Rayleigh Instruments RI-F400-C Modbus register map
Rayleigh RI-F400-C three-phase multifunction meter with RS-485 Modbus RTU
- Official
- 129 registers
- Modbus RTU
- Revision 1 · 2026-10-17
- Identity: serial number
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1
- Serial
- 9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
- Byte / word order
- CDAB · bytes big-endian, words low first (word swap)
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 47 holding registers, 82 input registers
- Groups
- 2
- Revision
- 1 · 2026-10-17
- Added
- ()
- File
- maps/rayleigh-instruments/ri-f400.mbmap.json · 22 KB · history
- SHA-256
- 2e10d09bbd60014123dd4128b28b012420013d07268e3f1fc0e0c10a653f32fa
- Manufacturer
- rayleigh.com
Device identity
What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.
| Role | Register | Address | Type | Values |
|---|---|---|---|---|
| Serial number | Serial No. | input 684 | uint32 CDAB |
Sources and notes
- RI-F400-C Modbus Registers · version V01
Source: Rayleigh Instruments, "RI-F400-C Modbus Registers", RI-F400-C-COMM V01
- Defaults: address 1, 9600 baud, 8 data bits, no parity, 1 stop bit. Baud rates 300 to 19200.
- Floats are sent low word first (the table's FLOAT REVERSE WORD); a setting in the setup registers can change this.
- The table numbers measurements 3xxxx and settings 4xxxx and gives the PDU address in hex; this map reads them as input and holding registers at those addresses. The table also says to add 1 to the address for function 3 holding-register access, so check the addressing on the device.
- The integer (HEX) copies of the measurements are not included: the table does not give their scaling.
- Settings that take a decimal range (pulse duration, pulse weight) are listed without a scale because the table does not give one.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| IR | 0 | float32 CDAB | R | V | |||
| IR | 2 | float32 CDAB | R | V | |||
| IR | 4 | float32 CDAB | R | V | |||
| IR | 6 | float32 CDAB | R | V | |||
| IR | 8 | float32 CDAB | R | V | |||
| IR | 10 | float32 CDAB | R | V | |||
| IR | 12 | float32 CDAB | R | V | |||
| IR | 14 | float32 CDAB | R | V | |||
| IR | 16 | float32 CDAB | R | A | |||
| IR | 18 | float32 CDAB | R | A | |||
| IR | 20 | float32 CDAB | R | A | |||
| IR | 22 | float32 CDAB | R | A | |||
| IR | 24 | float32 CDAB | R | kW | |||
| IR | 26 | float32 CDAB | R | kW | |||
| IR | 28 | float32 CDAB | R | kW | |||
| IR | 30 | float32 CDAB | R | kVA | |||
| IR | 32 | float32 CDAB | R | kVA | |||
| IR | 34 | float32 CDAB | R | kVA | |||
| IR | 36 | float32 CDAB | R | kvar | |||
| IR | 38 | float32 CDAB | R | kvar | |||
| IR | 40 | float32 CDAB | R | kvar | |||
| IR | 42 | float32 CDAB | R | kW | |||
| IR | 44 | float32 CDAB | R | kVA | |||
| IR | 46 | float32 CDAB | R | kvar | |||
| IR | 48 | float32 CDAB | R | ||||
| IR | 50 | float32 CDAB | R | ||||
| IR | 52 | float32 CDAB | R | ||||
| IR | 54 | float32 CDAB | R | ||||
| IR | 56 | float32 CDAB | R | Hz | |||
| IR | 58 | float32 CDAB | R | kWh | |||
| IR | 60 | float32 CDAB | R | kVAh | |||
| IR | 62 | float32 CDAB | R | kvarh | |||
| IR | 64 | float32 CDAB | R | kW | |||
| IR | 66 | float32 CDAB | R | kW | |||
| IR | 68 | float32 CDAB | R | kvar | |||
| IR | 70 | float32 CDAB | R | kvar | |||
| IR | 72 | float32 CDAB | R | kVA | |||
| IR | 74 | float32 CDAB | R | A | |||
| IR | 76 | float32 CDAB | R | A | The table's hex address is a typo; the decimal register number is used | ||
| IR | 78 | float32 CDAB | R | A | |||
| IR | 80 | float32 CDAB | R | A | |||
| IR | 82 | float32 CDAB | R | hrs | |||
| IR | 84 | float32 CDAB | R | kWh | |||
| IR | 86 | float32 CDAB | R | kWh | |||
| IR | 88 | float32 CDAB | R | kWh | |||
| IR | 90 | float32 CDAB | R | kWh | |||
| IR | 92 | float32 CDAB | R | kWh | |||
| IR | 94 | float32 CDAB | R | kWh | |||
| IR | 96 | float32 CDAB | R | kWh | |||
| IR | 98 | float32 CDAB | R | kWh | |||
| IR | 100 | float32 CDAB | R | kvarh | |||
| IR | 102 | float32 CDAB | R | kvarh | |||
| IR | 104 | float32 CDAB | R | kvarh | |||
| IR | 106 | float32 CDAB | R | kvarh | |||
| IR | 108 | float32 CDAB | R | kvarh | |||
| IR | 110 | float32 CDAB | R | kvarh | |||
| IR | 112 | float32 CDAB | R | kvarh | |||
| IR | 114 | float32 CDAB | R | kvarh | |||
| IR | 116 | float32 CDAB | R | kVAh | |||
| IR | 118 | float32 CDAB | R | kVAh | |||
| IR | 120 | float32 CDAB | R | kVAh | |||
| IR | 122 | float32 CDAB | R | A | |||
| IR | 124 | float32 CDAB | R | % | |||
| IR | 126 | float32 CDAB | R | % | |||
| IR | 128 | float32 CDAB | R | % | |||
| IR | 130 | float32 CDAB | R | % | |||
| IR | 132 | float32 CDAB | R | % | |||
| IR | 134 | float32 CDAB | R | % | |||
| IR | 136 | float32 CDAB | R | % | |||
| IR | 138 | float32 CDAB | R | % | |||
| IR | 140 | float32 CDAB | R | % | |||
| IR | 684 | uint32 CDAB | R | Read as hexadecimal | |||
| IR | 700 | uint32 CDAB | R | ||||
| IR | 702 | float32 CDAB | R | kW | |||
| IR | 704 | float32 CDAB | R | kW | |||
| IR | 706 | float32 CDAB | R | kvar | |||
| IR | 708 | float32 CDAB | R | kvar | |||
| IR | 710 | float32 CDAB | R | kVA | |||
| IR | 712 | float32 CDAB | R | A | |||
| IR | 714 | float32 CDAB | R | A | |||
| IR | 716 | float32 CDAB | R | A | |||
| IR | 718 | float32 CDAB | R | A | |||
| HR | 0 | uint16 | RW | Default 1000 | |||
| HR | 1 | uint16 | RW | Default 0 | |||
| HR | 2 | uint16 | R | A | 5. Default 5 | ||
| HR | 3 | uint16 | RW | A | Default 5 | ||
| HR | 4 | uint16 | RW | V | Default 350 | ||
| HR | 5 | uint32 CDAB | RW | V | Default 350 | ||
| HR | 7 | uint16 | RW | Default 1 | |||
| HR | 8 | uint16 | RW | Default 5 | |||
| HR | 9 | uint16 | RW | Default 0 | |||
| HR | 10 | uint16 | RW | Default 0 | |||
| HR | 11 | uint16 | RW | s | Default 0 | ||
| HR | 12 | uint16 | W | 1: Set to factory setting range | |||
| HR | 13 | uint16 | W | 1: Reset total active energy | |||
| HR | 14 | uint16 | W | 1: Reset total apparent energy | |||
| HR | 15 | uint16 | W | 1: Reset total reactive energy | |||
| HR | 16 | uint16 | RW | Default 21 | |||
| HR | 17 | uint16 | RW | 1-21 / 1-First Page; 21-Last Page | |||
| HR | 18 | uint16 | RW | 1-21 / 1-First Page; 21-Last Page |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.