Veris E34 Modbus register map
- Unofficial
- 50 registers
- Revision 2
Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus TCP and RTUdefault
- Unit ID
- 1default
- TCP port
- 502default
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 50 holding registers
- Revision
- 2
- Added
- ()
- File
- maps/veris/e34.mbmap.json · 7 KB · history
- SHA-256
- db7c8ae3645cadb214d25377758354df741a596d1f7b510185ecf674a49a607d
- Manufacturer
- veris.com
Sources and notes
Source: Modbus Database (Jibril Sharafi, MIT licence), table veris/e34; https://www.aggsoft.com/serial-data-logger/tutorials/modbus-data-logging/veris-e34.htm. Not verified against the manufacturer's documentation
- Veris E34.
- Converted automatically from the Modbus Database (MIT licence, Jibril Sharafi).
- Not verified against the manufacturer's documentation. The byte order is a guess: the source does not give one.
- Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 10101 | float32 ABCD | R | kWh | |||
| HR | 10109 | float32 ABCD | R | kW | |||
| HR | 10113 | float32 ABCD | R | kVA | |||
| HR | 10115 | float32 ABCD | R | ||||
| HR | 10119 | float32 ABCD | R | A | |||
| HR | 10121 | float32 ABCD | R | kW | |||
| HR | 10127 | float32 ABCD | R | A | |||
| HR | 10129 | float32 ABCD | R | kW | |||
| HR | 10135 | float32 ABCD | R | A | |||
| HR | 10137 | float32 ABCD | R | kW | |||
| HR | 10143 | float32 ABCD | R | A | |||
| HR | 10145 | float32 ABCD | R | V | |||
| HR | 10147 | float32 ABCD | R | V | |||
| HR | 10149 | float32 ABCD | R | Hz | |||
| HR | 10151 | float32 ABCD | R | ||||
| HR | 10153 | float32 ABCD | R | ||||
| HR | 10155 | float32 ABCD | R | ||||
| HR | 10157 | float32 ABCD | R | kWh | |||
| HR | 10301 | float32 ABCD | R | kWh | |||
| HR | 10309 | float32 ABCD | R | kW | |||
| HR | 10313 | float32 ABCD | R | kVA | |||
| HR | 10315 | float32 ABCD | R | ||||
| HR | 10317 | float32 ABCD | R | unit: degrees-angular | |||
| HR | 10319 | float32 ABCD | R | A | |||
| HR | 10321 | float32 ABCD | R | kW | |||
| HR | 10327 | float32 ABCD | R | A | |||
| HR | 10329 | float32 ABCD | R | kW | |||
| HR | 10335 | float32 ABCD | R | A | |||
| HR | 10337 | float32 ABCD | R | kW | |||
| HR | 10343 | float32 ABCD | R | A | |||
| HR | 10345 | float32 ABCD | R | V | |||
| HR | 10347 | float32 ABCD | R | V | |||
| HR | 10349 | float32 ABCD | R | Hz | |||
| HR | 10351 | float32 ABCD | R | ||||
| HR | 10353 | float32 ABCD | R | ||||
| HR | 10355 | float32 ABCD | R | ||||
| HR | 10357 | float32 ABCD | R | kWh | |||
| HR | 10501 | float32 ABCD | R | kWh | |||
| HR | 10509 | float32 ABCD | R | kW | |||
| HR | 10513 | float32 ABCD | R | kVA | |||
| HR | 10515 | float32 ABCD | R | ||||
| HR | 10517 | float32 ABCD | R | unit: degrees-angular | |||
| HR | 10519 | float32 ABCD | R | A | |||
| HR | 10521 | float32 ABCD | R | kW | |||
| HR | 10527 | float32 ABCD | R | A | |||
| HR | 10529 | float32 ABCD | R | kW | |||
| HR | 10535 | float32 ABCD | R | A | |||
| HR | 10537 | float32 ABCD | R | kW | |||
| HR | 10543 | float32 ABCD | R | A | |||
| HR | 10545 | float32 ABCD | R | V |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).