MBMap Registry
  1. Devices
  2. Powerside
  3. PQube 3

Powerside PQube 3 Modbus register map

Also covers PQube 3e, PQube 3v, PQube 3rs

Power quality analyser. Classic bank plus the main values of the voltage, current and power banks.

  • Official
  • 193 registers
  • Modbus TCP
  • Revision 1 · 2026-10-21
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
125 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
193 holding registers
Groups
7
Translation tables
2
Revision
1 · 2026-10-21
Added
()
File
maps/powerside/pqube-3.mbmap.json · 28 KB · history
SHA-256
8d8210a90a5de2cf6d9f65f87621cebcfac0206d4aa6808cdad1af409481d9d9
Manufacturer
powerside.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware major holding 29672 uint16
Firmware Firmware minor holding 29673 uint16
Firmware Firmware bug fix holding 29674 uint16

Sources and notes

  • Every address is the manual's register offset plus the Modbus base address, which is 0x7000 (28672) by default. If the base was changed in setup.ini, subtract 0x7000 from the addresses here and add the new base.
  • The manual treats FC03 and FC04 as the same: every register reads the same either way, so they are listed as holding registers. There are no coils or discrete inputs.
  • A 32-bit float spans two registers. The manual gives the byte order of such values as a setup.ini option (big endian by default), which is word_order here.
  • Registers refresh at about 2 Hz. The device accepts up to about 10 simultaneous TCP clients.
  • The manual lists many more registers (harmonics up to the 50th, interharmonics, scope and HF values, analog bank at 0x6000) that are not included here. The Classic bank is kept for compatibility with the PQube Classic; the voltage, current and power banks repeat many of its values.
  • Not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 28672 float32 ABCD R V
HR 28674 float32 ABCD R V
HR 28676 float32 ABCD R V
HR 28678 float32 ABCD R V
HR 28680 float32 ABCD R V
HR 28682 float32 ABCD R V
HR 28684 float32 ABCD R V
HR 28686 float32 ABCD R V
HR 28688 float32 ABCD R V
HR 28690 float32 ABCD R V
HR 28692 float32 ABCD R V
HR 28694 float32 ABCD R V
HR 28696 float32 ABCD R V
HR 28698 float32 ABCD R Hz
HR 28700 float32 ABCD R A
HR 28702 float32 ABCD R A
HR 28704 float32 ABCD R A
HR 28706 float32 ABCD R A
HR 28708 float32 ABCD R W
HR 28710 float32 ABCD R VA
HR 28712 float32 ABCD R Usually 0 or 1; a fractional value is a duty cycle
HR 28714 float32 ABCD R A
HR 28716 float32 ABCD R A
HR 28718 float32 ABCD R A
HR 28720 float32 ABCD R W
HR 28722 float32 ABCD R W
HR 28724 float32 ABCD R W
HR 28726 float32 ABCD R VA
HR 28728 float32 ABCD R VA
HR 28730 float32 ABCD R VA
HR 28732 float32 ABCD R Wh
HR 28734 float32 ABCD R VAh
HR 28736 float32 ABCD R %
HR 28738 float32 ABCD R %
HR 28740 float32 ABCD R %
HR 28742 float32 ABCD R %
HR 28752 float32 ABCD R var
HR 28754 float32 ABCD R
HR 28756 float32 ABCD R °C
HR 28758 float32 ABCD R %RH
HR 28760 float32 ABCD R °C
HR 28762 float32 ABCD R %RH
HR 28768 float32 ABCD R A
HR 28750 uint16 R New events since the last poll; cleared by reading
HR 28751 uint16 R New trends since the last poll; cleared by reading
HR 28770 float32 ABCD R V
HR 28772 float32 ABCD R °
HR 28774 float32 ABCD R V
HR 28776 float32 ABCD R °
HR 28778 float32 ABCD R V
HR 28780 float32 ABCD R °
HR 28782 float32 ABCD R A
HR 28784 float32 ABCD R °
HR 28786 float32 ABCD R A
HR 28788 float32 ABCD R °
HR 28790 float32 ABCD R A
HR 28792 float32 ABCD R °
HR 28806 uint16 R
HR 28807 uint16 R
HR 28808 uint16 R
HR 28809 uint16 R
HR 28810 uint16 R
HR 28811 uint16 R
HR 28812 float32 ABCD R h
HR 28846 float32 ABCD R %
HR 28848 float32 ABCD R %
HR 28850 float32 ABCD R %
HR 28852 float32 ABCD R %
HR 28854 float32 ABCD R W
HR 28856 float32 ABCD R Wh
HR 28864 float32 ABCD R %
HR 28866 float32 ABCD R %
HR 28868 float32 ABCD R %
HR 28870 float32 ABCD R %
HR 28872 float32 ABCD R %
HR 28874 float32 ABCD R %
HR 28876 float32 ABCD R W
HR 28878 float32 ABCD R W
HR 28880 float32 ABCD R W
HR 28882 float32 ABCD R VA
HR 28884 float32 ABCD R VA
HR 28886 float32 ABCD R VA
HR 28888 float32 ABCD R var
HR 28890 float32 ABCD R var
HR 28892 float32 ABCD R var
HR 28894 float32 ABCD R
HR 28896 float32 ABCD R
HR 28898 float32 ABCD R
HR 28912 float32 ABCD R varh
HR 29672 uint16 R
HR 29673 uint16 R
HR 29674 uint16 R
HR 29694 uint16 R
HR 29695 uint16 R
HR 29696 uint16 R min Averaging period N used by the N-minute peak values
HR 30672 float32 ABCD R V
HR 30674 float32 ABCD R V
HR 30676 float32 ABCD R V
HR 30678 float32 ABCD R V
HR 30680 float32 ABCD R V

Help improve this map