MBMap Registry
  1. Devices
  2. Landis+Gyr
  3. E650 with RS485 DLMS-Modbus gateway, meter 3

Landis+Gyr E650 with RS485 DLMS-Modbus gateway, meter 3 Modbus register map

Also covers MarCom RS485 DLMS-Modbus gateway

E650 energy meter number 3 behind a MarCom RS485 DLMS to Modbus gateway

  • Official
  • 114 registers
  • Modbus TCP and RTU
  • Revision 3 · 2026-11-11

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
114 holding registers
Groups
3
Revision
3 · 2026-11-11
Added
()
File
maps/landis-gyr/e650-gateway-meter-3.mbmap.json · 25 KB · history
SHA-256
3d2c512f63fab77fbb462d4da208836f09c176f9e1c9f065a683f80865ba8363
Manufacturer
landisgyr.com

Sources and notes

  • Landis & Gyr E650 with RS485 DLMS-MODBUS Gateway (MarCom) · version 3.107 EN
    Modbus mapping area; up to four meters on one gateway, one map per meter

Source: MarCom, Landis & Gyr E650 with RS485 DLMS-Modbus Gateway, rev. 3.107 EN

  • The Modbus data comes from a DLMS to Modbus gateway made by MarCom that reads the E650 meters over RS485; the meter itself does not speak Modbus. Up to four meters connect to one gateway; this map is for meter 3 (meter 1 starts at 40016, meter 2 at 40216, meter 3 at 40416, meter 4 at 40616). The gateway-wide registers 40000 to 40014 are the same in all four maps.
  • The manual writes the addresses as 4x40000 to 4x40798 (holding registers); they are used here as they are with address_base 0. If reads come out one register off, the gateway counts from 1 and address_base should be 1.
  • Each value takes 2 registers (FLOAT, DINT or UDINT). The word order is not stated; big is assumed. A value the meter does not answer reads -1.
  • The meter's serial number must be written to the gateway (registers 40004, 40006, 40008, 40010 for meters 1 to 4, or on its web page) before the first reading. The gateway's default address is 192.168.0.122; Modbus RTU on its RS232 ports and Modbus TCP on its Ethernet port.
  • Energy and power registers carry the DLMS OBIS code in their description (for example 1.8.0 is total active energy A+, 1.6.1 maximum power in time slot 1). The 'previous month' values are the OBIS codes with an asterisk. Units are not given by the manual.
AreaAddressNameTypeAccessUnitScaleDescription
HR 40000 uint16 R
HR 40001 uint16 R
HR 40002 uint16 R
HR 40003 uint16 R
HR 40004 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40006 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40008 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40010 uint32 ABCD RW Serial number of the meter, written to the gateway to enable DLMS reading
HR 40012 float32 ABCD R
HR 40014 float32 ABCD R
HR 40416 int32 ABCD R OBIS 0.9.1
HR 40418 int32 ABCD R OBIS 0.9.2
HR 40420 int32 ABCD R OBIS 0.0.0
HR 40422 float32 ABCD R OBIS 0.1.0
HR 40424 float32 ABCD R OBIS 1.8.0
HR 40426 float32 ABCD R OBIS 1.8.0*
HR 40428 float32 ABCD R OBIS 1.8.1
HR 40430 float32 ABCD R OBIS 1.8.1*
HR 40432 float32 ABCD R OBIS 1.8.2
HR 40434 float32 ABCD R OBIS 1.8.2*
HR 40436 float32 ABCD R OBIS 1.8.3
HR 40438 float32 ABCD R OBIS 1.8.3*
HR 40440 float32 ABCD R OBIS 1.8.4
HR 40442 float32 ABCD R OBIS 1.8.4*
HR 40444 float32 ABCD R OBIS 2.8.0
HR 40446 float32 ABCD R OBIS 2.8.0*
HR 40448 float32 ABCD R OBIS 2.8.1
HR 40450 float32 ABCD R OBIS 2.8.1*
HR 40452 float32 ABCD R OBIS 2.8.2
HR 40454 float32 ABCD R OBIS 2.8.2*
HR 40456 float32 ABCD R OBIS 2.8.3
HR 40458 float32 ABCD R OBIS 2.8.3*
HR 40460 float32 ABCD R OBIS 2.8.4
HR 40462 float32 ABCD R OBIS 2.8.4*
HR 40464 float32 ABCD R OBIS 5.8.0
HR 40466 float32 ABCD R OBIS 5.8.0*
HR 40468 float32 ABCD R OBIS 5.8.1
HR 40470 float32 ABCD R OBIS 5.8.1*
HR 40472 float32 ABCD R OBIS 5.8.2
HR 40474 float32 ABCD R OBIS 5.8.2*
HR 40476 float32 ABCD R OBIS 5.8.3
HR 40478 float32 ABCD R OBIS 5.8.3*
HR 40480 float32 ABCD R OBIS 5.8.4
HR 40482 float32 ABCD R OBIS 5.8.4*
HR 40484 float32 ABCD R OBIS 6.8.0
HR 40486 float32 ABCD R OBIS 6.8.0*
HR 40488 float32 ABCD R OBIS 6.8.1
HR 40490 float32 ABCD R OBIS 6.8.1*
HR 40492 float32 ABCD R OBIS 6.8.2
HR 40494 float32 ABCD R OBIS 6.8.2*
HR 40496 float32 ABCD R OBIS 6.8.3
HR 40498 float32 ABCD R OBIS 6.8.3*
HR 40500 float32 ABCD R OBIS 6.8.4
HR 40502 float32 ABCD R OBIS 6.8.4*
HR 40504 float32 ABCD R OBIS 7.8.0
HR 40506 float32 ABCD R OBIS 7.8.0*
HR 40508 float32 ABCD R OBIS 7.8.1
HR 40510 float32 ABCD R OBIS 7.8.1*
HR 40512 float32 ABCD R OBIS 7.8.2
HR 40514 float32 ABCD R OBIS 7.8.2*
HR 40516 float32 ABCD R OBIS 7.8.3
HR 40518 float32 ABCD R OBIS 7.8.3*
HR 40520 float32 ABCD R OBIS 7.8.4
HR 40522 float32 ABCD R OBIS 7.8.4*
HR 40524 float32 ABCD R OBIS 8.8.0
HR 40526 float32 ABCD R OBIS 8.8.0*
HR 40528 float32 ABCD R OBIS 8.8.1
HR 40530 float32 ABCD R OBIS 8.8.1*
HR 40532 float32 ABCD R OBIS 8.8.2
HR 40534 float32 ABCD R OBIS 8.8.2*
HR 40536 float32 ABCD R OBIS 8.8.3
HR 40538 float32 ABCD R OBIS 8.8.3*
HR 40540 float32 ABCD R OBIS 8.8.4
HR 40542 float32 ABCD R OBIS 8.8.4*
HR 40544 float32 ABCD R OBIS 1.6.1
HR 40546 float32 ABCD R OBIS 1.6.1*
HR 40548 float32 ABCD R OBIS 1.6.2
HR 40550 float32 ABCD R OBIS 1.6.2*
HR 40552 float32 ABCD R OBIS 1.6.3
HR 40554 float32 ABCD R OBIS 1.6.3*
HR 40556 float32 ABCD R OBIS 1.6.4
HR 40558 float32 ABCD R OBIS 1.6.4*
HR 40560 float32 ABCD R OBIS 2.6.1
HR 40562 float32 ABCD R OBIS 2.6.1*
HR 40564 float32 ABCD R OBIS 2.6.2
HR 40566 float32 ABCD R OBIS 2.6.2*
HR 40568 float32 ABCD R OBIS 2.6.3
HR 40570 float32 ABCD R OBIS 2.6.3*
HR 40572 float32 ABCD R OBIS 2.6.4
HR 40574 float32 ABCD R OBIS 2.6.4*
HR 40576 float32 ABCD R OBIS C.4.0
HR 40578 float32 ABCD R OBIS C.5.0
HR 40580 float32 ABCD R OBIS 32.7.0
HR 40582 float32 ABCD R OBIS 52.7.0
HR 40584 float32 ABCD R OBIS 72.7.0
HR 40586 float32 ABCD R OBIS C.7.1
HR 40588 float32 ABCD R OBIS C.7.2
HR 40590 float32 ABCD R OBIS C.7.3
HR 40592 float32 ABCD R OBIS C.7.0
HR 40594 float32 ABCD R OBIS 32.7.1

Help improve this map