SATEC PM130 PLUS Modbus register map

Also covers PM130A, PM130P, PM130E, PM130EH

Three-phase powermeter series. Live values, demands, energy, status and the main setup registers, read as 32-bit integers.

  • Official
  • 243 registers
  • Revision 1 · 2026-11-10
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first default
Addresses
0-baseddefault

Connection values are defaults: the device may be configured differently.

Map

Registers
243 holding registers
Groups
19
Translation tables
7
Revision
1 · 2026-11-10
Added
()
File
maps/satec/pm130-plus.mbmap.json · 45 KB · history
SHA-256
ede78b689cb2c253f1428075839dffa64e6bb5f931ad1f0863284810684307ef
Manufacturer
www.satec-global.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware version holding 2565 uint16

Sources and notes

  • Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH, Modbus Communications Protocol Reference Guide · version BG0427 Rev. A10, 2022-03
  • Registers are numbered from 0 as in the guide (add 40001 for a 5-digit 4XXXX address). Function 03 and 04 read the same registers.
  • 32-bit values use two registers with the low-order word first (word_order little). They are read here in the default 32-bit integer format. Register 246 can switch analog values, counters and energy to IEEE float32; with that setting the integer registers of this map decode wrongly.
  • Units of the 32-bit values depend on the device resolution option (register 2390). Low resolution (default) is assumed: 1 V, 1 A and 1 kW/kvar/kVA, in primary units (PT and CT ratios applied). High resolution gives 0.1 V (PT ratio 1) or 1 V, 0.01 A, and 1 W/var/VA (PT ratio 1) or 1 kW/kvar/kVA.
  • Energy registers (14720 onward), demands, summary/TOU registers and phase energies exist only in PM130E and PM130EH. Total harmonic values (THD, K-factor, TDD) are only in PM130EH. Harmonics, PF, frequency and reactive values do not apply to DC devices.
  • In 3-wire connection schemes the per-phase current unbalance, power factor, active power and reactive power read zero; only the totals are meaningful.
  • The 16-bit scaled registers (256-308 and 6656 onward), the harmonic spectra, min/max logs with timestamps, data logs and file transfer, TOU and IEC 60870/DNP setup are not included.
  • Total PF lag and lead (offsets 8-12 of the 1-second total block) are printed as UINT16 in a 32-bit block and are left out. The instrument options bitmap (2566-2567) is split into the low-word flags and the I/O counts.
  • The Device Identification block (serial number, model ID and name, device firmware version) is printed at address 46111 with offsets +0 to +31, which collides with the Factory Device Settings block that starts at 46112. It is left out; use the firmware version at 2565. Network IP addresses are left out because their word order is not stated.
  • Setup registers are best written together in a single request, or after zeroing the setup (guide, section 1). When password protection is enabled, write the password to register 2575 first.
  • Not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 240 uint16 R Modbus conversion scale, low end of the 16-bit scaled range
HR 241 uint16 R Modbus conversion scale, high end of the 16-bit scaled range
HR 2563 uint16 R 1-99
HR 2565 uint16 R ×0.01 Printed range 1100-1199: two high digits major, two low digits minor (1100 reads as 11.00)
HR 2566 uint16 R Format F28, bits 0-15 of the 32-bit value at 2566-2567
HR 2566 bool bit 0 R
HR 2566 bool bit 1 R
HR 2566 bool bit 6 R
HR 2566 bool bit 7 R
HR 2566 bool bit 8 R
HR 2566 bool bit 9 R
HR 2566 bool bit 10 R
HR 2566 bool bit 12 R
HR 2567 uint16 bits 0–2 R +1 Bits 16-18 of the 32-bit instrument options: number of RO minus 1
HR 2567 uint16 bits 3–6 R +1 Bits 19-22 of the 32-bit instrument options: number of DI minus 1
HR 2567 uint16 bits 7–8 R +1 Bits 23-24 of the 32-bit instrument options: number of AO minus 1
HR 3484 uint16 R Current serial port number
HR 46112 uint16 R V Factory setting: 690, or 120 (option U)
HR 46113 uint16 R % Factory setting: 120
HR 46114 uint16 R Relevant for devices that support AC/DC mode
HR 46116 uint16 R A Factory setting: 1 or 5
HR 46117 uint16 R % Factory setting: 200
HR 13952 uint32 CDAB R V Line-to-neutral with wiring 4LN3, 3LN3 or 3BLN3, otherwise line-to-line
HR 13954 uint32 CDAB R V Line-to-neutral with wiring 4LN3, 3LN3 or 3BLN3, otherwise line-to-line
HR 13956 uint32 CDAB R V Line-to-neutral with wiring 4LN3, 3LN3 or 3BLN3, otherwise line-to-line
HR 13958 uint32 CDAB R A
HR 13960 uint32 CDAB R A
HR 13962 uint32 CDAB R A
HR 13964 int32 CDAB R kW
HR 13966 int32 CDAB R kW
HR 13968 int32 CDAB R kW
HR 13970 int32 CDAB R kvar
HR 13972 int32 CDAB R kvar
HR 13974 int32 CDAB R kvar
HR 13976 uint32 CDAB R kVA
HR 13978 uint32 CDAB R kVA
HR 13980 uint32 CDAB R kVA
HR 13982 int32 CDAB R ×0.001
HR 13984 int32 CDAB R ×0.001
HR 13986 int32 CDAB R ×0.001
HR 13988 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 13990 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 13992 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 13994 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 13996 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 13998 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 14000 uint32 CDAB R ×0.1 3-second value. PM130EH only
HR 14002 uint32 CDAB R ×0.1 3-second value. PM130EH only
HR 14004 uint32 CDAB R ×0.1 3-second value. PM130EH only
HR 14006 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 14008 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 14010 uint32 CDAB R % ×0.1 3-second value. PM130EH only
HR 14012 uint32 CDAB R V
HR 14014 uint32 CDAB R V
HR 14016 uint32 CDAB R V
HR 14336 int32 CDAB R kW
HR 14338 int32 CDAB R kvar
HR 14340 uint32 CDAB R kVA
HR 14342 int32 CDAB R ×0.001
HR 14348 uint32 CDAB R kW
HR 14350 uint32 CDAB R kW
HR 14352 uint32 CDAB R kvar
HR 14354 uint32 CDAB R kvar
HR 14356 uint32 CDAB R V Line-to-neutral with wiring 4LN3, 3LN3 or 3BLN3, otherwise line-to-line
HR 14358 uint32 CDAB R V
HR 14360 uint32 CDAB R A
HR 14466 uint32 CDAB R A
HR 14468 uint32 CDAB R Hz ×0.01
HR 14470 uint32 CDAB R %
HR 14472 uint32 CDAB R %
HR 14474 uint32 CDAB R Hz ×0.001 Available in newer firmware (revision A8 of the guide)
HR 11904 uint32 CDAB R
HR 14592 uint32 CDAB R V
HR 14594 uint32 CDAB R V
HR 14596 uint32 CDAB R V
HR 14598 uint32 CDAB R A
HR 14600 uint32 CDAB R A
HR 14602 uint32 CDAB R A
HR 14604 uint32 CDAB R kW
HR 14606 uint32 CDAB R kvar
HR 14608 uint32 CDAB R kVA
HR 14610 uint32 CDAB R kW
HR 14612 uint32 CDAB R kvar
HR 14614 uint32 CDAB R kVA
HR 14622 uint32 CDAB R kW
HR 14624 uint32 CDAB R kvar
HR 14626 uint32 CDAB R kVA
HR 14636 uint32 CDAB R kW
HR 14638 uint32 CDAB R kvar
HR 14640 uint32 CDAB R kW
HR 14642 uint32 CDAB R kvar
HR 14660 uint32 CDAB R A
HR 18816 uint32 CDAB R V
HR 18818 uint32 CDAB R V
HR 18820 uint32 CDAB R V
HR 18822 uint32 CDAB R A
HR 18824 uint32 CDAB R A
HR 18826 uint32 CDAB R A
HR 18834 uint32 CDAB R kW
HR 18836 uint32 CDAB R kvar