Panasonic KW9M Eco-POWER METER Modbus register map

Also covers AKW91110, AKW92112

Multi-circuit power meter with RS-485 Modbus RTU

  • Official
  • 120 registers
  • Modbus RTU
  • Revision 1 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8O1 · 19200 baud, 8 data bits, odd parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based
Max read
26 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
120 holding registers
Groups
9
Translation tables
8
Revision
1 · 2026-10-18
Added
()
File
maps/panasonic/kw9m.mbmap.json · 22 KB · history
SHA-256
fbcaf83ea48dad730d8ce6c6faa9526f28016222202b4536a0e59101bace5350
Manufacturer
industry.panasonic.com

Sources and notes

Source: Panasonic KW9M Eco-POWER METER User's Manual, section 7.4 MODBUS (RTU) communication

  • The meter leaves the factory set to MEWTOCOL: set Protocol (0x62) to MODBUS at the keys or with the Configurator before using this map; changing the protocol resets the serial settings.
  • 32-bit values take two registers with the least significant word at the lower address (the manual marks the lower register <LSB>), so the word order is little; the bytes of each register are big-endian.
  • The manual lists each measurement twice at different resolutions. This map uses the finer one (0.001 kWh, 0.001 kW, 0.01 V, 0.001 A, 0.01 Hz). The coarser mirrors start at 0x64 (energy, 0.01 kWh), 0x8C (power, 0.01 kW), 0xA4 (voltage, 0.1 V), 0xB4 (current, 0.01 A) and 0xBE (frequency, 0.1 Hz), and 0x145 to 0x158 repeat the total energies.
  • The numbers in brackets, (1) to (3), are the measuring circuits or phases of the chosen wiring; with a single-phase two-wire meter only (1) is meaningful.
  • Supported functions are 03 (read), 06 (write one register) and 16 (write several); a read is limited to 26 registers (57 bytes) and a write to 23 (55 bytes). Registers that are not listed read as 0 and writes to them are acknowledged but ignored, as are writes outside the setting range.
  • Settings written over Modbus go to the internal memory straight away, which limits its life: do not rewrite them in a loop.
  • Integral energies can be cleared by writing 0 to them or with the reset registers; the totals are read only. Instantaneous active and reactive powers are signed 32-bit values.
  • The factory serial settings are device number 1, 19200 bit/s, 8 data bits, odd parity, 1 stop bit, response time 5 ms.
AreaAddressNameTypeAccessUnitScaleDescription
HR 50 uint16 RW
HR 51 uint16 RW
HR 52 uint16 RW
HR 53 uint16 RW
HR 54 uint16 RW ms
HR 55 uint16 RW
HR 56 uint16 RW A 1 A or 5 A
HR 57 uint16 RW A
HR 58 uint16 RW ×0.01
HR 59 int16 RW °C ×0.1
HR 65 uint16 RW ms ×100
HR 70 uint16 RW min 0 = display always on
HR 87 uint16 RW ×0.01
HR 93 uint16 RW ×0.01
HR 94 uint16 RW
HR 95 uint16 RW min 0 = fixed display item
HR 96 uint16 RW s
HR 97 uint16 RW
HR 98 uint16 RW Changing it resets the other serial settings to their defaults
HR 30108 uint16 RW
HR 30109 uint16 RW min
HR 30110 uint16 RW min
HR 30111 uint16 RW min
HR 30200 uint16 RW
HR 30300 uint16 RW
HR 30301 uint16 RW
HR 30302 uint16 RW
HR 30303 uint16 RW
HR 30306 uint16 RW
HR 30307 uint16 RW % ×0.1
HR 198 uint32 CDAB RW kWh ×0.001
HR 200 uint32 CDAB RW kWh ×0.001
HR 202 uint32 CDAB RW kWh ×0.001
HR 204 uint32 CDAB R kWh ×0.001
HR 206 uint32 CDAB RW kvarh ×0.001
HR 208 uint32 CDAB RW kvarh ×0.001
HR 210 uint32 CDAB RW kvarh ×0.001
HR 212 uint32 CDAB R kvarh ×0.001
HR 214 uint32 CDAB RW kVAh ×0.001
HR 216 uint32 CDAB RW kVAh ×0.001
HR 218 uint32 CDAB RW kVAh ×0.001
HR 220 uint32 CDAB R kVAh ×0.001
HR 222 uint32 CDAB RW kWh ×0.001
HR 224 uint32 CDAB RW kWh ×0.001
HR 226 uint32 CDAB RW kWh ×0.001
HR 228 uint32 CDAB R kWh ×0.001
HR 230 uint32 CDAB RW kvarh ×0.001
HR 232 uint32 CDAB RW kvarh ×0.001
HR 234 uint32 CDAB RW kvarh ×0.001
HR 236 uint32 CDAB R kvarh ×0.001
HR 238 int32 CDAB R kW ×0.001
HR 240 int32 CDAB R kW ×0.001
HR 242 int32 CDAB R kW ×0.001
HR 244 int32 CDAB R kW ×0.001
HR 246 int32 CDAB R kvar ×0.001
HR 248 int32 CDAB R kvar ×0.001
HR 250 int32 CDAB R kvar ×0.001
HR 252 int32 CDAB R kvar ×0.001
HR 254 uint32 CDAB R kVA ×0.001
HR 256 uint32 CDAB R kVA ×0.001
HR 258 uint32 CDAB R kVA ×0.001
HR 260 uint32 CDAB R kVA ×0.001
HR 262 uint32 CDAB R V ×0.01
HR 264 uint32 CDAB R V ×0.01
HR 266 uint32 CDAB R V ×0.01
HR 268 uint32 CDAB R V ×0.01
HR 270 uint32 CDAB R V ×0.01
HR 272 uint32 CDAB R V ×0.01
HR 274 uint32 CDAB R V ×0.01
HR 276 uint32 CDAB R V ×0.01
HR 278 uint32 CDAB R A ×0.001
HR 280 uint32 CDAB R A ×0.001
HR 282 uint32 CDAB R A ×0.001
HR 286 uint32 CDAB R A ×0.001
HR 288 uint16 R Hz ×0.01
HR 289 uint16 R Hz ×0.01
HR 290 uint16 R Hz ×0.01
HR 291 uint16 R Hz ×0.01
HR 194 int16 R ×0.001
HR 195 int16 R ×0.001
HR 196 int16 R ×0.001
HR 197 int16 R ×0.001
HR 324 uint16 R
HR 305 uint32 CDAB R kW ×0.001
HR 307 uint32 CDAB R kvar ×0.001
HR 309 uint32 CDAB R kVA ×0.001
HR 311 uint32 CDAB R kW ×0.001
HR 313 uint32 CDAB R kvar ×0.001
HR 315 uint32 CDAB R A ×0.001
HR 317 uint32 CDAB R A ×0.001
HR 319 uint32 CDAB R A ×0.001
HR 31903 uint32 CDAB R kW ×0.001
HR 31908 uint32 CDAB R kvar ×0.001
HR 31913 uint32 CDAB R kVA ×0.001
HR 31918 uint32 CDAB R kW ×0.001
HR 31923 uint32 CDAB R kvar ×0.001
HR 31928 uint32 CDAB R A ×0.001
HR 31933 uint32 CDAB R A ×0.001
HR 31938 uint32 CDAB R A ×0.001
HR 418 int16 R °C ×0.1