Legrand EMDX3 4 120 45 Modbus register map

EMDX3 multifunction measuring unit, RS-485 Modbus RTU

  • Official
  • 131 registers
  • Modbus RTU
  • Revision 1 · 2026-10-18
  • Identity: model

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
131 holding registers
Groups
12
Translation tables
12
Revision
1 · 2026-10-18
Added
()
File
maps/legrand/emdx3-412045.mbmap.json · 25 KB · history
SHA-256
aa6d06c710f1db1b8570f2458f4833c8e00db2b03037c0cf83420da715e024dc
Manufacturer
legrand.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Device identifier holding 768 uint16 4112 = EMDX3 4 120 45

Sources and notes

Source: Legrand EMDX3 Measuring Unit RS485 Modbus table, cat. no. 4 120 45

  • The table calls the measurement block 'input registers' but lists only function codes 3 (read) and 16 (write), so every register is read as a holding register.
  • Only the sections of the table that hold measurements and settings are mapped. The 'Register Number' column of the manual is the address plus one; this map uses the address column.
  • Voltages are in mV and currents in mA. Powers and energies are raw counts whose unit depends on the CT ratio (register 4608): powers are 0.01 W, 0.01 var or 0.01 VA when CT < 5000 and 1 W, 1 var or 1 VA when CT >= 5000; energies are 10 Wh to 1 MWh per count as the manual's note 2 lists by CT ratio. Use the signed block at 5400 (always in W, var and VA) when a fixed scale is wanted.
  • A sign register next to each power value says if it is positive (0) or negative (1); the power itself is unsigned.
  • In a 3-wire network without neutral the voltage THD and the voltage minimum and maximum registers refer to the chained voltages instead of the phase voltages (note 3 of the manual).
  • Writing settings: write 0x5AA5 to register 9984, write the new values, write 0x5AA5 to 9984 again and then 0x000A to 9728 to save them. Writing 0x000B to 10240 after unlocking restores the defaults.
  • The manual gives no factory serial settings: baud rate and parity are programmable, one stop bit, device address 1 to 247. The defaults in this file are the format's defaults.
AreaAddressNameTypeAccessUnitScaleDescription
HR 768 uint16 R Returns 0x1010
HR 4096 uint32 ABCD R V ×0.001
HR 4098 uint32 ABCD R V ×0.001
HR 4100 uint32 ABCD R V ×0.001
HR 4102 uint32 ABCD R A ×0.001
HR 4104 uint32 ABCD R A ×0.001
HR 4106 uint32 ABCD R A ×0.001
HR 4108 uint32 ABCD R A ×0.001
HR 4110 uint32 ABCD R V ×0.001
HR 4112 uint32 ABCD R V ×0.001
HR 4114 uint32 ABCD R V ×0.001
HR 4116 uint32 ABCD R 3-phase; 0.01 W when CT < 5000, 1 W otherwise; sign in register 4122
HR 4118 uint32 ABCD R 3-phase; 0.01 var when CT < 5000, 1 var otherwise; sign in register 4123
HR 4120 uint32 ABCD R 3-phase; 0.01 VA when CT < 5000, 1 VA otherwise
HR 4122 uint16 R
HR 4123 uint16 R
HR 4124 uint32 ABCD R Unit set by the CT ratio (note 2), in Wh; the wrap-around counter at 5440 counts each 100 000 000
HR 4126 uint32 ABCD R Unit set by the CT ratio (note 2), in varh
HR 4128 uint32 ABCD R Unit set by the CT ratio (note 2), in Wh
HR 4130 uint32 ABCD R Unit set by the CT ratio (note 2), in varh
HR 4132 int16 R ×0.01 3-phase
HR 4133 uint16 R 3-phase
HR 4134 uint16 R Hz ×0.1
HR 4135 uint32 ABCD R 3-phase; 0.01 W when CT < 5000, 1 W otherwise
HR 4137 uint32 ABCD R 3-phase; 0.01 W when CT < 5000, 1 W otherwise
HR 4139 uint16 R min
HR 4140 uint32 ABCD R 0.01 W when CT < 5000, 1 W otherwise; sign in register 4146
HR 4142 uint32 ABCD R 0.01 W when CT < 5000, 1 W otherwise; sign in register 4147
HR 4144 uint32 ABCD R 0.01 W when CT < 5000, 1 W otherwise; sign in register 4148
HR 4146 uint16 R
HR 4147 uint16 R
HR 4148 uint16 R
HR 4149 uint32 ABCD R 0.01 var when CT < 5000, 1 var otherwise; sign in register 4155
HR 4151 uint32 ABCD R 0.01 var when CT < 5000, 1 var otherwise; sign in register 4156
HR 4153 uint32 ABCD R 0.01 var when CT < 5000, 1 var otherwise; sign in register 4157
HR 4155 uint16 R
HR 4156 uint16 R
HR 4157 uint16 R
HR 4158 uint32 ABCD R 0.01 VA when CT < 5000, 1 VA otherwise
HR 4160 uint32 ABCD R 0.01 VA when CT < 5000, 1 VA otherwise
HR 4162 uint32 ABCD R 0.01 VA when CT < 5000, 1 VA otherwise
HR 4164 int16 R ×0.01
HR 4165 int16 R ×0.01
HR 4166 int16 R ×0.01
HR 4167 uint16 R
HR 4168 uint16 R
HR 4169 uint16 R
HR 4170 uint16 R % ×0.1 Chained voltage when there is no neutral
HR 4171 uint16 R % ×0.1 Chained voltage when there is no neutral
HR 4172 uint16 R % ×0.1 Chained voltage when there is no neutral
HR 4173 uint16 R % ×0.1
HR 4174 uint16 R % ×0.1
HR 4175 uint16 R % ×0.1
HR 4176 uint32 ABCD R A ×0.001
HR 4178 uint32 ABCD R A ×0.001
HR 4180 uint32 ABCD R A ×0.001
HR 4182 uint32 ABCD R A ×0.001
HR 4184 uint32 ABCD R A ×0.001
HR 4186 uint32 ABCD R A ×0.001
HR 4188 uint32 ABCD R A ×0.001 (I1 + I2 + I3) / 3
HR 4190 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4192 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4194 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4196 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4198 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4200 uint32 ABCD R V ×0.001 Chained voltage when there is no neutral
HR 4202 uint32 ABCD R Unit set by the CT ratio (note 2), in Wh
HR 4204 uint32 ABCD R Unit set by the CT ratio (note 2), in varh
HR 4206 uint16 R h
HR 4208 uint32 ABCD R 3-phase; 0.01 W when CT < 5000, 1 W otherwise
HR 4210 uint32 ABCD R 3-phase; 0.01 var when CT < 5000, 1 var otherwise
HR 4212 uint32 ABCD R 3-phase; 0.01 VA when CT < 5000, 1 VA otherwise
HR 4214 uint32 ABCD R 3-phase; 0.01 W when CT < 5000, 1 W otherwise
HR 4216 uint32 ABCD R 3-phase; 0.01 var when CT < 5000, 1 var otherwise
HR 4218 uint32 ABCD R 3-phase; 0.01 VA when CT < 5000, 1 VA otherwise
HR 4220 uint32 ABCD R min
HR 4608 uint16 R Primary current divided by secondary current; sets the unit of powers and energies
HR 5400 int32 ABCD R W
HR 5402 int32 ABCD R var
HR 5404 int32 ABCD R W
HR 5406 int32 ABCD R W
HR 5408 int32 ABCD R W
HR 5410 int32 ABCD R var
HR 5412 int32 ABCD R var
HR 5414 int32 ABCD R var
HR 5416 int32 ABCD R ×0.001
HR 5418 int32 ABCD R ×0.001
HR 5420 int32 ABCD R ×0.001
HR 5422 int32 ABCD R ×0.001
HR 5424 uint32 ABCD R VA
HR 5426 uint32 ABCD R W
HR 5428 uint32 ABCD R var
HR 5430 uint32 ABCD R VA
HR 5432 uint32 ABCD R W
HR 5434 uint32 ABCD R var
HR 5436 uint32 ABCD R VA
HR 5440 uint16 R Counts each time the energy register passes 100 000 000
HR 5441 uint16 R
HR 5442 uint16 R
HR 5443 uint16 R