REDZ LKM124 Modbus register map

P1 Companion Standard meter to Modbus RTU gateway, RS485 on the Modbus side. Reads one meter

  • Official
  • 36 registers
  • Modbus RTU
  • Revision 2

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
36 holding registers
Groups
3
Translation tables
1
Revision
2
Added
()
File
maps/redz/lkm124.mbmap.json · 11 KB · history
SHA-256
84613551cb108a836adb08b55f36d6d7ae1ffba821c8d53ed4f92d9d6d49c2f8
Manufacturer
redz-sc.com

Sources and notes

  • LKM Series Electricity Meter Protocol to Modbus Protocol Gateways User Manual
    sections 6.1, 6.5-6.10 and 8 (standard 24-register firmware)

Source: REDZ, "LKM Series Electricity Meter Protocol to Modbus Protocol Gateways User Manual", sections 6.1, 6.5-6.10 and 8 (standard 24-register firmware)

  • REDZ LKM124.
  • Standard firmware with the OBIS_EURO list (24 values per meter). Other firmware (OBIS_EURO_1..14, TRF, 64-register versions) keeps the same addresses but maps different OBIS codes, so the names below would be wrong for it.
  • Data addresses: the manual's table lists them as 1, 3, 5... (1-based), while its Modbus Poll and ZTerminal examples read
  • Time at wire address 0 and 1.8.0 at 4. This map follows the examples. The settings (128-133) and monitoring (160-189)
  • addresses are wire addresses, as the FC06/FC16 examples show.
  • Values are the read-out digits without the decimal point, so no scale or unit is given: they depend on the meter.
  • Mode switch 1 (OFF-OFF): 9600 8N1; modes 2-4 are 19200, 57600 and 115200 8N1 on both sides.
  • Table code, reading method and init string are IEC 62056-21 settings; the manual does not say whether the P1 firmware uses them.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint32 ABCD R OBIS 0.9.1. hhmmss as digits (10:25:07 reads 102507). 0 if not in the read-out
HR 2 uint32 ABCD R OBIS 0.9.2. yymmdd as digits (22-09-14 reads 220914). 0 if not in the read-out
HR 4 uint32 ABCD R OBIS 1.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 6 uint32 ABCD R OBIS 2.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 8 uint32 ABCD R OBIS 3.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 10 uint32 ABCD R OBIS 4.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 12 uint32 ABCD R OBIS 5.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 14 uint32 ABCD R OBIS 6.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 16 uint32 ABCD R OBIS 7.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 18 uint32 ABCD R OBIS 8.8.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 20 uint32 ABCD R OBIS 1.6.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 22 uint32 ABCD R OBIS 2.6.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 24 uint32 ABCD R OBIS 1.5.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 26 uint32 ABCD R OBIS 1.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 28 uint32 ABCD R OBIS 31.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 30 uint32 ABCD R OBIS 51.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 32 uint32 ABCD R OBIS 71.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 34 uint32 ABCD R OBIS 32.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 36 uint32 ABCD R OBIS 52.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 38 uint32 ABCD R OBIS 72.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 40 int32 ABCD R OBIS 13.7.0. Can be negative; the manual lists UInt32. 0 if not in the read-out
HR 42 uint32 ABCD R OBIS 14.7.0. Digits of the read-out value without the decimal point (e.g. 6895.2317 reads 68952317): apply the meter's decimals. 0 if not in the read-out
HR 44 uint32 ABCD R OBIS C.1.0. Meter ID / serial number. 0 if not in the read-out
HR 46 int32 ABCD R OBIS 16.7.0. Can be negative; the manual lists UInt32. 0 if not in the read-out
HR 128 uint16 RW Gateway slave id; answers the write with the old id
HR 129 uint16 RW s Wait after each read attempt (default 10)
HR 130 uint16 RW ASCII code sent in the IEC 62056-21 option select message (0x30 = '0' default; 0x37 = '7')
HR 131 uint16 RW Default 1
HR 132 uint16 RW Times the init string is sent before the request; 0 = off
HR 133 uint16 RW Meters read on the bus (this model reads one meter)
HR 160 uint32 ABCD RW IEC 62056-21 device address (usually the serial number); 0 = not used. Write with FC16
HR 162 uint32 ABCD R Successful meter reads
HR 164 uint32 ABCD R s Seconds since power-up; the gateway restarts every 24 h
HR 166 uint32 ABCD R 0xDDMYYYVV: day byte; month nibble; year 12 bits; version byte
HR 168 uint32 ABCD R Same layout as Firmware original; differs after a field upgrade
HR 170 uint32 ABCD RW 4 wake-up bytes sent before the read-out (needs Init string repeat count >= 1). Write with FC16