MBMap Registry
  1. Devices
  2. Lumel
  3. NR30

Lumel NR30 Modbus register map

DIN rail 3-phase power network meter with harmonics up to 63, two alarm relays, data logging and Ethernet; Modbus RTU over RS485 and Modbus TCP

  • Official
  • 986 registers
  • Modbus TCP and RTU
  • Revision 1 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1default
TCP port
502default
Serial
9600 8N2 · 9600 baud, 8 data bits, none parity, 2 stop bits
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
125 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
986 holding registers
Groups
11
Revision
1 · 2026-10-18
Added
()
File
maps/lumel/nr30.mbmap.json · 209 KB · history
SHA-256
aca3a886a9beabbc073fe000596ea94bcb7b95e831408a18d654caced662d35c
Manufacturer
lumel.com.pl

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Program version holding 4403 uint16
Serial number Serial number holding 4411 uint64 ABCD

Sources and notes

Source: Lumel, NR30 user's manual NR30-09E_R1, section 12

  • Measurements are read from the 8000 area: IEEE 754 floats in two registers, byte order 3-2-1-0 (high word first). The same values are at 6000 (order 1-0-3-2) and as 32-bit registers at 7500-7985.
  • Harmonics 2-51 are in the 8000 area and harmonics 52-63 in the 9200 area (order 3-2-1-0); the 9000 area has the same values in order 1-0-3-2.
  • Which values exist depends on the connection type (3Ph/4W, 3Ph/3W, 1Ph/2W); in 3Ph/3W the per-phase powers, voltages and power factors are not available.
  • Energy is available as floats (an overflow count in 100 MWh and a counter in kWh, kvarh or kVAh) and as 32-bit integers in hundredths of kWh. The 24-hour exported energy row is printed in the manual with the address of an earlier row; here it follows the pattern of the other rows (overflows 7991, counter 7992).
  • The Modbus TCP service uses the same register map (port 502 by default, device address in register 4146).
  • The Modbus map of the ND30 has the same layout but differs in the configuration and display registers, so it is not covered by this file.
AreaAddressNameTypeAccessUnitScaleDescription
HR 4401 uint16 R
HR 4402 uint16 R ×0.01
HR 4403 uint16 R ×0.01
HR 4405 uint16 R
HR 4406 uint16 R V ×0.1
HR 4407 uint16 R V ×0.1
HR 4408 uint16 R A ×0.01
HR 4409 uint16 R A ×0.01
HR 4411 uint64 ABCD R
HR 4421 uint16 R
HR 4422 uint16 R
HR 4423 uint16 R
HR 4415 bool bit 15 R
HR 4415 bool bit 14 R
HR 4415 bool bit 11 R
HR 4415 bool bit 10 R
HR 4415 bool bit 9 R
HR 4415 bool bit 8 R
HR 4415 bool bit 7 R
HR 4415 bool bit 6 R
HR 4415 bool bit 5 R
HR 4415 bool bit 2 R
HR 4415 bool bit 1 R
HR 4416 bool bit 0 R
HR 4416 bool bit 1 R
HR 4416 bool bit 2 R
HR 4416 bool bit 3 R
HR 4416 bool bit 4 R
HR 4416 bool bit 5 R
HR 4416 bool bit 6 R
HR 4416 bool bit 7 R
HR 4416 bool bit 8 R
HR 4416 bool bit 9 R
HR 4416 bool bit 10 R
HR 4416 bool bit 11 R
HR 4416 bool bit 12 R
HR 4416 bool bit 13 R
HR 4416 bool bit 14 R
HR 4416 bool bit 15 R
HR 4417 bool bit 15 R
HR 4417 bool bit 11 R
HR 4417 bool bit 10 R
HR 4417 bool bit 8 R
HR 4417 bool bit 7 R
HR 4417 bool bit 5 R
HR 4417 bool bit 4 R
HR 4417 bool bit 3 R
HR 4417 bool bit 2 R
HR 4417 bool bit 1 R
HR 4417 bool bit 0 R
HR 4418 bool bit 14 R Type of the reactive power
HR 4418 bool bit 13 R Type of the reactive power
HR 4418 bool bit 12 R Type of the reactive power
HR 4418 bool bit 11 R Type of the reactive power
HR 4418 bool bit 10 R Type of the reactive power
HR 4418 bool bit 9 R Type of the reactive power
HR 4418 bool bit 8 R Type of the reactive power
HR 4418 bool bit 7 R Type of the reactive power
HR 4418 bool bit 6 R Type of the reactive power
HR 4418 bool bit 5 R Type of the reactive power
HR 4418 bool bit 4 R Type of the reactive power
HR 4418 bool bit 3 R Type of the reactive power
HR 4418 bool bit 2 R Type of the reactive power
HR 4418 bool bit 1 R Type of the reactive power
HR 4418 bool bit 0 R Type of the reactive power
HR 4419 bool bit 0 R
HR 4419 bool bit 1 R
HR 4419 bool bit 2 R
HR 4419 bool bit 3 R
HR 4419 bool bit 4 R
HR 4419 bool bit 5 R
HR 4419 bool bit 6 R
HR 4419 bool bit 7 R
HR 4419 bool bit 8 R
HR 4420 bool bit 0 R
HR 4420 bool bit 1 R
HR 4420 bool bit 2 R
HR 4420 bool bit 3 R
HR 4420 bool bit 4 R
HR 4420 bool bit 5 R
HR 4420 bool bit 6 R
HR 4420 bool bit 7 R
HR 4420 bool bit 8 R
HR 4424 bool bit 1 R
HR 4424 bool bit 0 R
HR 4426 uint32 ABCD R kWh ×0.01
HR 4428 uint32 ABCD R kWh ×0.01
HR 4430 uint32 ABCD R kvarh ×0.01
HR 4432 uint32 ABCD R kvarh ×0.01
HR 4434 uint32 ABCD R kVAh ×0.01
HR 4462 uint32 ABCD R kWh ×0.01
HR 4464 uint32 ABCD R kWh ×0.01
HR 4466 uint32 ABCD R kWh ×0.01
HR 4468 uint32 ABCD R kWh ×0.01
HR 4470 uint32 ABCD R kWh ×0.01
HR 4472 uint32 ABCD R kWh ×0.01
HR 4474 uint32 ABCD R kWh ×0.01
HR 4476 uint32 ABCD R kWh ×0.01
HR 4478 uint32 ABCD R kWh ×0.01
HR 4480 uint32 ABCD R kWh ×0.01

Help improve this map