MBMap Registry
  1. Devices
  2. Metaltex
  3. IF10

Metaltex IF10 Modbus register map

Also covers IF-10

Frequency inverter: frequency, current, speed, DC bus and output voltage, power, run state, alarms, run and stop commands and frequency command

  • Official
  • 21 registers
  • Modbus RTU
  • Revision 1 · 2026-11-08

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
21 holding registers
Groups
4
Revision
1 · 2026-11-08
Added
()
File
maps/metaltex/if10.mbmap.json · 5 KB · history
SHA-256
c24eadf07dbe731c23ec5cd0b533f84bd282696d7573be8a419e1bf1c6339c0d
Manufacturer
metaltex.com.br

Sources and notes

Source: Metaltex Manual de Operação IF10, chapter 9 (Modbus RTU)

  • Modbus RTU on RS-485 (terminals RS+ and RS-). FC03 reads and FC06 writes; coils are not supported. Addresses are 0-based, as sent on the wire.
  • Factory settings: 9600 bit/s (P700 = 1), 8N1 RTU (P701 = 3), address 1 (P702).
  • To control the inverter over Modbus set P101 = 5 (frequency from the serial link) and P102 = 2 (run and stop from the serial link).
  • The manual lists the reverse command as 0006H next to the decimal value 4; the map uses 4, which fits the bit pattern of the other commands (forward 8, reset 16).
  • Written from the manual; this map has not been tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint16 R Hz ×0.01 P001
HR 2 uint16 R Hz ×0.1 P002
HR 3 uint16 R A ×0.1 P003
HR 4 uint16 R rpm P004
HR 5 uint16 R V ×0.1 P005
HR 9 uint16 R V ×0.1 P009
HR 20 uint16 R kW ×0.1 P020
HR 28 uint16 R P028
HR 27 bool bit 0 R P027
HR 27 bool bit 1 R P027
HR 27 bool bit 2 R P027
HR 27 bool bit 3 R P027
HR 27 bool bit 4 R P027
HR 27 bool bit 6 R P027
HR 27 bool bit 7 R P027
HR 27 bool bit 8 R P027
HR 27 bool bit 9 R P027
HR 27 bool bit 10 R P027
HR 27 bool bit 15 R P027
HR 8192 uint16 W Cannot be read. Needs P102 = 2. After a jog, send stop before run
HR 8193 uint16 RW Hz ×0.01 Needs P101 = 5