Three-phase multimeter: voltages, currents, frequency, power, power factor, energy, demand, minimums and maximums, settings and reset commands

  • Official
  • 126 registers
  • Modbus RTU
  • Revision 1 · 2026-11-08
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
DCBA · bytes little-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1
Max read
8 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
10 holding registers, 104 input registers, 12 coils
Groups
13
Translation tables
6
Revision
1 · 2026-11-08
Added
()
File
maps/kron/mult-k-serie-2.mbmap.json · 20 KB · history
SHA-256
31c79be8a53e9b2ac9c79e435ce2e375d215a57234b165a7f62222cae5cee4ae
Manufacturer
kron.com.br

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number input 1 uint32 ABCD

Sources and notes

Source: KRON Protocolo MODBUS - Mult-K Série 2, rev. 1.0 (June 2016)

  • Modbus RTU on RS-485. Addresses are numbered from 1 as in the document (30.003 is input register 3, sent as 2). Commands are coils: command 006 is coil 6, sent as 5.
  • Float values are sent with the bytes fully reversed (the document's example sends 60 Hz as 00 00 70 42), which is little byte order and little word order. That is the factory setting of holding register 2901; changing it breaks this map.
  • Holding registers can be read or written at most 8 at a time; input registers up to 66 at a time.
  • The baud rate (9600 to 57600 bit/s) and the format (8N1, 8N2, 8E1, 8O1) are set on the display or in holding register 7. The document gives no factory default; 9600 8N1 is assumed here.
  • The THD registers (33.001 to 33.006) are left out: the document gives no scale or unit for them.
  • Written from the protocol document; this map has not been tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
IR 3 float32 DCBA R V
IR 5 float32 DCBA R V
IR 7 float32 DCBA R V
IR 9 float32 DCBA R V
IR 11 float32 DCBA R V
IR 13 float32 DCBA R V
IR 15 float32 DCBA R V
IR 17 float32 DCBA R A
IR 19 float32 DCBA R A
IR 21 float32 DCBA R A
IR 23 float32 DCBA R A
IR 25 float32 DCBA R A
IR 27 float32 DCBA R Hz
IR 29 float32 DCBA R Hz
IR 31 float32 DCBA R Hz
IR 35 float32 DCBA R W
IR 37 float32 DCBA R W
IR 39 float32 DCBA R W
IR 41 float32 DCBA R W
IR 43 float32 DCBA R var
IR 45 float32 DCBA R var
IR 47 float32 DCBA R var
IR 49 float32 DCBA R var
IR 51 float32 DCBA R VA
IR 53 float32 DCBA R VA
IR 55 float32 DCBA R VA
IR 57 float32 DCBA R VA
IR 59 float32 DCBA R
IR 61 float32 DCBA R
IR 63 float32 DCBA R
IR 65 float32 DCBA R
IR 1003 float32 DCBA R V
IR 2003 float32 DCBA R V
IR 1005 float32 DCBA R V
IR 2005 float32 DCBA R V
IR 1007 float32 DCBA R V
IR 2007 float32 DCBA R V
IR 1009 float32 DCBA R V
IR 2009 float32 DCBA R V
IR 1011 float32 DCBA R V
IR 2011 float32 DCBA R V
IR 1013 float32 DCBA R V
IR 2013 float32 DCBA R V
IR 1015 float32 DCBA R V
IR 2015 float32 DCBA R V
IR 1017 float32 DCBA R A
IR 2017 float32 DCBA R A
IR 1019 float32 DCBA R A
IR 2019 float32 DCBA R A
IR 1021 float32 DCBA R A
IR 2021 float32 DCBA R A
IR 1023 float32 DCBA R A
IR 2023 float32 DCBA R A
IR 1025 float32 DCBA R A
IR 2025 float32 DCBA R A
IR 1027 float32 DCBA R Hz
IR 2027 float32 DCBA R Hz
IR 1029 float32 DCBA R Hz
IR 2029 float32 DCBA R Hz
IR 1031 float32 DCBA R Hz
IR 2031 float32 DCBA R Hz
IR 1035 float32 DCBA R W
IR 2035 float32 DCBA R W
IR 1037 float32 DCBA R W
IR 2037 float32 DCBA R W
IR 1039 float32 DCBA R W
IR 2039 float32 DCBA R W
IR 1041 float32 DCBA R W
IR 2041 float32 DCBA R W
IR 1043 float32 DCBA R var
IR 2043 float32 DCBA R var
IR 1045 float32 DCBA R var
IR 2045 float32 DCBA R var
IR 1047 float32 DCBA R var
IR 2047 float32 DCBA R var
IR 1049 float32 DCBA R var
IR 2049 float32 DCBA R var
IR 1051 float32 DCBA R VA
IR 2051 float32 DCBA R VA
IR 1053 float32 DCBA R VA
IR 2053 float32 DCBA R VA
IR 1055 float32 DCBA R VA
IR 2055 float32 DCBA R VA
IR 1057 float32 DCBA R VA
IR 2057 float32 DCBA R VA
IR 1059 float32 DCBA R
IR 2059 float32 DCBA R
IR 1061 float32 DCBA R
IR 2061 float32 DCBA R
IR 1063 float32 DCBA R
IR 2063 float32 DCBA R
IR 1065 float32 DCBA R
IR 2065 float32 DCBA R
IR 201 float32 DCBA R kWh
IR 203 float32 DCBA R kvarh
IR 205 float32 DCBA R kWh
IR 207 float32 DCBA R kvarh
IR 209 float32 DCBA R kW
IR 211 float32 DCBA R kW
IR 213 float32 DCBA R kVA

Help improve this map