 1017 float32 DCBA R A
IR 1019 float32 DCBA R A
IR 1021 float32 DCBA R A
IR 1023 float32 DCBA R A
IR 1025 float32 DCBA R A
IR 1027 float32 DCBA R Hz
IR 1029 float32 DCBA R Hz
IR 1031 float32 DCBA R Hz
IR 1033 float32 DCBA R Hz
IR 1035 float32 DCBA R W
IR 1037 float32 DCBA R W
IR 1039 float32 DCBA R W
IR 1041 float32 DCBA R W
IR 1043 float32 DCBA R var
IR 1045 float32 DCBA R var
IR 1047 float32 DCBA R var
IR 1049 float32 DCBA R var
IR 1051 float32 DCBA R VA
IR 1053 float32 DCBA R VA
IR 1055 float32 DCBA R VA
IR 1057 float32 DCBA R VA
IR 1059 float32 DCBA R
IR 1061 float32 DCBA R
IR 1063 float32 DCBA R
IR 1065 float32 DCBA R
IR 1067 float32 DCBA R
IR 1069 float32 DCBA R
IR 1071 float32 DCBA R
IR 1073 float32 DCBA R
IR 1075 float32 DCBA R
IR 1077 float32 DCBA R
IR 1079 float32 DCBA R

Help improve this map