Novus RHT Climate Modbus register map

Also covers RHT Climate WM, RHT Climate DM

Temperature and humidity transmitter (wall and duct mount) with two analog outputs, two alarm outputs, buzzer and Modbus RTU over RS485: temperature, humidity and psychrometric values, min/max, outputs, alarms, forcing and diagnostics

  • Official
  • 126 registers
  • Modbus RTU
  • Revision 1 · 2026-10-31
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
126 holding registers
Groups
13
Translation tables
4
Revision
1 · 2026-10-31
Firmware
from 1.4 V1.4x or later
Added
()
File
maps/novus/rht-climate.mbmap.json · 27 KB · history
SHA-256
e31d5d871dd05e9086ce37c645de327b4640c6a7482247767a9b51c6ab818b46
Manufacturer
novus.com.br

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 300 uint32 ABCD
Firmware Firmware version holding 302 uint16

Sources and notes

Source: Novus RHT Climate WM / DM instruction manual V1.4x I (Portuguese), chapters 7 and 10

  • Functions 03, 05, 06 and 16; writes with address 0 are broadcast.
  • Serial defaults: address 1, 19200 bit/s, no parity. The device answers whatever the stop bits are.
  • 32-bit values are two registers, least significant word first; every register is big-endian. Both registers of a 32-bit value must be read or written together.
  • The measurements are shown with two decimals. Units follow the unit system (register 127): SI (°C, mbar, g/m³, g/kg, kJ/kg) or US (°F, psi, gr/ft³, gr/lb, BTU/lb).
  • The manual does not give the decimals of the 32-bit output limits and alarm setpoints; this map reads them with two decimals, like the measurements. Their ranges depend on the quantity chosen for the output or alarm.
  • Settings with an input pair (103-106, 115-118, 135-138, 152-155, 169-172) are copied to the working pair (108-111, 120-123, 145-148, 162-165, 179-182) when in range; out-of-range inputs are flagged in register 343.
  • Alarm 3 in the register table is the buzzer (models with display).
  • Written from the manufacturer's manual; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 int32 CDAB R %RH ×0.01 %RH
HR 2 int32 CDAB R ×0.01 °C (°F in US units)
HR 4 int32 CDAB R ×0.01 °C (°F in US units)
HR 6 int32 CDAB R ×0.01 °C (°F in US units)
HR 8 int32 CDAB R ×0.01 °C (°F in US units)
HR 10 int32 CDAB R ×0.01 kJ/kg (BTU/lb in US units)
HR 12 int32 CDAB R ×0.01 g/m³ (gr/ft³ in US units)
HR 14 int32 CDAB R ×0.01 mbar (psi in US units)
HR 16 int32 CDAB R ×0.01 g/kg (gr/lb in US units)
HR 18 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 20 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 22 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 24 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 26 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 28 int32 CDAB R ×0.01 The manual gives a range of 0-1000 for this pair, unlike the measurement; read here with two decimals like the measurement
HR 217 uint16 RW Write 1 to reset every minimum and maximum
HR 101 uint16 RW
HR 102 uint16 RW
HR 103 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 108 when valid
HR 105 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 110 when valid
HR 107 uint16 RW
HR 108 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 110 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 113 uint16 RW
HR 114 uint16 RW
HR 115 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 120 when valid
HR 117 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 122 when valid
HR 119 uint16 RW
HR 120 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 122 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 133 uint16 RW
HR 134 uint16 RW
HR 135 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 145 when valid
HR 137 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 147 when valid
HR 139 uint16 RW
HR 140 uint16 RW ×0.1 In the unit of the alarm quantity
HR 141 uint16 RW s
HR 142 uint16 RW s
HR 143 uint16 RW
HR 144 uint16 RW
HR 145 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 147 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 150 uint16 RW
HR 151 uint16 RW
HR 152 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 162 when valid
HR 154 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 164 when valid
HR 156 uint16 RW
HR 157 uint16 RW ×0.1 In the unit of the alarm quantity
HR 158 uint16 RW s
HR 159 uint16 RW s
HR 160 uint16 RW
HR 161 uint16 RW
HR 162 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 164 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 167 uint16 RW
HR 168 uint16 RW
HR 169 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 179 when valid
HR 171 int32 CDAB RW ×0.01 Two decimals assumed, as in the measurements; copied to register 181 when valid
HR 173 uint16 RW
HR 174 uint16 RW ×0.1 In the unit of the alarm quantity
HR 175 uint16 RW s
HR 176 uint16 RW s
HR 177 uint16 RW
HR 178 uint16 RW
HR 179 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 181 int32 CDAB R ×0.01 Two decimals assumed, as in the measurements
HR 125 uint16 RW s
HR 126 uint16 RW s
HR 127 uint16 RW
HR 192 int16 RW ×0.1 ±5.0 °C (±9.0 °F)
HR 193 int16 RW %RH ×0.1
HR 200 uint16 RW Used for the psychrometric calculations: 1013 = 1013 mbar in SI units, 147 = 14.7 psi in US units
HR 187 uint16 RW
HR 209 uint16 RW
HR 221 uint16 RW
HR 222 uint16 RW
HR 201 uint16 RW
HR 202 uint16 RW 0-10.00 V or 3.6-21.00 mA; the manual does not give the encoding
HR 203 uint16 RW
HR 204 uint16 RW 0-10.00 V or 3.6-21.00 mA; the manual does not give the encoding
HR 205 uint16 RW
HR 206 uint16 RW
HR 207 uint16 RW
HR 208 uint16 RW
HR 211 uint16 RW
HR 212 uint16 RW
HR 213 uint16 RW
HR 215 uint16 RW
HR 214 uint16 RW %RH ×0.1
HR 216 int16 RW ×0.1 °C (°F in US units)
HR 184 uint16 RW
HR 185 uint16 RW
HR 186 uint16 RW
HR 341 bool bit 1 R
HR 341 bool bit 2 R
HR 341 bool bit 3 R
HR 341 bool bit 4 R
HR 341 bool bit 5 R
HR 341 bool bit 6 R
HR 341 bool bit 7 R