MBMap Registry
  1. Devices
  2. LaskaKit
  3. 8-CH RS485 Relay

LaskaKit 8-CH RS485 Relay Modbus register map

8-channel RS485 relay module, Modbus RTU. FC06 write to addresses 1-8 to control individual relays (0x0001=open,0x0002=close,0x0003=toggle,0x0004=latch,0x0005=momentary 1s,0x06AA=delay AA s). FC06 write to address 0 for broadcast (0x0007=open all,0x0008=close all). FC03 read addresses 1-8: 0x0001=open, 0x0000=close.

  • Unofficial
  • 9 registers
  • Revision 2

Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
9 holding registers
Revision
2
Added
()
File
maps/laskakit/8-ch-rs485-relay.mbmap.json · 3 KB · history
SHA-256
de05ed3f260575f52780e4c4ed90a38eff7969b455b7464fd7569cef622a2d6b
Manufacturer
laskakit.cz

Sources and notes

Source: Omni Console device library (OmniCoreST), modbus-library/laskakit-8ch-rs485-relay.toml; Source: laskakit-8ch-rs485-relay-modbus-commands.pdf. Not verified against the manufacturer's documentation

  • LaskaKit 8-CH RS485 Relay.
  • Converted automatically from the Omni Console device library (OmniCoreST).
  • Not verified against the manufacturer's documentation.
  • Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
  • | LaskaKit 8-Channel Rail RS485 Relay Module
  • |
  • | Source: laskakit-8ch-rs485-relay-modbus-commands.pdf
  • | Protocol: Modbus RTU RS-485; default 9600 baud, 8N1 (selectable via M1/M2 pads)
  • | Slave ID: set via DIP switches A0-A5 (1-63); default varies by assembly
  • | FC06: Write Single Register — relay control
  • | FC03: Read Holding Registers — relay state
  • |
  • | Addresses 1-8 correspond to channels 1-8 (1-based PDU addressing).
  • | Address 0 is a broadcast-only write address (no FC03 read).
  • |
  • | FC06 command codes (data word):
  • | 0x0001 = Open (energise)
  • | 0x0002 = Close (de-energise)
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 R
HR 1 uint16 R
HR 2 uint16 R
HR 3 uint16 R
HR 4 uint16 R
HR 5 uint16 R
HR 6 uint16 R
HR 7 uint16 R
HR 8 uint16 R

Help improve this map