Therma TH 9XRP Modbus register map

Also covers TH 90RP, TH 91RP, TH 92RP, TH 93RP

Programmable temperature controller (ramps and soaks), heating and cooling: process value, set points, alarms, PID settings, control outputs, program execution and serial settings

  • Official
  • 91 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
91 holding registers
Groups
7
Translation tables
2
Revision
1 · 2026-11-10
Added
()
File
maps/therma/th9xrp.mbmap.json · 18 KB · history
SHA-256
43ce0c0ec8ffc47024485a092bd682af1f46935dc4fa3901a5fbd9792be3efce
Manufacturer
therma.com.br

Sources and notes

  • Controladores Programadores para Aquecimento e Resfriamento, TH 90 RP / 91 RP / 92 RP / 93 RP (Manual de Operação) · version 8ª edição 06/2025, 2025-06
    linked in issue #121; table of register addresses, pages 39 to 42

Source: Controladores Programadores para Aquecimento e Resfriamento TH 90 RP, TH 91 RP, TH 92 RP, TH 93 RP (Manual de Operação), 8ª edição 06/2025

  • Modbus RTU on the optional RS-485 port (controllers ordered with serial communication). The manual lists registers as 40001 to 40091 (function codes 03, 06 and 16); they are numbered from 1 here, so address 40001 is register 1 and address_base is 1. The manual does not name the factory baud rate, parity or controller number: 9600, no parity and 1 are placeholders. Options are 2400, 4800 or 9600 bit/s, no, odd or even parity, 8 data bits and 1 stop bit.
  • Values are 16-bit integers, signed where the range includes negative numbers. The manual does not say how decimals are sent: fields with a decimal point (for example some input types) are probably sent without it, so check against the display before applying a scale.
  • Packed BCD registers (ALD, SETi, SETL, CFPR and AL xy) hold one digit per alarm relay (A = AL1, B = AL2, C = AL3, D unused) and are read in hexadecimal. Registers 40035, 40038, 40049, 40050, 40069 and 40070 are internal or reserved and are not listed.
  • The serial ID range is 1 to 63 in the register table and 1 to 31 in the parameter description. The parity code order (0 = none, 1 = even, 2 = odd) differs from the TH 9XMP manual.
  • Registers 40071 to 40088 apply only to programmable (ramp and soak) controllers. Registers 40083 to 40088 act on the segment chosen with PTN and SEGC.
  • Written from the manufacturer's manual; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 int16 R Measured value; decimals depend on the input type (see notes)
HR 2 int16 RW Active set point, between LSPL and USPL
HR 3 int16 RW Alarm 1 set point; the allowed range depends on the alarm mode ALD1
HR 4 int16 RW Alarm 2 set point; the allowed range depends on the alarm mode ALD2
HR 5 int16 RW Alarm 3 set point; the allowed range depends on the alarm mode ALD3
HR 6 uint16 RW 0 to 9999
HR 7 bool bit 0 R
HR 7 bool bit 1 R
HR 7 bool bit 2 R
HR 7 bool bit 3 R
HR 7 bool bit 4 R
HR 7 bool bit 5 R
HR 7 bool bit 6 R
HR 8 uint16 R
HR 9 uint16 R % Output level, 0 to 100 %
HR 10 uint16 RW Write 1 to store the settings written over Modbus; 0 = do not save
HR 11 uint16 R Remote set point, or the current set point of a programmable controller
HR 12 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 13 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 14 uint16 R Minutes left on a timed alarm (ALD = 9)
HR 15 uint16 RW
HR 16 uint16 RW Control output 1 percentage, 0 to 100
HR 17 uint16 RW
HR 18 uint16 RW 0 to 3600
HR 19 uint16 RW 0 to 900
HR 20 uint16 RW
HR 21 uint16 RW 5 to 500
HR 22 uint16 RW 0 to 10
HR 23 uint16 RW 0 to 2000
HR 24 uint16 RW 0 to 3600
HR 25 uint16 RW 0 to 900
HR 26 uint16 RW
HR 27 uint16 RW 0 to 100, or 0 to 10.0 with a decimal input
HR 28 uint16 RW 0 to 100, or 0 to 10.0 with a decimal input
HR 29 uint16 RW Control output 2 percentage, 0 to 100
HR 30 uint16 R % Output 2 level, 0 to 100 %
HR 31 uint16 RW
HR 32 int16 RW Lower end of the measuring range
HR 33 int16 RW Upper end of the measuring range
HR 34 uint16 RW
HR 36 uint16 RW 0 to 100
HR 37 uint16 RW 0 to 100
HR 39 uint16 RW Packed BCD, read as hex: one digit per alarm relay (A = AL1, B = AL2, C = AL3, D unused)
HR 40 uint16 RW Packed BCD, read as hex: one digit per alarm relay (A = AL1, B = AL2, C = AL3, D unused)
HR 41 uint16 RW Packed BCD, read as hex: one digit per alarm relay (A = AL1, B = AL2, C = AL3, D unused)
HR 42 uint16 RW 0 to 1000
HR 43 uint16 RW 0 to 1000
HR 44 uint16 RW 0 to 1000
HR 45 uint16 RW
HR 46 uint16 RW
HR 47 uint16 RW
HR 48 int16 RW Between LSPL and USPL
HR 51 uint16 RW 0 to 5
HR 52 int16 RW -1999 to +9999
HR 53 int16 RW -1999 to +9999
HR 54 uint16 R Ambient temperature reading, 0 to 50
HR 55 uint16 RW 0 to 100
HR 56 int16 RW Start of the analog input signal 1
HR 57 int16 RW End of the analog input signal 1
HR 58 int16 RW Start of the analog input signal 2 (remote)
HR 59 int16 RW End of the analog input signal 2 (remote)
HR 60 uint16 RW s Closed-to-open time of the motor, 5 to 200 s
HR 61 uint16 RW Start of control analog output 1, 0 to 100
HR 62 uint16 RW End of control analog output 1, 0 to 100
HR 63 uint16 RW Start of control analog output 2, 0 to 100
HR 64 uint16 RW End of control analog output 2, 0 to 100
HR 65 uint16 RW 0 to 4095
HR 66 uint16 RW 0 to 4095
HR 67 uint16 RW
HR 68 uint16 RW
HR 71 uint16 RW Packed BCD, read as hex; see the manual
HR 72 uint16 RW 0 to 8
HR 73 uint16 R
HR 74 uint16 R 0 to 8
HR 75 uint16 RW 0 to 9999
HR 76 uint16 RW
HR 77 uint16 RW Meaning of the pause function, see the manual
HR 78 uint16 RW Segment where the program starts
HR 79 uint16 RW
HR 80 uint16 RW
HR 81 uint16 RW 1 to 8
HR 82 uint16 RW 1 to 8
HR 83 int16 RW Set point of the selected segment
HR 84 uint16 RW 0 to 9999
HR 85 uint16 RW 0 to 100 %
HR 86 uint16 RW 5 to 9999
HR 87 uint16 RW Packed BCD, read as hex: one digit per alarm relay (A = AL1, B = AL2, C = AL3, D = 0)
HR 88 uint16 RW
HR 89 uint16 RW Controller number for the serial link; the table says 1 to 63, the text 1 to 31
HR 90 uint16 RW
HR 91 uint16 RW