MBMap Registry
  1. Devices
  2. Landis+Gyr
  3. E650 with RS485 DLMS-Modbus gateway, meter 1

Landis+Gyr E650 with RS485 DLMS-Modbus gateway, meter 1 Modbus register map

Also covers MarCom RS485 DLMS-Modbus gateway

E650 energy meter number 1 behind a MarCom RS485 DLMS to Modbus gateway

  • Official
  • 114 registers
  • Modbus TCP and RTU
  • Revision 3 · 2026-11-11

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
114 holding registers
Groups
3
Revision
3 · 2026-11-11
Added
()
File
maps/landis-gyr/e650-gateway-meter-1.mbmap.json · 25 KB · history
SHA-256
0a73e66f15f22230d3abcfe34fc76a464ea827ce4ff4f51a91f3120d787c71ae
Manufacturer
landisgyr.com

Sources and notes

  • Landis & Gyr E650 with RS485 DLMS-MODBUS Gateway (MarCom) · version 3.107 EN
    Modbus mapping area; up to four meters on one gateway, one map per meter

Source: MarCom, Landis & Gyr E650 with RS485 DLMS-Modbus Gateway, rev. 3.107 EN

  • The Modbus data comes from a DLMS to Modbus gateway made by MarCom that reads the E650 meters over RS485; the meter itself does not speak Modbus. Up to four meters connect to one gateway; this map is for meter 1 (meter 1 starts at 40016, meter 2 at 40216, meter 3 at 40416, meter 4 at 40616). The gateway-wide registers 40000 to 40014 are the same in all four maps.
  • The manual writes the addresses as 4x40000 to 4x40798 (holding registers); they are used here as they are with address_base 0. If reads come out one register off, the gateway counts from 1 and address_base should be 1.
  • Each value takes 2 registers (FLOAT, DINT or UDINT). The word order is not stated; big is assumed. A value the meter does not answer reads -1.
  • The meter's serial number must be written to the gateway (registers 40004, 40006, 40008, 40010 for meters 1 to 4, or on its web page) before the first reading. The gateway's default address is 192.168.0.122; Modbus RTU on its RS232 ports and Modbus TCP on its Ethernet port.
  • Energy and power registers carry the DLMS OBIS code in their description (for example 1.8.0 is total active energy A+, 1.6.1 maximum power in time slot 1). The 'previous month' values are the OBIS codes with an asterisk. Units are not given by the manual.
AreaAddressNameTypeAccessUnitScaleDescription
HR 40000 uint16 R
HR 40001 uint16 R
HR 40002 uint16 R
HR 40003 uint16 R
HR 40004 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40006 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40008 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40010 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40012 float32 ABCD R
HR 40014 float32 ABCD R
HR 40016 int32 ABCD R OBIS 0.9.1
HR 40018 int32 ABCD R OBIS 0.9.2
HR 40020 int32 ABCD R OBIS 0.0.0
HR 40022 float32 ABCD R OBIS 0.1.0
HR 40024 float32 ABCD R OBIS 1.8.0
HR 40026 float32 ABCD R OBIS 1.8.0*
HR 40028 float32 ABCD R OBIS 1.8.1
HR 40030 float32 ABCD R OBIS 1.8.1*
HR 40032 float32 ABCD R OBIS 1.8.2
HR 40034 float32 ABCD R OBIS 1.8.2*
HR 40036 float32 ABCD R OBIS 1.8.3
HR 40038 float32 ABCD R OBIS 1.8.3*
HR 40040 float32 ABCD R OBIS 1.8.4
HR 40042 float32 ABCD R OBIS 1.8.4*
HR 40044 float32 ABCD R OBIS 2.8.0
HR 40046 float32 ABCD R OBIS 2.8.0*
HR 40048 float32 ABCD R OBIS 2.8.1
HR 40050 float32 ABCD R OBIS 2.8.1*
HR 40052 float32 ABCD R OBIS 2.8.2
HR 40054 float32 ABCD R OBIS 2.8.2*
HR 40056 float32 ABCD R OBIS 2.8.3
HR 40058 float32 ABCD R OBIS 2.8.3*
HR 40060 float32 ABCD R OBIS 2.8.4
HR 40062 float32 ABCD R OBIS 2.8.4*
HR 40064 float32 ABCD R OBIS 5.8.0
HR 40066 float32 ABCD R OBIS 5.8.0*
HR 40068 float32 ABCD R OBIS 5.8.1
HR 40070 float32 ABCD R OBIS 5.8.1*
HR 40072 float32 ABCD R OBIS 5.8.2
HR 40074 float32 ABCD R OBIS 5.8.2*
HR 40076 float32 ABCD R OBIS 5.8.3
HR 40078 float32 ABCD R OBIS 5.8.3*
HR 40080 float32 ABCD R OBIS 5.8.4
HR 40082 float32 ABCD R OBIS 5.8.4*
HR 40084 float32 ABCD R OBIS 6.8.0
HR 40086 float32 ABCD R OBIS 6.8.0*
HR 40088 float32 ABCD R OBIS 6.8.1
HR 40090 float32 ABCD R OBIS 6.8.1*
HR 40092 float32 ABCD R OBIS 6.8.2
HR 40094 float32 ABCD R OBIS 6.8.2*
HR 40096 float32 ABCD R OBIS 6.8.3
HR 40098 float32 ABCD R OBIS 6.8.3*
HR 40100 float32 ABCD R OBIS 6.8.4
HR 40102 float32 ABCD R OBIS 6.8.4*
HR 40104 float32 ABCD R OBIS 7.8.0
HR 40106 float32 ABCD R OBIS 7.8.0*
HR 40108 float32 ABCD R OBIS 7.8.1
HR 40110 float32 ABCD R OBIS 7.8.1*
HR 40112 float32 ABCD R OBIS 7.8.2
HR 40114 float32 ABCD R OBIS 7.8.2*
HR 40116 float32 ABCD R OBIS 7.8.3
HR 40118 float32 ABCD R OBIS 7.8.3*
HR 40120 float32 ABCD R OBIS 7.8.4
HR 40122 float32 ABCD R OBIS 7.8.4*
HR 40124 float32 ABCD R OBIS 8.8.0
HR 40126 float32 ABCD R OBIS 8.8.0*
HR 40128 float32 ABCD R OBIS 8.8.1
HR 40130 float32 ABCD R OBIS 8.8.1*
HR 40132 float32 ABCD R OBIS 8.8.2
HR 40134 float32 ABCD R OBIS 8.8.2*
HR 40136 float32 ABCD R OBIS 8.8.3
HR 40138 float32 ABCD R OBIS 8.8.3*
HR 40140 float32 ABCD R OBIS 8.8.4
HR 40142 float32 ABCD R OBIS 8.8.4*
HR 40144 float32 ABCD R OBIS 1.6.1
HR 40146 float32 ABCD R OBIS 1.6.1*
HR 40148 float32 ABCD R OBIS 1.6.2
HR 40150 float32 ABCD R OBIS 1.6.2*
HR 40152 float32 ABCD R OBIS 1.6.3
HR 40154 float32 ABCD R OBIS 1.6.3*
HR 40156 float32 ABCD R OBIS 1.6.4
HR 40158 float32 ABCD R OBIS 1.6.4*
HR 40160 float32 ABCD R OBIS 2.6.1
HR 40162 float32 ABCD R OBIS 2.6.1*
HR 40164 float32 ABCD R OBIS 2.6.2
HR 40166 float32 ABCD R OBIS 2.6.2*
HR 40168 float32 ABCD R OBIS 2.6.3
HR 40170 float32 ABCD R OBIS 2.6.3*
HR 40172 float32 ABCD R OBIS 2.6.4
HR 40174 float32 ABCD R OBIS 2.6.4*
HR 40176 float32 ABCD R OBIS C.4.0
HR 40178 float32 ABCD R OBIS C.5.0
HR 40180 float32 ABCD R OBIS 32.7.0
HR 40182 float32 ABCD R OBIS 52.7.0
HR 40184 float32 ABCD R OBIS 72.7.0
HR 40186 float32 ABCD R OBIS C.7.1
HR 40188 float32 ABCD R OBIS C.7.2
HR 40190 float32 ABCD R OBIS C.7.3
HR 40192 float32 ABCD R OBIS C.7.0
HR 40194 float32 ABCD R OBIS 32.7.1

Help improve this map