Therma TH 9XMP Modbus register map

Also covers TH 90MP, TH 91MP, TH 92MP, TH 93MP

Programmable modulating controller (ramps and soaks): process value, set points, alarms, PID settings, program execution, calibration values and identity registers, over Modbus RTU

  • Official
  • 86 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
86 holding registers
Groups
9
Translation tables
2
Revision
1 · 2026-11-10
Added
()
File
maps/therma/th9xmp.mbmap.json · 17 KB · history
SHA-256
7b27be48b9ac366c2dd6df8a469b54abf7eb60da2889fdf6de0e94592cffa703
Manufacturer
therma.com.br

Sources and notes

  • Controladores Microprocessados Modulantes Programáveis, TH 90MP / 91MP / 92MP / 93MP (Manual de Operação) · version 6ª edição (agosto de 2019), 2019-08
    linked in issue #122; chapter Protocolo de Comunicação MODBUS RTU, pages 38 to 42

Source: Controladores Microprocessados Modulantes Programáveis TH 90MP, TH 91MP, TH 92MP, TH 93MP (Manual de Operação), 6ª edição (agosto de 2019)

  • Modbus RTU on the optional RS-485 port. The manual lists registers 40001 to 40105 (function codes 03, 06 and 16, no broadcast); they are numbered from 1 here, so address 40001 is register 1 and address_base is 1. Reading a reserved address returns 0xFFFF. The manual does not name the factory baud rate, parity or controller number: 9600, no parity and 1 are placeholders. Options are 2400, 4800 or 9600 bit/s, no, odd or even parity, 8 data bits and 1 stop bit.
  • The register table in this edition skips addresses 40025 to 40046 (the page that should list them repeats the first page), so those registers are not included (RP-series controllers have registers there, but the layout may differ).
  • Values are 16-bit integers, signed where the range includes negative numbers. The manual does not say how decimals are sent: check against the display before applying a scale.
  • Packed BCD registers (CFPR, SEGP and AL xy) are read in hexadecimal. The relay bit order of register 40007 differs from the TH 9XRP manual. The parity codes (0 = none, 1 = odd, 2 = even) are as printed in this manual, whose label for 0 reads NOME (probably none); the TH 9XRP manual lists even before odd.
  • Registers 40071 to 40088 act on the segment chosen with PTN and SEGC, and apply only to the programmable series. Registers 40092 to 40099 are calibration values; do not write them without the manual's calibration procedure.
  • The software version, model number (A and B) and serial number (A, B and C) are plain 16-bit numbers; the manual does not say how they are formed. Written from the manufacturer's manual; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 int16 R Measured value; decimals depend on the input type (see notes)
HR 2 int16 R Active set point, between LSPL and USPL
HR 3 int16 RW Alarm 1 set point; the allowed range depends on the alarm mode ALD1
HR 4 int16 RW Alarm 2 set point; the allowed range depends on the alarm mode ALD2
HR 5 int16 RW Alarm 3 set point; the allowed range depends on the alarm mode ALD3
HR 6 uint16 RW 0 to 9999
HR 7 bool bit 0 R
HR 7 bool bit 1 R
HR 7 bool bit 2 R
HR 7 bool bit 3 R
HR 7 bool bit 4 R
HR 7 bool bit 5 R
HR 7 bool bit 6 R
HR 7 bool bit 7 R
HR 8 uint16 R
HR 9 uint16 R % Output level, 0 to 100 %
HR 10 uint16 RW Write 1 to store the settings written over Modbus; 0 = do not save
HR 11 uint16 R Remote set point, or the current set point of a programmable controller
HR 12 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 13 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 14 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 15 uint16 RW
HR 16 uint16 RW 0 to 100
HR 17 uint16 RW
HR 18 uint16 RW 0 to 3600
HR 19 uint16 RW 0 to 900
HR 20 uint16 RW
HR 21 uint16 RW 5 to 500
HR 22 uint16 RW 0 to 10
HR 23 uint16 RW 0 to 2000
HR 24 uint16 RW 0 to 3600
HR 47 uint16 RW
HR 48 int16 RW Between LSPL and USPL
HR 51 uint16 RW 0 to 5
HR 52 int16 RW -1999 to +9999
HR 53 int16 RW -1999 to +9999
HR 54 uint16 R Ambient temperature reading, 0 to 50
HR 55 uint16 RW 0 to 100
HR 56 uint16 RW Start of the analog input signal 1 (hexadecimal, see the manual's calibration mode)
HR 57 uint16 RW End of the analog input signal 1 (hexadecimal, see the manual's calibration mode)
HR 58 uint16 RW Start of the analog input signal 2 (remote) (hexadecimal, see the manual's calibration mode)
HR 59 uint16 RW End of the analog input signal 2 (remote) (hexadecimal, see the manual's calibration mode)
HR 60 uint16 RW s Closed-to-open time of the motor, 5 to 200 s
HR 61 uint16 RW Start of control analog output 1, 0 to 100
HR 62 uint16 RW End of control analog output 1, 0 to 100
HR 63 uint16 RW Start of control analog output 2, 0 to 100
HR 64 uint16 RW End of control analog output 2, 0 to 100
HR 65 uint16 RW 0 to 4095
HR 66 uint16 RW 0 to 4095
HR 67 uint16 RW
HR 68 uint16 RW
HR 71 uint16 RW Packed BCD, read as hex; see the manual
HR 72 uint16 RW 1 to 8
HR 73 uint16 R
HR 74 uint16 R 0 to 8
HR 75 uint16 RW 0 to 9999
HR 76 uint16 RW
HR 77 uint16 RW
HR 78 uint16 RW Packed BCD, read as hex; low digits 1 to 8
HR 79 uint16 RW
HR 80 uint16 RW
HR 81 uint16 RW 1 to 8
HR 82 uint16 RW 1 to 8
HR 83 int16 RW Set point of the selected segment
HR 84 uint16 RW 0 to 9999
HR 85 uint16 RW 0 to 100 %
HR 86 uint16 RW 5 to 9999
HR 87 uint16 RW Packed BCD, read as hex: one digit per alarm relay (A = AL1, B = AL2, C = AL3, D = 0)
HR 88 uint16 RW
HR 89 uint16 RW 1 to 127; changing it ends communication on the current address
HR 90 uint16 RW
HR 91 uint16 RW
HR 92 uint16 RW Calibration value; see the manual's calibration mode
HR 93 uint16 RW Calibration value; see the manual's calibration mode
HR 94 uint16 RW Calibration value; see the manual's calibration mode
HR 95 uint16 RW Calibration value; see the manual's calibration mode
HR 96 uint16 RW Calibration value; see the manual's calibration mode
HR 97 uint16 RW Calibration value; see the manual's calibration mode
HR 98 uint16 R Hexadecimal, read only
HR 99 uint16 R Hexadecimal, read only
HR 100 uint16 R Plain 16-bit number; how it maps to a version string is not stated
HR 101 uint16 R First part of the model number
HR 102 uint16 R Second part of the model number
HR 103 uint16 R First part of the serial number
HR 104 uint16 R Second part of the serial number
HR 105 uint16 R Third part of the serial number