Veris E50 Modbus register map

  • Official
  • 91 registers
  • Revision 3 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
91 holding registers
Groups
3
Revision
3 · 2026-11-10
Added
()
File
maps/veris/e50.mbmap.json · 17 KB · history
SHA-256
c31540507e96691f82629b5f15c5000b1169b73b92b5dbe1e278213bdb40ec57
Manufacturer
veris.com

Sources and notes

  • E50B1, E50C2, E50C3 Compact Power and Energy Meter Installation Guide (Modbus Point Map) · version ZL0103-0D (0818), 2018-08
    Modbus point map, integer and floating point data

Source: E50B1, E50C2, E50C3 Compact Power and Energy Meter Installation Guide (Modbus Point Map), ZL0103-0D (0818)

  • Veris E50 (E50C2 full data set; E50C3 adds data logging).
  • Pulse counter 1 and 2 weights come from the energy-per-pulse setting (register 144). Registers 257 and 259 are both labelled real energy in the manual; the second is probably a duplicate listing.
  • Addresses follow the manual's numbering, which starts at 1 (address_base 1). 32-bit values and floats have the most significant register first.
  • Integer registers hold the value as an integer; the engineering value is the raw value times 10 to the power in the matching scale factor register (current, voltage, power, energy). Float registers need no scaling. Values the meter does not support in the chosen system type read as 0x8000 (integers) or NaN (floats).
  • The meter answers on both FC03 and FC04; the map lists the registers as holding.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint32 ABCD R kWh ×10^Scale factor E (energy)
HR 3 uint16 R kW ×10^Scale factor W (power)
HR 4 uint16 R kvar ×10^Scale factor W (power)
HR 5 uint16 R kVA ×10^Scale factor W (power)
HR 6 uint16 R ×0.0001
HR 7 uint16 R V ×10^Scale factor V (voltage)
HR 8 uint16 R V ×10^Scale factor V (voltage)
HR 9 uint16 R A ×10^Scale factor I (current)
HR 10 uint16 R kW ×10^Scale factor W (power)
HR 11 uint16 R kW ×10^Scale factor W (power)
HR 12 uint16 R kW ×10^Scale factor W (power)
HR 13 uint16 R ×0.0001
HR 14 uint16 R ×0.0001
HR 15 uint16 R ×0.0001
HR 16 uint16 R V ×10^Scale factor V (voltage)
HR 17 uint16 R V ×10^Scale factor V (voltage)
HR 18 uint16 R V ×10^Scale factor V (voltage)
HR 19 uint16 R V ×10^Scale factor V (voltage)
HR 20 uint16 R V ×10^Scale factor V (voltage)
HR 21 uint16 R V ×10^Scale factor V (voltage)
HR 22 uint16 R A ×10^Scale factor I (current)
HR 23 uint16 R A ×10^Scale factor I (current)
HR 24 uint16 R A ×10^Scale factor I (current)
HR 26 uint16 R Hz ×0.01
HR 27 uint32 ABCD R kVAh ×10^Scale factor E (energy)
HR 29 uint32 ABCD R kvarh ×10^Scale factor E (energy)
HR 31 uint16 R kVA ×10^Scale factor W (power)
HR 32 uint16 R kVA ×10^Scale factor W (power)
HR 33 uint16 R kVA ×10^Scale factor W (power)
HR 34 uint16 R kvar ×10^Scale factor W (power)
HR 35 uint16 R kvar ×10^Scale factor W (power)
HR 36 uint16 R kvar ×10^Scale factor W (power)
HR 37 uint16 R kW ×10^Scale factor W (power)
HR 38 uint16 R kvar ×10^Scale factor W (power)
HR 39 uint16 R kVA ×10^Scale factor W (power)
HR 40 uint16 R kW ×10^Scale factor W (power)
HR 41 uint16 R kvar ×10^Scale factor W (power)
HR 42 uint16 R kVA ×10^Scale factor W (power)
HR 43 uint32 ABCD R
HR 45 uint32 ABCD R
HR 47 uint32 ABCD R kWh ×10^Scale factor E (energy)
HR 49 uint32 ABCD R kWh ×10^Scale factor E (energy)
HR 51 uint32 ABCD R kWh ×10^Scale factor E (energy)
HR 138 int16 R
HR 139 int16 R
HR 140 int16 R
HR 141 int16 R
HR 257 float32 ABCD R kWh
HR 259 float32 ABCD R kWh
HR 261 float32 ABCD R kW
HR 263 float32 ABCD R kvar
HR 265 float32 ABCD R kVA
HR 267 float32 ABCD R
HR 269 float32 ABCD R V
HR 271 float32 ABCD R V
HR 273 float32 ABCD R A
HR 275 float32 ABCD R kW
HR 277 float32 ABCD R kW
HR 279 float32 ABCD R kW
HR 281 float32 ABCD R
HR 283 float32 ABCD R
HR 285 float32 ABCD R
HR 287 float32 ABCD R V
HR 289 float32 ABCD R V
HR 291 float32 ABCD R V
HR 293 float32 ABCD R V
HR 295 float32 ABCD R V
HR 297 float32 ABCD R V
HR 299 float32 ABCD R A
HR 301 float32 ABCD R A
HR 303 float32 ABCD R A
HR 307 float32 ABCD R Hz
HR 309 float32 ABCD R kVAh
HR 311 float32 ABCD R kvarh
HR 313 float32 ABCD R kVA
HR 315 float32 ABCD R kVA
HR 317 float32 ABCD R kVA
HR 319 float32 ABCD R kvar
HR 321 float32 ABCD R kvar
HR 323 float32 ABCD R kvar
HR 325 float32 ABCD R kW
HR 327 float32 ABCD R kvar
HR 329 float32 ABCD R kVA
HR 331 float32 ABCD R kW
HR 333 float32 ABCD R kvar
HR 335 float32 ABCD R kVA
HR 337 float32 ABCD R
HR 339 float32 ABCD R
HR 341 float32 ABCD R kWh
HR 343 float32 ABCD R kWh
HR 345 float32 ABCD R kWh